Delete Thresholds option
This option allows you to delete thresholds for any sensor on any device.
You select a device group or device in the   Navigation  view of the  Alarm
Configuration perspective to view the thresholds for that selection in the  Threshold
Alarms Configuration view. You can then select any thresholds, with the exception of
communication link status thresholds, and delete them from the thresholds list. The
thresholds will also be deleted from any notification policy to which they were added.
Note:  You can filter the list to view only certain thresholds ( Filter Thresholds icon).
You access the  Delete Thresholds option from the right-click menu in the  Threshold
Alarms Configuration view. When one threshold is selected, only that threshold is deleted.
When multiple thresholds are selected, they are deleted simultaneously.
Note:  Only user-created alarm thresholds can be deleted. Communication link status
thresholds are never deleted, regardless of whether they are included in the selection.
Button icons (Threshold Alarm Configuration view)
In addition to standard minimize and maximize icons, two icons are available to perform
specific  Threshold Alarm Configuration view functions.
Icon
Description
Use this  Configure Columns icon to
identify the attribute columns that appear in
the  Threshold Alarm Configuration view.
Use this  Filter Thresholds icon to enable
filters that prevent communication link
status and user-created thresholds,
thresholds with 'Enabled' set to 'No', and
thresholds of any severity, from appearing
in the list.
"Configure Threshold Attribute Columns" display
Use this display to identify the columns that appear in the  Threshold Alarm
Configuration view.
Section
Description
Threshold Attribute Columns
Lists all possible threshold attribute columns that
can appear in the view.
Threshold: Identifies the threshold.
Severity: The severity associated with the
threshold.
Label: The label of the device
StruxureWare Data Center Expert 7.2.1
161
Pdf to tiff conversion - application software utility:C# PDF Convert to Tiff SDK: Convert PDF to tiff images in C#.net, ASP.NET MVC, Ajax, WinForms, WPF
Online C# Tutorial for How to Convert PDF File to Tiff Image File
www.rasteredge.com
Pdf to tiff conversion - application software utility:VB.NET PDF Convert to Tiff SDK: Convert PDF to tiff images in vb.net, ASP.NET MVC, Ajax, WinForms, WPF
Free VB.NET Guide to Render and Convert PDF Document to TIFF
www.rasteredge.com
Hostname: The hostname, or IP address, if
no hostname is defined.
Enabled: Whether or not the threshold is
enabled.
Device Model: The device model, if known.
For example, Symmetra PX, for an APC/
MGE UPS.
Device Type: The type of device
Name: The name of the threshold.
IP Address: The IP address of the device.
Notification Policy: The name of the
notification policy or policies to which the
alarm is added.
Sensor: Identifies the sensor associated
with the alarm.
Sensor Type: The type of sensor.
Parameters: The settings defined on the
sensor.
"Filter Thresholds" display
Use this display to select the types of thresholds to exclude from the  Thresholds view.
Device Alarm Configuration view
This view in the  Alarm Configuration perspective shows device alarms that can be
configured for the device groups and devices selected in the Navigation view.
You select a device group or device in the  Navigation view to display the device alarms
that can be configured for that selection in the  Device Alarm Configuration view. The
device alarms associated with each device group or device are displayed by alarm type,
then by alarm name, then by device. The number of device alarms associated with each
device group or device is shown next to the alarm type or alarm, in parentheses.
You can select one or more device alarm types, alarm names, or alarm by device and modify
the alarm configuration. You can disable or enable alarms, modify the severity, add a
custom description, or modify the recommended action.
Note:  For additional alarm configuration, you can access the web interface for the device.
All device alarms for all devices are added to the  Default notification policy at device
discovery. You use the  Change Device Alarm Notification Policy option in the right-click
menu of the  Navigation view to change the notification policy associated with a device.
You can use the "Edit Notification Policy" display, accessed from the  Edit option in the
Notification Policies view, to add and remove a device group or device from a notification
policy. All the device alarms available for the selected device group or device are added or
removed simultaneously.
You can use the  Search fields to filter the list based on text you enter in the Navigation or
Device Alarm Configuration views; only items that contain the text you type are listed.
