Configuring FactoryTalk Historian Chapter 6 
Rockwell Automation Publication HSE-IN024A-EN-E–December 2012 
91 
Historian Points. The Add Historian Points dialog box 
appears. 
4.
In the Add points to server list, select the FactoryTalk 
Historian SE server to which you want to add the points. 
5.
In the respective lists, select the data collection interface, 
default scan rate, and tag attributes for new points. 
6.
Click Browse Tags. The Tag Browser dialog box appears. 
7.
In the Tag Browser dialog box, select the folder from which 
you want to collect data points. The data points from the 
selected folder are displayed in the right pane of the dialog box. 
8.
Select the data points that you want to add, and click Add 
Tag(s) to List. The tags appear in the Selected tag(s) list at 
the bottom of the Tag Browser dialog box. 
9.
Click OK until you return to the FactoryTalk Administration 
Console. 
The point discovery wizard is a feature of FactoryTalk Historian SE 
that guides you through the process of finding data points from 
selected point sources, such as Linx Enterprise, Linx Classic, other 
OPC-DA Servers (for example, kepware opc), and HMI/ Alarm 
Servers (for example, FactoryTalk View). 
The point discovery wizard uses discovery rules to search for 
Historian points. Creating the rules is a part of the discovery 
process. The data points (tags) that match the rules you create are 
added to the FactoryTalk Historian SE server. The default rules are 
stored in the following XML file: 
C:\ProgramData\Rockwell Automation\FactoryTalk Historian\Auto 
Discovery and Configuration Rules.xml 
The rules that you define are saved in a user-defined XML file. The 
file is stored in the same location as the file with the default set of 
rules. The point discovery wizard uses the rules from both files. 
Adding Multiple Data Points 
Automatically 
Convert pdf to powerpoint presentation - application SDK tool:C# Create PDF from PowerPoint Library to convert pptx, ppt to PDF in C#.net, ASP.NET MVC, WinForms, WPF
Online C# Tutorial for Creating PDF from Microsoft PowerPoint Presentation
www.rasteredge.com
Convert pdf to powerpoint presentation - application SDK tool:VB.NET Create PDF from PowerPoint Library to convert pptx, ppt to PDF in vb.net, ASP.NET MVC, WinForms, WPF
VB.NET Tutorial for Export PDF file from Microsoft Office PowerPoint
www.rasteredge.com
Chapter 6  Configuring FactoryTalk Historian 
92 
Rockwell Automation Publication HSE-IN024A-EN-E–December 2012 
However, the rules defined in the user-defined XML file take 
precedence over the rules defined in the default XML file. 
To automatically discover Historian points with the wizard: 
1.
Go to Start > All Programs > Rockwell Software > FactoryTalk 
Administration Console. The FactoryTalk Administration 
Console appears. 
2.
In the Select FactoryTalk Directory dialog box, choose either 
Network or Local directory that you want to use, and click 
OK. 
3.
In the Explorer tree, right-click the application or area from 
which you want to search for data points, and select Discover 
Historian Points. The Discover New Historian Points 
dialog box appears. 
NOTE 
For more information on the point discovery wizard, click the help 
icon in the Discover New Historian Points dialog box. 
4.
In the Add points to server list, select the FactoryTalk 
Historian SE server to which you want to add the points. 
5.
In the Using data collection interface list, select the 
appropriate data collection interface. 
6.
In the Default scan rate list, select the time interval at which 
points will be collected. 
7.
Under Add points from these sources, select the sources 
from which you want to add the points. 
8.
Under Start searching from, click the tree at the starting 
point for the point search. If this is a new server, the root node 
in the tree is selected by default. 
9.
Click Edit Discovery Rules to create rules to be used during 
the discovery process. The FactoryTalk Historian Discovery 
Rule Editor dialog box appears. 
