CoDeSys V2.3 
6-47 
'Extras' 'Show grid'  
With this command you can switch on and off the grid in the graphic window. When the grid is 
switched on, a check (ü) will appear next to the menu item. 
'Extras' 'Y Scaling' 
With this command you can change the preset Y scaling of a curve in the trace display. By 
doubleclicking on a curve you will also be given the dialog box 'Y-scaling'.  
As long as option Automatic is activated, the default scaling will be used, which depends on the type 
of the used variable. In case of enumeration variables the enumeration values will be displayed at the 
scale. In order to change the scaling, deactivate option 'Automatic' and enter the number of the 
respective curve (Channel) and the new maximum (maximum y scale) and the new minimum value 
(minimum y scale) on the y axis. 
The channel and the former value are preset. 
Dialog Box for Setting the Y Scale  
'Extras' 'Stretch' 
Symbol: 
With this command you can stretch (zoom) the values of the Sampling Trace that are shown. The 
beginning position is set with the horizontal picture adjustment bar. With repeated stretches that follow 
one-after-another, the trace section displayed in the window will increasingly shrink in size. 
This command is the counterpart to 'Extras' 'Compress'.  
'Extras' 'Compress' 
Symbol: 
With this command the values shown for the Sampling Trace are compressed; i.e., after this 
command you can view the progression of the trace variables within a larger time frame. A multiple 
execution of the command is possible. 
This command is the counterpart to 'Extras' 'Stretch'.  
6.9.2 'Extras' 'Save trace values' 
Use the commands of this menu to save traces (configuration + values) to files resp. to reload them 
from files to the project. Besids that a trace can be saved in a file in ASCII-format. 
Note: Regard the alternative way of storing and reloading traces by using the commands of menu
'Extras' 
'External Trace Configurations
' (XML format, *.mon-Datei) ! 
'Save Values' 
With this command you can save a Sampling Trace (values + configuration data). The dialog box for 
saving a file is opened. The file name receives the extension "*.trc". 
Adding pdf to powerpoint slide - C# Create PDF from PowerPoint Library to convert pptx, ppt to PDF in C#.net, ASP.NET MVC, WinForms, WPF
Online C# Tutorial for Creating PDF from Microsoft PowerPoint Presentation
add pdf to powerpoint; convert pdf to powerpoint slide
Adding pdf to powerpoint slide - VB.NET Create PDF from PowerPoint Library to convert pptx, ppt to PDF in vb.net, ASP.NET MVC, WinForms, WPF
VB.NET Tutorial for Export PDF file from Microsoft Office PowerPoint
converting pdf to powerpoint online; how to convert pdf into powerpoint
6-48 
CoDeSys V2.3 
Be aware, that here you save the traced values as well as the trace configuration, whereas Save 
trace in the configuration dialog only concerns the configuration data. 
The saved Sampling Trace can be loaded again with 'Extras' 'Load Trace'. 
'Load Values' 
With this command a saved Sampling Trace (traced values + configuration data) can be reloaded. 
The dialog box for opening a file is opened. Select the desired file with the "*.trc" extension.  
With 'Extras' 'Save Values' you can save a Sampling Trace. 
'Trace in ASCII-File' 
With this command you can save a Sampling Trace in an ASCII-file. The dialog box for saving a file is 
opened. The file name receives the extension "*.txt". The values are deposited in the file according to 
the following scheme: 
CODESYS Trace 
D:\CODESYS\PROJECTS\TRAFFICSIGNAL.PRO 
Cycle PLC_PRG.COUNTER PLC_PRG.LIGHT1  
0 2 1  
1 2 1  
2 2 1 
..... 
If no frequency scan was set in the trace configuration, then the cycle is located in the first column; 
that means one value per cycle has been recorded at any given time. In the other respects, the entry 
here is for the point in time in ms at which the values of the variables have been saved since the 
Sampling Trace has been run. 
In the subsequent columns, the corresponding values of the trace variables are saved. At any given 
time the values are separated from one another by a blank space. 
The appertaining variable names are displayed next to one another in the third line, according to the 
sequence (PLC_PRG.COUNTER, PLC_PRG.LIGHT1). 
6.9.3 'Extras' 'External Trace Configurations' 
Use the commands of this menu to save or reload traces (configuration + trace values) in files resp. 
from files, to load a trace from the controller to the project or to set a certain trace as that which should 
be used in the project. 
Note: Regard the alternative way of storing and reloading traces by using the commands of menu 
'Extras' 'Save 
Trace'
(Projektformat, *.trc-Datei, ASCII) ! 