StruxureWare Data Center Expert 7.2.1
162
application software utility:Online Convert PDF file to Word. Best free online PDF Conversion
In addition to PDF to Tiff conversion, our .NET PDF document imaging SDK also supports conversion from Tiff image to PDF document in C# class.
www.rasteredge.com
application software utility:Online Convert PDF file to Tiff. Best free online PDF Tif
to TIFF converting library control (XDoc.PDF) is a multifunctional PDF document converting tool, which can perform high-fidelity PDF to TIFF conversion in an
www.rasteredge.com
When the results of a search are displayed, the background of the search field is shaded.
When you clear the search field, the background shading is removed and all items are
displayed.
Note:  You can hold the Ctrl key down to select multiple items.
You can use the right-click options and the button icons at the top of the view to do the
following:
• Enable or disable, modify the severity and recommended action, and add a custom
description on one or more alarms for the device group or device selected ( Edit
Device Alarm Configuration option).
• Locate a device in the Navigation view from the device alarm list ( Find Device in
Navigation Tree option).
• Show all the device alarms for the alarm type selected ( Expand Selection option).
• Access the "Configure Columns" display to select the attribute columns that appear
in the list ( Configure Columns icon (
)).
• Enable filters that hide various device alarm attributes. ( Filter Device Alarms icon
(
)).
Modifying device alarms
All device alarms use the same basic procedure and displays to modify the device alarm
configuration.
Note:  The same display is used to modify the device alarm configuration regardless of
whether you select:
• Edit Device Alarm Configuration, a right-click option in the  Navigation  view in
the  Alarm Configuration perspective.
• Edit Device Alarm Configuration, a right-click option in the  Device Alarm
Configuration  view in the  Alarm Configuration perspective.
• Edit Alarm Configuration, a right-click option in the  Active Alarms view in the
Monitoring perspective.
Modifying device alarms in the Alarm Configuration perspective
1. Select a device group or device in the   Navigation  view of the perspective, or select
a device alarm type, alarm name, or alarm by device in the  Device Alarm
Configuration view of the  Alarm Configuration perspective. Right-click to select
Edit Alarm Configuration.
2.
In the "Edit Device Alarm Configuration" display, define the alarm settings, and click
OK.
Modifying device alarms in the Active Alarms view
1. In the  Active Alarms view in the  Monitoring  perspective, select an alarm, and right-
click to select  Edit Alarm Configuration.
2. Select  This Instance to modify the device alarm configuration on the device reporting
the selected alarm only, or select All Instances to simultaneously modify the
configuration on every device for which that alarm is defined, regardless of whether
those devices are currently reporting an alarm.
3. Click  OK .
StruxureWare Data Center Expert 7.2.1
163
application software utility:C# TIFF: C#.NET Code to Convert TIFF Image File
Online C# tutorial for high-fidelity Tiff image file conversion from MS Office Word, Excel, and PowerPoint document. Convert PDF to Tiff Using C#.
www.rasteredge.com
application software utility:C# Create PDF from Tiff Library to convert tif images to PDF in C#
In addition to PDF to Tiff conversion, our .NET PDF document imaging SDK also supports conversion from Tiff image to PDF document in C# class.
www.rasteredge.com
"Edit Device Alarm Configuration" display
This display allows you to specify how device alarms reported by monitored SNMP or
Modbus devices are displayed in  StruxureWare Data Center Expert. You can modify
severity and recommended action, add a custom description, and disable or reenable
device alarms for the device groups, devices, or device alarms selected.
You access the display from the right-click menu in the  Device Alarm Configuration view
or the  Navigation view in the  Alarm Configuration perspective.
When you access the display from the  Navigation view, all the device alarms associated
with the device groups or devices selected are configured simultaneously.
When you access the display from the  Device Alarm Configuration view, you can specify
which device alarms associated with the device groups or devices you selected in the
Navigation view to configure. You can expand the selection to view and configure device
alarms by alarm type, alarm name, or by one or more devices reporting that alarm.
Note:  With the exception of the  Enabled option, device alarm settings you modify do not
apply to active alarms. The modified settings will apply the next time the alarm is triggered.
