2
● 
For End Users: Viewing FactoryTalk Historian Data with FactoryTalk Historian ActiveView 
● 
● 
● 
● 
● 
23 
Relative and combined time expressions contain only a single 
operator: either a single plus sign (+) or a single minus sign (-). 
Additional operators can lead to unpredictable results. For example, 
the following are not valid time expressions: 
*+1d+4h
T-1d+12h
The name or short name for an interval used to denote FactoryTalk 
Historian time is not case-sensitive. 
FactoryTalk Historian Time String Examples 
Time Syntax Examples 
PI Time String 
Meaning 
06-dec-91 15:00:00 
3:00:00 pm on December 6, 1991 
Current time (now) 
25 
00:00:00 (midnight) on the 25th of the 
current month 
25-aug-92 
00:00:00 (midnight) on August 25th, 1992 
8: 
08:00:00 on the current date 
25 8: 
08:00:00 on the 25th of the current month 
00:00:00 on the current date (today) 
00:00:00 on the previous date (yesterday) 
sun, mon, tue, wed, thu, fri, sat 
00:00:00 on the most recent Sunday, 
Monday, ... Saturday 
*-1h 
One hour ago 
t+8h 
8:00:00 am today 
y-8h 
4:00:00 pm on the day before yesterday 
mon+14.5h 
2:30:00 pm last Monday 
Pdf to powerpoint conversion - application Library cloud:C# Create PDF from PowerPoint Library to convert pptx, ppt to PDF in C#.net, ASP.NET MVC, WinForms, WPF
Online C# Tutorial for Creating PDF from Microsoft PowerPoint Presentation
www.rasteredge.com
Pdf to powerpoint conversion - application Library cloud:VB.NET Create PDF from PowerPoint Library to convert pptx, ppt to PDF in vb.net, ASP.NET MVC, WinForms, WPF
VB.NET Tutorial for Export PDF file from Microsoft Office PowerPoint
www.rasteredge.com
● 
● 
● 
● 
● 
FactoryTalk Historian ActiveView User Guide 
24 
PI Time String 
Meaning 
sat-1m 
11:59:00 pm last Friday 
Time Interval Examples 
In interval expressions, a positive or unmarked interval is based on the start 
time, and a negative interval is based on the end time of a time expression. 
For example, if the start time is y, the end time is t, and the interval is +5h 
for a Sampled Data function, then interpolated values are generated at y, 
y+5h, y+10h, y+15h, and y+20h. If the interval is -5h, the interpolated 
values are generated at y+4h, y+9h , y+14h , y+19h  and t. 
PI Time String 
Meaning 
1.5h 
One and one-half hours 
32m 
Thirty-two minutes 
49s 
Forty-nine seconds 
+5h 
Five hours added to the time beginning with 
the start time. 
-5h 
Five hours subtracted from the time 
beginning with the end time. 
Change Time Range 
To change the time range represented by a dynamic symbol: 
1.  Scroll time ranges directly on a trend by using the Step Forward or 
Backward buttons 
on the time scale. These time changes are 
not saved with the symbol. 
-or- 
Click to select the symbol you want to change. To select multiple 
symbols, hold down the Shift key while selecting symbols. To change 
application Library cloud:Online Convert PowerPoint to PDF file. Best free online export
area. Then just wait until the conversion from Powerpoint to PDF is complete and download the file. The perfect conversion tool.
www.rasteredge.com
application Library cloud:C# powerpoint - PowerPoint Conversion & Rendering in C#.NET
And detailed C# demo codes for these conversions are offered below. C# Demo Codes for PowerPoint Conversions. PowerPoint to PDF Conversion.
www.rasteredge.com
2
● 
For End Users: Viewing FactoryTalk Historian Data with FactoryTalk Historian ActiveView 
● 
● 
● 
● 
● 
25 
the time range for every symbol in the display, click an unused area of 
the display. 
2.  Right-click and choose Time Range. The Change Time Range dialog 
box appears. 
3.  In the dialog box, select a range from the two lists or type a range. 
You can type time ranges in relative time, absolute time, or a 
combination of the two. For details, see Time Range Formats (page 
20). 