'Save to file' 
With this command a trace (configuration + values) can be saved in a file in XML format. For this 
purpose the standard dialog for saving a file opens. Automatically the file extension *.mon will be 
used. 
A *.mon-file can be reloaded to a project with command 'Load from file'. 
'Load from file' 
With this command a trace (configuration + values), which is available in a file in XML format (*.mon, 
can be loaded into the project. The dialog for opening a file will open and you can browse for files with 
extension *.mon. The loaded trace will be displayed and added to the selection list in field 'Trace in the 
configuration dialog. If you want to set it as currently used project trace configuration, use command 
'Set as project configuration'. 
VB.NET PowerPoint: Add Image to PowerPoint Document Slide/Page
insert or delete any certain PowerPoint slide without affecting on C#.NET PPT image adding library. powerful & profession imaging controls, PDF document, tiff
change pdf to powerpoint; export pdf to powerpoint
VB.NET PowerPoint: Edit PowerPoint Slide; Insert, Add or Delete
To view C# code for adding, inserting or To view more VB.NET PowerPoint slide processing functions powerful & profession imaging controls, PDF document, image
drag and drop pdf into powerpoint; chart from pdf to powerpoint
CoDeSys V2.3 
6-49 
A *.mon-file can be created by using command 'Save to file'. 
Note: Regard the alternative way of saving a trace by using the commands of menu 
'Extras' 'Save trace 
values
'. 
'Load from controller' 
With this command the trace (configuration + values) which is currently used on the controller can be 
loaded to the CoDeSys project. It will be displayed in the trace window and can be set as active 
project trace configuration. 
'Set as project configuration' 
With this command the trace configuration which is currently selected in the list of available traces 
(field 'Trace' in the trace window) can be set as active configuration within the project. The selection 
list besides the currently used (top position) offers all traces which have been loaded to the project by 
command 'Load from file' from *.mon-files (e.g. for the purpose of viewing). 
6.10 Target Settings 
The "Target Settings" is an object of the 'Resources'. Here you define, which target shall be used for 
the project and how it will be configured. If a new project is started with 'Project' 'New', a dialog will 
open where the target, that means a predefined configuration for a target, has to be set. 
The list of available targets depends on which Target Support Packages (TSP) are installed on the 
computer. These describe platform specific basic configurations and also define, to which extent the 
configuration can be modified by the user in the CoDeSys Target settings dialogs. 
Please regard: If no TSP is available, only the setting 'None' will be offered in the target system selection box. 
This will switch to simulation mode automatically and no configuration settings will be possible.  
Target-Support-Package 
A Target Support Package (TSP) must be installed before starting by the aid of the installation 
program InstallTarget which might be part of the CoDeSys-Setup. 
A Target Support Package (TSP) contains all the files and configuration information necessary to 
control a standard platform with a program created in CoDeSys. What has to be configured: 
codegenerator, memory layout, PLC functionality, I/O modules. In addition libraries, gateway drivers, 
ini-files for error messaging and PLC browser have to be linked. The central component of a TSP is 
one or more Target files. A Target file directs to the files which are in addition necessary to configure 
the target. It is possible that several target files share these additional files. 
The default extension for a Target file is *.trg, the format is binary. Additive definitions are attached to 
the entries in the target file which determine whether the user can see and edit the settings in the 
CoDeSys dialogs. 
During installation of a TSP the target file for each target is put to a separate directory and the path is 
registered. The associated files are copied to the computer according to the information of a Info file 
*.tnf . The name of the target directory is the same as the targets name. It is recommended to store 
the target specific files in a directory which is named with the manufacturers name. 
The files which get installed with a TSP are read when CoDeSys is started. The target settings which 
are done in the CoDeSys dialogs will be saved with the project. 
Please Note: If you use a new target file or if you have changed the existing one, CoDeSys has to be restarted 
to read the updated version.  
VB.NET PowerPoint: VB Code to Draw and Create Annotation on PPT
PDF, TIFF, MS Word and Excel). Most of end users would like to install and use Microsoft PowerPoint software and create PPT slide annotation through adding a
create powerpoint from pdf; images from pdf to powerpoint
C# PowerPoint - How to Process PowerPoint
Use the provided easy to call and write APIs programmed in C# class to develop user-defined PowerPoint slide adding and inserting projects.
how to change pdf to ppt on; pdf picture to powerpoint
6-50 
CoDeSys V2.3 
6.10.1 Dialog Target Settings 
The dialog Target Settings will open automatically, when a new project is created. It also can be 
opened by selecting the menu item 'Target Settings' in the register 'Resources' in the Object 
Organizer. 