Element
Description
Enabled
Select to enable the device alarm, if it is disabled.
Note:  Device alarms are enabled by default.
Severity
Select the severity you want associated with the
device alarm:  Information Warning Error,
Critical, or  Failure.
Description
The alarm description provided by the device.
You cannot modify this description.
Custom Description
Provide a description you want included in the
device alarm notifications.
Recommended Action
The recommended action provided by the
device. You can modify the recommended action
to include instructions you want in the device
alarm notifications.
Reset to default
Reset the recommended action to default, if it has
been modified.
Button icons (Device Alarm Configuration view)
In addition to standard minimize and maximize icons, two icons are available to perform
specific  Device Alarm Configuration view functions.
Icon
Description
Use this  Configure Columns icon to
identify the attribute columns that appear in
the  Device Alarm Configuration  view.
StruxureWare Data Center Expert 7.2.1
164
application software utility:.NET PDF Document Viewing, Annotation, Conversion & Processing
Convert PDF to Word (.docx). Convert PDF to images, like Tiff. Convert image files to PDF. File & Page Process. Create new file, load PDF from existing files.
www.rasteredge.com
application software utility:VB.NET Create PDF from Tiff Library to convert tif images to PDF
Except PDF to Tiff conversion, RasterEdge SDK has related Tiff to PDF converting control, which supports conversion from Tiff image to PDF document in VB.NET
www.rasteredge.com
Icon
Description
Use this  Filter Device Alarms icon to
enable filters that prevent device alarms
with 'Enabled' set to 'No', and device alarms
of any severity, from appearing in the list.
"Filter Device Alarms" display
Use this display to select the types of device alarms to exclude from the  Device Alarm
Configuration view.
"Configure Device Alarm Attribute Columns" display
Use this display to identify the columns that appear in the  Device Alarm Configuration
view.
Section
Description
Device Alarm Attribute Columns
Lists all possible device alarm attribute columns
that can appear in the view.
Device Alarm: Identifies the device alarm.
Severity: The severity associated with the
device alarm.
Label: The label of the device.
Hostname: The hostname, or IP address, if
no hostname is defined.
Enabled: Whether or not the device alarm
is enabled.
Device Model: The device model, if known.
For example, Symmetra PX, for an APC/
MGE UPS.
Device Type: The type of device.
IP Address: The IP address of the device.
Notification Policy: The name of the
notification policy or policies to which the
alarm is added.
Device Definition File: The file the
StruxureWare Data Center Expert  server
uses to access information about the
environmental, power, and cooling alarms
at supported SNMP and Modbus devices.
Notification Policies View
StruxureWare Data Center Expert 7.2.1
165
application software utility:Online Convert Excel to PDF file. Best free online export xlsx
your C#.NET project, Microsoft Office like Word, Excel, and PowerPoint can be converted to PDF document. Generally speaking, following conversion types are
www.rasteredge.com
application software utility:C# TIFF: Easy to Convert PDF Document to TIFF Image File
Guide for Converting PDF File to TIFF Document in C#.NET Programming. C# TIFF Imaging: PDF to TIFF Conversion. C# Project: DLLs for Conversion from PDF to TIFF.
www.rasteredge.com
This view in the  Alarm Configuration perspective shows the default and user-created
notification policies.
You can create your own custom notification policies for the  StruxureWare Data Center
Expert server, and edit existing policies used to generate alarm notifications. A  Default
notification policy exists for the  StruxureWare Data Center Expert server. This default
notification policy cannot be deleted, but it can be edited and renamed.
Note:  A notification policy must include at least one threshold or device and one alarm
action before it can be used to generate alarm notifications.
You can use the button icons and the right-click options at the top of the view to perform
the following functions:
• Create a new notification policy, and add one or more alarm actions, and one or more
thresholds and devices, for the selected device group or device ( Create option and
icon 
).
• Edit the thresholds, devices, and alarm actions for the selected notification policy
( Edit option and icon 
).
Delete the selected notification policy ( Delete option and icon 
).
• Add, edit, delete, and test alarm actions for the selected notification policy using the
"Manage Alarm Actions" display ( Manage Alarm Actions 
).