NOTE 
For more information on the Discovery Rule Editor click the help 
icon in the dialog box. 
application SDK tool:VB.NET PowerPoint: Use PowerPoint SDK to Create, Load and Save PPT
About This SDK. Specifically speaking, this VB.NET PowerPoint presentation document control of RasterEdge .NET Imaging SDK has been developed and provided to
www.rasteredge.com
application SDK tool:VB.NET PowerPoint: Sort and Reorder PowerPoint Slides by Using VB.
you can choose to show your PPT presentation in inverted clip art or screenshot to PowerPoint document slide & profession imaging controls, PDF document, image
www.rasteredge.com
Configuring FactoryTalk Historian Chapter 6 
Rockwell Automation Publication HSE-IN024A-EN-E–December 2012 
93 
10.
Select Enable data type filter to perform the search using the 
default discovery rule. 
NOTE 
When you check the Enable data type filter option, the 
auto-discovery mechanism will get all attributes that match the 
name, UDT, and data type rule. When you leave the option cleared, 
the mechanism will ignore the data type filter and only check the 
name and UDT rule. 
11.
Click Next to begin discovering points. The Discovering 
Historian Points dialog box displays the progress of point 
discovery. 
The discovered points are listed in the Confirm New 
Historian Points dialog box. 
12.
Click Confirm Points to accept the search result. 
13.
In the New Historian Points Discovery Complete dialog 
box, click Start. The FactoryTalk Historian SE server starts 
collecting the discovered points. 
14.
Click OK. 
You can view current and archive data using System Management 
Tools. In this section you will learn how to: 
View current data (page 93). 
View archive data (page 94). 
To view current data being collected by the FactoryTalk 
Historian SE server: 
1.
Go to Start > All Programs > Rockwell Software > FactoryTalk 
Historian SE > System Management Tools. The System 
Management Tools dialog box appears. 
2.
Under Collectives and Servers, select the FactoryTalk 
Historian SE server whose data you want to view. 
Viewing Current and 
Archive Data 
Viewing Current Data 
application SDK tool:VB.NET PowerPoint: Merge and Split PowerPoint Document(s) with PPT
individual slide is with the virtual presentation of PPTXPage in VB.NET to finish PowerPoint document splitting If you want to see more PDF processing functions
www.rasteredge.com
application SDK tool:C# Create PDF from OpenOffice to convert odt, odp files to PDF in
using RasterEdge.XDoc.Excel; using RasterEdge.XDoc.PowerPoint; How to Use C#.NET Demo Code to Convert ODT to PDF in C#.NET Project.
www.rasteredge.com
Chapter 6  Configuring FactoryTalk Historian 
94 
Rockwell Automation Publication HSE-IN024A-EN-E–December 2012 
3.
Under System Management Tools, select Data > Current 
Values. 
4.
From the menu bar, select Tools > Tag Search. The Tag 
Search dialog box appears. 
5.
Use the default settings and click Search. 
6.
From the list of tags that appears in the search results, select 
the tags you want to view, and click OK. The current values of 
the tags are displayed in the right pane of the System 
Management Tools dialog box. 
If you want the server to start updating the values for the tag, 
right-click it and select Start Updating Values. 
To view archive data that has been collected by the FactoryTalk 
Historian SE server: 
1.
Go to Start > All Programs > Rockwell Software > FactoryTalk 
Historian SE > System Management Tools. The System 
Management Tools dialog box appears. 
2.
Under Collectives and Servers, select the FactoryTalk 
Historian SE server whose data you want to view. 
3.
Under System Management Tools, select Data > Archive 
Editor. 
4.
In the (Tag Not Specified) tab, click 
. The Tag Search 
dialog box appears. 
5.
Use the default settings and click Search. 
6.
From the list of tags that appears in the search results, choose 
one of the tags you have selected in "Adding Individual Data 
Points Manually (page 90)", and click OK. 
Viewing Archive Data 
application SDK tool:C# PDF Text Extract Library: extract text content from PDF file in
But sometimes, we need to extract or fetch text content from source PDF document file for word processing, presentation and desktop publishing applications.
www.rasteredge.com
application SDK tool:VB.NET PowerPoint: VB Codes to Create Linear and 2D Barcodes on
2d barcodes of different types on PowerPoint presentation when you Here is a market-leading PowerPoint barcode add 2d barcodes QR Code, Data Matrix, PDF-417,
www.rasteredge.com
Configuring FactoryTalk Historian Chapter 6 
Rockwell Automation Publication HSE-IN024A-EN-E–December 2012 
95 
The list of events of the selected tag is displayed in the tab in 
the right pane of the System Management Tools dialog box. 