Choose one of the target configurations offered at Configuration. 
If no Target Support Package has been installed, only 'None' can be selected, which means working 
in simulation mode. If you choose one of the installed configurations it depends on the entries in the 
target files, which possibilities are left to customize this configuration in the CoDeSys dialogs. If you 
choose a target configuration, for which there exists no valid licence on the computer, CoDeSys asks 
you to choose another target. 
If a configuration is selected, which is provided with the entry "HideSettings" in the corresponding 
target file, you only can see the name of the configuration. Otherwise there are five dialogs available 
to modify the given configuration:  
1. Target Platform 
2. Memory Layout 
3. General 
4. Networkfunctionality 
5. Visualization 
Attention !: Please be aware, that each modification of the predefined target configuration can cause severe 
changes in performance and behaviour of the target ! 
Press <Default> if you want to reset the target settings to the standard configuration given by the 
target file.  
6.11 Parameter Manager 
TheParameter Manager is a a target specific component component of the CoDeSys programming 
system and must be activated in the target settings. (siehe Kap. ???).  
The Parameter Manager can be used to make variables of a CoDeSys IEC-program, constant 
parameters or specific system parameters accessible to all CoDeSys compatible systems in a network 
for the purpose of data exchange, typically via fieldbus. For this purpose in the editor you can create 
parameter lists and load down to and up from the runtime system.  
What are Parameters ?:
In this context parameters are: 
· process variables of the CoDeSys IEC project 
· process independent parameters 
· specific system parameters, predefined by the target system 
· functionblock instances or structure variables, arrays 
Each parameter is identified by a certain set of attributes like e.g.'default value', 'access rights', and 
especially by an unique access key ('Index', 'SubIndex', 'Name'), which can be addressed for reading 
or writing data from/to the parameter list. This data exchange can be done via communication 
services and it is not necessary to know any addresses of variables or to provide any extra functions. 
So the use of the Parameter Manager functionality it is an alternative to using Network Variables. 
What are Parameter Lists?:
Parameter lists are used for organizing the parameters and can be saved with the project and loaded 
to the local target system which is controlled by the corresponding IEC-program. For each type of 
parameters there is a corresponding type of parameter list. 
VB.NET PowerPoint: VB Codes to Create Linear and 2D Barcodes on
PowerPoint PDF 417 barcode library is a mature and This PowerPoint ISSN barcode adding control is compatible ITF-14 barcode on any PowerPoint document slide
pdf to ppt; add pdf to powerpoint slide
VB.NET PowerPoint: Read, Edit and Process PPTX File
SDK into VB.NET class application by adding several compact well, like reading Excel in VB.NET, Reading PDF in VB Independent from Microsoft PowerPoint Product.
convert pdf to powerpoint; convert pdf to ppt
CoDeSys V2.3 
6-51 
Each parameter entry is represented by a line in the parameter list. Each column of the list is 
representing one of the parameter attributes. In addition to a certain set of standard attributes also 
manufacturer specific attributes might be used for the description of a parameter in the Parameter 
Manager.  
It depends on the definitions in a target specific description file which attributes (columns) will be 
visible and editable in the Parameter Manager and in which way they will be arranged in a parameter 
list. If the description file is missing, the complete standard set of attributes will be displayed, each 
showing the default value.  
Besides lists for project variables and project constants the Parameter Manager also can handle lists 
for system parameters. Those are parameters which are fixly defined by the target system. Furtheron 
you can create lists for functionblock instances or structure variables which base on user-defined 
templates also created in the Parameter Manager.  
Due to the fact that the data are stored independently of the IEC-program, a parameter list for 
example can be used for saving 'recipes', which are preserved even if the program is replaced by 
another version. Furtheron a running PLC can be "feeded" with different recipes without the need of a 
re-download the program. 
Application example: 
Two or more parameter lists can be generated which have identical indexing, the objects of which, 
however, have different values. As required, the desired set of values can be loaded into the controller 
by loading the corresponding list. This way it is not necessary to "touch" the control program itself. 
Note: It is depending on the target system, whether the parameter manager will be regarded at the creation of a 
boot project
.  
6.11.1 Activating the Parameter Manager 
In the Resources tab in CoDeSys open the Target Settings, category Networkfunctionality
Activate option Support parameter manager and insert the desired Index- and Subindex ranges, 
which should be valid for the entries in the parameter lists of type 'Parameter' (constants) and 
'Variables' (project variables). 