4.  Click OK. The new values for the selected dynamic symbols appear. 
application Library cloud:.NET PDF Document Viewing, Annotation, Conversion & Processing
XDoc.PDF SDK for .NET. RasterEdge XDoc.PDF for .NET is a professional .NET PDF solution that provides complete and advanced PDF document processing features.
www.rasteredge.com
application Library cloud:VB.NET PDF Converter Library SDK to convert PDF to other file
Conversion of MS Office to PDF. This guide give a series of demo code directly for converting MicroSoft Office Word, Excel and PowerPoint document to PDF file
www.rasteredge.com
● 
● 
● 
● 
● 
FactoryTalk Historian ActiveView User Guide 
26 
You can also use the scroll bar in the FactoryTalk Historian ActiveView 
toolbar
(page 27) to change the time range.
Trends with Future Time Ranges 
Trends with time ranges that extend into the future update normally if the 
end time uses an asterisk (
*
). Use an asterisk plus a time interval (for 
example, 
*+4h
) to display updating future time. The asterisk and plus sign 
are necessary; this feature does not work if you input the time in a format 
such as 
10-Jan-00
or 
T+10H
Change Time Zone 
You can show times in the Client or Server time zone for each FactoryTalk 
Historian ActiveView display. To see or change the time zone in use, right-
click the display and choose Time Zone, then choose either Client or 
Server. The current selection is shown with a check mark. 
If you choose Client time, all the times displayed are in your client 
machine's time zone. If you select Server time, all times appear with 
respect to the time zone of each Historian Server from which the tag data is 
retrieved. 
Any times that are input by the user (such as in changing the time range 
(page 24)) are interpreted in the selected time zone. 
application Library cloud:C# PDF Converter Library SDK to convert PDF to other file formats
C#.NET PDF - PDF Conversion & Rendering SDK for C#.NET. A best C# PDF converter control for adobe PDF document conversion in Visual Studio .NET applications.
www.rasteredge.com
application Library cloud:C# PDF Convert: How to Convert MS PPT to Adobe PDF Document
C# PDF Convert: How to Convert MS PPT to Adobe PDF Document. Provide Free Demo Code for PDF Conversion from Microsoft PowerPoint in C# Program.
www.rasteredge.com
2
● 
For End Users: Viewing FactoryTalk Historian Data with FactoryTalk Historian ActiveView 
● 
● 
● 
● 
● 
27 
The FactoryTalk Historian ActiveView Toolbar 
To display a toolbar, right-click the display and choose Tool Bar
Review the following for additional information: 
Tool 
Description 
Time Range scroll bar. To adjust the time range, 
select a dynamic symbol. (To select multiple symbols, 
hold down the Shift key. To change all the symbols in 
a display, click in an unused area of the display.) 
Move the slider or click the arrow buttons to change 
the time range being displayed. 
Return to the configured time range of a selected 
symbol. If no symbols are selected, every symbol in 
the display returns to its original time range. 
Displays the 
Layers
(page 12) dialog box. 
application Library cloud:C# PDF Convert: How to Convert Word, Excel, PowerPoint, Tiff
In addition to Word and Excel, Office PowerPoint is also supported by our SDK. Please click to see detailed C# programming demo for PPT to PDF conversion.
www.rasteredge.com
application Library cloud:VB.NET PowerPoint: Complete PowerPoint Document Conversion in VB.
resolution, bit depth, scaling, etc. Implement Conversion from PowerPoint to PDF in VB.NET, Converting PowerPoint document to PDF
www.rasteredge.com
● 
● 
● 
● 
● 
FactoryTalk Historian ActiveView User Guide 
28 
Indicates the presence and nature of status 
information. The appearance of the Status button 
on 
indicates a display's current state: 
No errors. 
A dynamic symbol in the display contains a 
warning. 
A symbol is reporting bad data or shutdown 
status. 
A symbol shows questionable data. 
A symbol shows annotated data. 
A symbol shows substituted data. 
Click this button to view the 
Status Report
(page 15) 
dialog box. 
Displays the FactoryTalk Historian ActiveView help. 