NOTE 
For more information on the Archive Editor, click 
7.
Verify that the system has returned archived values, and close 
the System Management Tools. 
After you have installed and verified the Historian server, configure 
your Historian server automatic daily backups. You must specifically 
schedule a backup task on the Historian server. 
Historian Archive files store the historical record of process data 
maintained by the Historian server. By default, the Historian server 
setup program creates three archive files. Make sure that the location 
of the archive directory contains enough free space for these files. 
The default archive file size of 256 MB might be too small for most 
systems. Rockwell Automation recommends that you change the 
default size based on the number of Historian Points, according to 
the recommendations in the Introduction to Historian SE Server 
System Management guide. 
NOTE 
The complete user documentation on FactoryTalk Historian SE is 
available in the Common Files\Rockwell\Help folder in your 
Program Files directory, and in the Redist\Docs folder on your 
FactoryTalk Historian SE installation DVD. 
The location for archives is typically on the largest drive on the 
server. Rockwell Automation recommends that you change the 
name of the archive directory from the default Server\dat to a more 
meaningful name, such as \arc. 
NOTE 
Use the Windows File System Compression feature with caution; it 
might slow down the access of the Historian server to archive files. The 
compression can save disk space, but it requires more CPU resources. 
Archiving and Backups 
application SDK tool:VB.NET Create PDF from OpenOffice to convert odt, odp files to PDF
using RasterEdge.XDoc.Word; using RasterEdge.XDoc.Excel; using RasterEdge.XDoc.PowerPoint; How to VB.NET: Convert ODT to PDF.
www.rasteredge.com
application SDK tool:VB.NET PowerPoint: Add Image to PowerPoint Document Slide/Page
image or clip art to your PowerPoint presentation in VB insert or delete any certain PowerPoint slide without & profession imaging controls, PDF document, tiff
www.rasteredge.com
Chapter 6  Configuring FactoryTalk Historian 
96 
Rockwell Automation Publication HSE-IN024A-EN-E–December 2012 
NOTE 
You need administrative rights to perform these steps. 
To restart the server: 
1.
Stop the server: 
1.
Go to Start > All Programs > Rockwell Software > 
FactoryTalk Historian SE > Stop FactoryTalk Historian SE. 
The server stopping process begins. The progress is 
displayed in the Command Prompt window. 
2.
Wait until the server is stopped and the Command Prompt 
window is closed. 
2.
Start the server: 
1.
Go to Start > All Programs > Rockwell Software > 
FactoryTalk Historian SE > Start FactoryTalk Historian SE. 
The server starting process begins. The progress is displayed 
in the Command Prompt window. 
2.
Wait until the server is started and the Command Prompt 
window is closed. 
Use the FactoryTalk Administration Console to configure the data 
server by adding new applications, areas, data server instances, and 
shortcuts to controllers. 
To open FactoryTalk Administration Console: 
1.
Go to Start > All Programs > Rockwell Software > FactoryTalk 
Administration Console. The FactoryTalk Administration 
Console dialog box appears. 
Restarting FactoryTalk 
Historian SE Server 
Configuring the Data Server 
Configuring FactoryTalk Historian Chapter 6 
Rockwell Automation Publication HSE-IN024A-EN-E–December 2012 
97 
Under Explorer, the tree of the FactoryTalk Directory you 
have selected using the FactoryTalk Directory Server Location 
Utility (page 28) is displayed. 
2.
From the menu bar, select Help > Contents to open 
FactoryTalk Help and learn more about configuring the data 
server. 
NOTE 
Refer to the information on configuring Historian interface connections 
in the Configuring FT Historian SE Security guide for details associated 
with the following procedure. 
To configure your Historian server to provide access for 
Historian Interfaces: 
1.
Identify all the Historian Interfaces that need access to the 
Historian server. 
2.
Consult the documentation for each interface and gather the 
information you need to configure the trust. You need to 
know the connection type. The type of connection determines 
what information you can use to define the trust. You also 
need to specify at least one of the following: 
The correct application name to define the trust. 
IP information for the connecting computer. 
3.