C# PowerPoint: C# Guide to Add, Insert and Delete PPT Slide(s)
offer this C#.NET PowerPoint slide adding, inserting and guide for each PowerPoint slide processing operation & profession imaging controls, PDF document, tiff
convert pdf to editable ppt online; convert pdf file to powerpoint
VB.NET PowerPoint: Sort and Reorder PowerPoint Slides by Using VB.
easily VB.NET PPT image adding and inserting clip art or screenshot to PowerPoint document slide at powerful & profession imaging controls, PDF document, image
converter pdf to powerpoint; convert pdf file to powerpoint presentation
6-52 
CoDeSys V2.3 
6.11.2 Der Parameter Manager Editor... 
Overview 
In the Resources tab choose the object 'Parameter-Manager'. An editor window will open, where you 
can create, edit and store parameter lists and in online mode also can load them to the target system 
and monitor the current parameter values.  
Note 
In order to have available the Parameter Manager functionality in a CoDeSys project, the option ' 
Support Parameter Manager' in the Target Settings must be activated and appropriate index ranges 
must be defined there ! 
Parameter Manager Editor in CoDeSys 
The editor window is bipartited. The left part is used for navigation, it shows a list of all parameter lists 
currently loaded to the Parameter Manager. The right part contains a table editor, the columns titled 
with the names of the attributes.  
In the navigation window you insert, delete, rearrange or rename parameter lists of different types 
(Variables, Constant Parameters, Template, Instance, System Parameters).  
In the table editor you fill the lists with parameter entries. Each list type will show a special selection 
of attribute columns which can be edited or just are visible. Either this is defined by a target specific 
description file or the default settings will be taken. 
In online mode you can load the lists, you have created before, to the currently connected target 
system. You also can use the Parameter Manager functions to access them there for the purpose of 
data exchange with other systems (write values, upload). Furtheron in the Parameter Manager 
window you can monitor the current values of the parameters. If currently no online connection is 
established, the parameter lists just can be created locally and saved with the project. 
6.11.3 Parameter List Types and Attributes 
The Parameter Manager can handle the following parameter list types: 
Variables:  The entries in parameter lists of this type represent processing variables of the project.   
Parameters: The entries in parameter lists of this type represent parameters whose values are not 
attached by the process.  
System Parameters The entries in parameter lists of this type represent special constant 
parameters which are not attached by the process and which are determined by the target system. 
System Parameter lists cannot be deleted or renamed. 
Template:  A template does not contain parameter entries which can be directly accessed for the 
purpose of data exchange. In fact the entries provide a "basic attribute configuration" for the 
components of a functionblock or a structure. Thus a template can be used in parameters lists of type 
'Instance'.  
VB.NET PowerPoint: Extract & Collect PPT Slide(s) Using VB Sample
functions, like VB.NET PPT slide adding/removing, PPT read this VB.NET PowerPoint slide processing tutorial & profession imaging controls, PDF document, image
converting pdf to powerpoint; convert pdf to powerpoint presentation
VB.NET PowerPoint: PPTX to SVG Conversion; Render PPT to Vector
into VB.NET project by adding project reference PowerPoint files that end with .pptx file suffix can powerful & profession imaging controls, PDF document, tiff
convert pdf slides to powerpoint; convert pdf to ppt online
CoDeSys V2.3 
6-53 
Instance: The entries in parameter lists of this type represent parameter entries for variables which 
are of type of the a functionblock or structure, that means which are instances or structure variables. 
For an easy entering of the parameters a template can be used, which has also been created in the 
Parameter Manager before.   
Each list type will be displayed in the Parameter Manager Editor according to the attributes defined by 
a description file in XML format. If such a file is missing, default settings will be used. 
Instances and Templates 
An  Instance" parameter list  ...
... handles parameter entries, which represent a functionblock, a structure variable or an array. 
Instance lists for a functionblock or a structure are each based on a template which is also to be 
defined in the Parameter Manager for the respective functionblock resp. structure. Instance lists for 
arrays cannot use a template made in the Parameter Manager, but directly refer to the array which is 
used in the project. 
A "Template" parameter list ...
... does not contain parameters which are directly accessed for the purpose of data exchange. In fact 
it defines index and subindex offsets and certain attributes for parameter entries which represent the 
components of a functionblock or a structure. The template then can be used in a 'Instance' parameter 
list (see above), thus providing an easy way to create parameter entries for project variables which 
are instances of a functionblock or a structure. 