Displays the About FactoryTalk Historian 
ActiveView dialog box, which includes the 
FactoryTalk Historian ActiveView executable version 
number and ActiveX control information. 
To hide the toolbar, right-click the display and choose Tool Bar
Trend Interactions 
Trend Zoom 2x In or Out 
Click the Zoom In or Out button at the bottom of a trend to reduce or 
expand the time range of that trend by a factor of 2. In other words, if your 
time range is 8 hours, Trend Zoom 2x In divides the time range by 2 and 
displays the trend for a 4 hour time period. Trend Zoom 2x Out multiplies 
the time range by 2 and displays the trend for a 16 hour time period. 
application Library cloud:C# powerpoint - Convert PowerPoint to PDF in C#.NET
PowerPoint to PDF Conversion Overview. RasterEdge XDoc.PowerPoint empowers your C#.NET application with advanced PowerPoint to PDF conversion functionality.
www.rasteredge.com
application Library cloud:C# Windows Viewer - Image and Document Conversion & Rendering in
CSV Document Conversion. RasterEdge Windows Viewer SDK provides how to convert TIFF: Convert to PDF. Convert to Various Images. PDF Document Conversion.
www.rasteredge.com
2
● 
For End Users: Viewing FactoryTalk Historian Data with FactoryTalk Historian ActiveView 
● 
● 
● 
● 
● 
29 
You can remove changes to the time range by clicking the Revert button 
If a trend is too small these buttons may not appear. Double-click a trend to 
expand its size and display hidden buttons.
If there are no trend cursors, the Trend Zoom 2x command zooms in or 
out of the last portion of the time period. For example, if the initial time 
range is 60 minutes and you select Trend Zoom 2x In, the trend displays 
the last 30 minutes. Trend Zoom 2x Out displays 120 minutes adding 60 
minutes to the beginning of the trend. 
When a trend cursor is displayed, the command uses the trend cursor as the 
center of the zoomed trend. If several cursors are used, the last one set is 
used as the center of the zoomed trend. See Trend Cursors (page 10) for 
more information on trend cursors. 
Back and Forward Trend Buttons 
Click the Back and Forward buttons on the trend time scale to scroll the 
time forward or backward one increment. Each click adjusts the time scale 
by the current time range. 
For example, if a trend shows 4 hours of data, clicking the Back button 
shows the previous 4 hours and clicking the Forward button shows the 
next 4 hours. 
Browser Interactions 
Back and Forward Browser Buttons 
Click the Back and Forward buttons to switch to the previous or next Web 
page. 
● 
● 
● 
● 
● 
FactoryTalk Historian ActiveView User Guide 
30 
Refresh Button 
Data is refreshed automatically. You can click the Refresh button on the 
Internet Explorer toolbar to download a new HTML Web page, but it does 
not obtain either new data or a new Display Document. Display 
Documents are stored in your cache until they expire. 
Chapter 3 
31 
For Developers: Administering 
FactoryTalk Historian ActiveView 
Flow of Information 
When you open a Web page with FactoryTalk Historian ActiveView 
content, the flow of information occurs as follows: 
1.  Open Internet Explorer and browse to an Internet or intranet address 
(
URL
) for a stored HTML Web page. The Web page downloads from 
the Web server unless it is already cached on your PC. The PC's 
Internet settings determine how long an existing page is stored before 
it is discarded. 
2.  The Web page instructs the browser to create an instance of the 
ActiveView Control (
pbdctrl.ocx
) on your PC. 
3.  The Web page sets the DisplayURL (page 62) property of the 
FactoryTalk Historian ActiveView Control. This property tells where 
the Display Document (
.pdi
) is stored. The Control downloads the 
display (
.pdi
), which may be stored separately from the HTML page. 
The Control then opens 
acview.exe
. See also Expiration of 
Displays (page 34). 
● 
● 
● 
● 
● 
FactoryTalk Historian ActiveView User Guide 
32 
4. 
Acview.exe
connects to the Historian Server through the PI-SDK 
and retrieves actual data for the display. You can see the data on the 
display within the HTML page. 
Documents you may be interested