Decide how many trusts you will create. You can create 
explicit individual trusts for each Historian interface, or you 
can group them by subnet, host machine, or user name. A 
group of Historian interfaces can share the same privileges. 
4.
For each trust, create a PI identity. 
5.
Give that PI identity all the access permissions required by the 
trust. 
6.
Create a trust based on that PI identity. 
Configuring Historian 
Interface Connections 
Chapter 6  Configuring FactoryTalk Historian 
98 
Rockwell Automation Publication HSE-IN024A-EN-E–December 2012 
The interface collects data points (tags) from the data server and 
passes them to the FactoryTalk Historian SE server. Install the 
FactoryTalk Historian Live Data Interface component on the same 
computer as the data server. After installing the interface, configure 
the buffering service on the data server computer. The buffering 
service stores data in its memory so that in the event the interface is 
not able to communicate with the FactoryTalk Historian SE server, 
the data will not be lost. 
When you create a Historian server connection in the FactoryTalk 
Administration Console (page 75), a default Live Data Interface 
instance FTLD1 is created and registered. 
To register another instance of the FactoryTalk Historian Live 
Data Interface: 
1.
On the computer with the FactoryTalk Historian SE server 
installed, go to Start > All Programs > Rockwell Software > 
FactoryTalk Administration Console. 
2.
In the Select FactoryTalk Directory dialog box, click 
Network. 
3.
In the Explorer tree of the FactoryTalk Administration 
Console dialog box, go to System > Connections > 
Historical Data, right-click the FactoryTalk Historian server 
connection name, and select New Data Collection Interface. 
The Data Collection Interface Properties dialog box 
appears. 
4.
In the Computer hosting the interface drop-down list, select 
the name of the computer on which you have installed the data 
server and the FactoryTalk Historian Live Data Interface. 
5.
From the Startup Type drop-down list, choose Automatic. 
6.
Click Apply. 
Configuring FactoryTalk 
Historian Live Data 
Interface 
Registering Live Data 
Interfaces 
Configuring FactoryTalk Historian Chapter 6 
Rockwell Automation Publication HSE-IN024A-EN-E–December 2012 
99 
7.
Click Start to start the data collection service. Wait until the 
service status changes to Started. 
8.
Click OK. 
The new Live Data Interface instance is added to the server 
connection branch. 
For each instance of the FactoryTalk Historian Live Data Interface, 
a service (FTLD) is created and started when you start the interface. 
You define the service startup type (page 98) in the Data Collection 
Interface Properties dialog box in the FactoryTalk Administration 
Console. 
To view the status of the services, open the Services dialog box 
(Start > All Programs > Administrative Tools > Services). 
Live Data Interface Services 
Chapter 6  Configuring FactoryTalk Historian 
100 
Rockwell Automation Publication HSE-IN024A-EN-E–December 2012 
The services are removed when you delete the interface instances in 
FactoryTalk Administration Console. 
NOTE 
If you want to take advantage of the buffering feature, Rockwell 
Automation recommends that you install the FactoryTalk Historian Live 
Data Interface on a remote computer, typically the computer where the 
data server is installed. 
The buffering subsystem stores time-series values to memory when 
the remote interface computer cannot communicate with the 
FactoryTalk Historian SE server. 
NOTE 
FactoryTalk Historian SE supports the PI Buffer Subsystem only. It does 
not support the API Buffer Subsystem. 
To enable buffering on the computer with the FactoryTalk 
Historian Live Data Interface installed: 
1.
Go to Start > All Programs > Rockwell Software > FactoryTalk 
Historian SE System Management Tools. The System 
Management Tools dialog box appears. 
2.
From the menu bar, select File > Connections. The 
Connection Manager dialog box appears. 
3.
Select the FactoryTalk Historian SE server to which you want 
to connect. 
If the server name is not listed, do the following: 
1.
From the menu bar, select Server > Add Server. The Add 
Server dialog box appears. 
2.
In the Network Node text box, type the fully qualified 
domain name (FQDN) of the server. 
3.
Clear the Confirm check box, and click OK. The new 
server is added to the server list. 
This allows a remote client connection to be established 
with the FactoryTalk Historian SE server. 
Enable Buffering 