Creating a Template parameter list:
In the edit field next to Base POU enter the name of the functionblock or structure for which a 
parameter template should be created. Using the input assistant you can browse the available POUs 
of the project. Press Apply to enter the components of the chosen POU in the parameter list editor. 
Now edit the attribute fields and close the list to make it available for use in an 'Instance' list.  
The command Insert missing entries in the context menu or in the 'Extras' menu will cause an 
update of the entries according to the current version of the Base POU. This might be necessary after 
having deleted some lines or after having changed the Base-POU. 
Creating an Instance parameter list: 
Edit a Template from the selction list below the table. This list offers all templates currently available 
for functionblocks or structures in the Parameter Manager plus the option ARRAY, which you select, if 
you want to refer directly to an array used in your project. Press Apply to insert the predefined 
components to the parameter list table.  
In the edit field Base variable enter exactly that project variable (must be of type of the functionblock 
or the structure or the array  which is described by the chosen template), for the components of which 
you want to create parameter entries.  
Enter a Base index and Base subindex for the instance. The indices and subindices of the particular 
components then will be calculated automatically by adding the index resp. subindex values which are 
defined in the template for each component. They will be filled automatically to the respective attribute 
fields. 
The command Insert missing entries in the context menu or in the 'Extras' menu will cause an 
update of the entries according to the current version of the used template. That might be useful after 
having deleted entries or after the template has been modified. 
Example: 
Create a functionblock fubo with input- or output variables: a,b,c. In PLC_PRG define the following FB-
instances:  inst1_fubo:fubo; inst2_fubo:fubo.  
Now open the Parameter Manager in order to create parameter lists for the variables inst1_fubo.a, inst1_fubo.b, 
inst1_fubo.c and inst2_fubo.a, inst2_fubo.b, inst2_fubo.  Insert a parameter list which is of type 'Template' and 
name it "fubo_template". Define the Base-POU: "fubo". Press Apply and define some attributes for the 
components a,b,c: te. Inter alia enter the Index offsets: for a: 16#1, for b: 16#2, for c: 16#3. Also the SubIndex 
offsets, e.g. a: 16#2, b: 16#3, c: 16#4. 
6-54 
CoDeSys V2.3 
Now close the template and insert a parameter list which is of type 'Instance'. Choose template "fubo_template". 
Insert the Base variable "inst1_fubo". Define a Base index of e.g. 16#2300 and a Base subindex of 30 (you must 
regard the ranges defined in the target settings in tab Networkfunctionality !). Now press Apply to get displayed 
the indices which are calculated for the componentes a, b, c by the addition of base offsets and template 
defined offsets: Indices: 16#2301, 16#2302, 16#2303; SubIndices:16#23, 16#33, 16#43.  
6.11.4 Editing parameter lists 
Insert list 
Shortcut: Ins 
To insert a new parameter list in the Parameter Manage use the command 'Insert list...', resp. 'Insert 
new list' in the 'Insert' or context menu. The commands are available when the focus is in the empty 
navigation window resp. on an already existing entry in the navigation tree. 
The dialog 'Insert list' opens: 
Dialog 'Insert list' 
Insert a Name for the new parameter list (must be unique within the list type) and choose one of the 
following list types: 
Variables 
Entries for process variables 
Parameters 
Entries for constant parameters, whose values remain 
unattached by the process 
Template 
Template of attribut setting for the components of a 
functionblock or a structure 
Instance  
Entries for variables of type of a functionbolck or a 
structure, basing on the corresponding template (see 
above) 
System parameters 
Entries for parameters whose values are not attached by 
the process and which are defined by the target system 
After confirming the settings and closing the dialog with OK the new parameter list will appear as an 
entry in the navigation window, the list type beeing indicated by the icon. In the table editor the 
appropriate attributes will be displayed as column titles. Selection and order of the columns are 
CoDeSys V2.3 
6-55 
defined by a target specific description file, otherwise the default settings are used. Now you can edit 
the table, by entering a line for each desired parameter (see chapter 6.11.4, Editing parameter lists). 
Rename List 
The parameter list, which is currently marked in the navigation window, can be renamed by using the 
command 'Rename list' which is available in the 'Extras' menu or in the context menu. An edit field will 
open, which you also get when doing a double-click with the mouse on the list name. 
Cut / Copy /Paste list 
Shortcut: <Strg> + <X>, <Strg> + <C>, <Strg> + <V>,  
The command 'Cut' (Edit menu) resp. 'Cut list' (context menu) moves the currently marked list from 
the navigation window to a temporary buffer, so that you can reinsert it by the 'Paste' command at any 
other position in the navigation tree. Before re-inserting mark that list, above which you want to insert.  
The command 'Copy' resp. 'Copy list' also uses the temporary buffer, but the original navigation tree 
entry will be kept, and a copy will be added by 'Paste'.   
Delete list 
Shortcut: <Del> 
The list currently selected in the navigation window will be removed by the command 'Delete' ('Edit' 
Menu) resp. 'Delete list' ('Extras' or context menu).   
Please regard: In online mode this command will delete the corresponding list in the runtime system. 
Which columns (attributes) are displayed:
The currently marked parameter list (navigation window) will be displayed in the table window as 
defined by a target specifc description file resp. according to the default settings.  
This means that the attributes' values of each particular parameter will be displayed in a separate line 
according to the list-type-specific order and selection of columns.  
You can fade out and fade in columns by deactivating/activating them in the context menu when the 
cursor is pointing to any field of the list column title bar. 
For modifying the column move the dividers between the column title fields or use one of the 
commands available in the context menu when the cursor is placed on a column title field: Command 
Standard column width will set a standard width for all columns which makes them all visible in the 
window. Maximize width will change the width of the currently focussed column so that each entry 
will be fully displayed. 
Commands for editing a parameter list entry:
The following commands for editing a parameter list are available in the context menu resp. in the 
menus 'Insert' or 'Extras': 
Inserting /Deleting lines: 
Insert line resp. 
New line 
A new entry (line) will be inserted before that one where the 
cursor is currently placed.  
Line after resp. 
New line after 
Shortcut:<Ctrl><Enter> 
A new entry (line) will be inserted after that one where the cursor 
is currently placed. .   
Delete line 
The line, where the cursor is currently placed, will be deleted.  
Cut, copy, paste line 
These commands can be used to move (cut/paste) or to copy 
(copy/paste) the selected line. 
Editing attribute values: 
If a new line for a parameter entry is inserted, the attribute fields will be automatically filled with 
default values. See chapter 6.11.3, 'Parameter List Types and Attributes' for the possible 
6-56 
CoDeSys V2.3 
attributes. To enter or edit an attribute value, click on the corresponding field. An edit field will 
be opened, if the attribute is editable. The input assistant (<F2>) will be available in fields where 
a component of the CoDeSys project should be entered.  
Press <Enter> to close the entry.  
Using the arrow keys you can jump to another field.  
In order to toggle the input format between 'decimal' and hexadecimal' use the command 'Format 
Dec/Hex' in the 'Extras' menu. 
Options:
Below the table in the editor window there can be activated the following options (availability 
depending on list type): 
Download with program: At a login the list will be downloaded automatically to the controller. 
Synchronous actions: currently without function 
The sequence of entries within a parameter list can be sorted concerning an attribute (column) in 
ascending or descending order of the attribute values. This works in offline and in online mode. 
Perform a mouse-click on the field which contains the column title of the desired attribute. Thus the 
table lines will be re-sorted and in the column title field of the attribute am arrow symbol will be 
displayed, showing the current sorting (pointing upwards = ascending sort sequence, pointing 
downwards = descending sort sequence). 
6.11.5 Export / Import of parameter lists 
'Extras' 'Export' 
The command 'Export' of the 'Extras' menu can be used to export the lists of the Parameter Manager 
to a  XML-file. This file for example might be imported to another project by using the import function 
in the CoDeSys Parameter Manager. 
'Extras' 'Import' 
The command 'Import' of the 'Extras' menu can be used to import a  XML-file which describes 
parameter lists. This file for example might be created by using the export function in the CoDeSys 
Parameter Manager. 
6.11.6 Parameter Manager in Online Mode 
List transfer between Editor and Controlling Unit 
In online mode the parameter lists, which have been created in the editor, can be downloaded to 
resp. uploaded from the runtime system. Furtheron you can write single parameter values to the 
runtime system. 
Please regard: At login automatically a download of all parameter lists will be done for which the 
option 'Load with project' is activated !  
The current value of  each parameter is monitored in an additional column which is displayed in the 
parameter manager in online mode : 
The following commands are available in the 'Extras' menu for handling the list transfer between editor 
and controller: 
Delete list 
The list currently marked in the navigation window will be deleted from the 
Documents you may be interested