Button icons (Notification Policies view)
In addition to standard minimize and maximize icons, four icons are available to perform
specific  Notification Policies view functions.
Icon
Description
Use the  Create Notification Policy icon to
create a new notification policy.
Note:  A notification policy must include at
least one threshold or device and one alarm
action before it can be used to generate
alarm notifications.
Use the  Edit Notification Policy  icon to
choose thresholds or devices to add or
remove, and to add, edit, or remove alarm
actions in the notification policy selected.
Use the Delete Notification Policy icon to
delete the notification policy selected.
Use the  Manage Alarm Actions icon to
add, edit, delete, or test alarm actions for the
notification policy selected.
Create Notification Policy option
StruxureWare Data Center Expert 7.2.1
166
application software utility:VB.NET PDF Converter Library SDK to convert PDF to other file
plug-in embeds several image compression mechanisms, it can be used for multiple PDF to image converting applications, like PDF to tiff conversion, PDF to JPEG
www.rasteredge.com
This option allows you to create a policy used by the  StruxureWare Data Center Expert
server to generate alarm notifications.
In the  Notification Policies view of the  Alarm Configuration perspective, you can create
a new notification policy, and choose the thresholds, and SNMP and Modbus devices, to
include in the new policy; view the thresholds and devices you have added, and add alarm
actions and configure options for those actions.
Note:  A notification policy must include at least one threshold or device and one alarm
action before it can be used to generate alarm notifications.
The right-click menu  Create in the  Notification Policy Name list, and the  Create
Notification Policy icon (
) in the  Notification Policies  view, provide access to the
"Create New Notification Policy" display.
Creating a New Notification Policy
In the  Alarm Configuration perspective, you can create a new notification policy in the
Notification Policies view. You select any existing notification policy, or use the  Create
Notification Policy icon 
, to create a new notification policy.
A notification policy must include at least one threshold or device, and one alarm action
before it can be used to generate alarm notifications. No thresholds or actions are included
by default in a new notification policy.
1.
Select the  Create Notification Policy icon or right-click option in the  Notification
Policies view.
2. In the "Create New Notification Policy" display, identify a policy name, choose the
thresholds, devices, and actions to add to the notification policy.
a. Click  Add to configure the alarm actions to add to the notification policy. Click
Manage Actions to create alarm actions, or modify or remove existing alarm
actions on the  StruxureWare Data Center Expert server. Check-mark one or
more actions to configure their notification options, check-mark the actions you
want to add to the notification policy, and click  OK  .
b. On the Thresholds tab, click  Choose Thresholds to identify the thresholds you
want to add to the notification policy. In the "Choose Thresholds" display, you
select a device group or device, select the thresholds you want to add to the
notification policy, and click the  Add Selected Thresholds button. Use the
Remove Selected Thresholds to refine the list. Click  OK to exit the display.
Note:  You can modify thresholds in the  Threshold Alarm Configuration view
in the  Alarm Configuration perspective.
c. On the Devices tab, click  Choose Devices to identify the devices you want to
add to the notification policy. In the "Choose Devices" display, you select a
device group or device you want to add to the notification policy, and click  OK .
Note:  All device alarms reported by the device or device group selected will be
added to the notification policy. You can modify the alarm configuration for alarm
types or individual device alarms in the  Device Alarm Configuration view in
the  Alarm Configuration perspective.
3. Modify the alarm actions, thresholds, or devices you have added to the notification
policy, if necessary, or click  OK  to exit the display.
"Create New Notification Policy/Edit Notification Policy" display
Use this display to create a new notification policy or edit an existing notification policy used
by the  StruxureWare Data Center Expert server to generate alarm notifications.
StruxureWare Data Center Expert 7.2.1
167
 Default notification policy exists for the  StruxureWare Data Center Expert server. This
default notification policy cannot be deleted, but it can be edited and renamed.
Note:  A notification policy must include at least one threshold or device and one alarm
action before it can be used to generate alarm notifications.
Three menus and one button icon in the  Alarm Configuration perspective provide access
to the  Create New Notification Policy display:
Right-click menu  Create in the  Notification Policy Name pane of the  Notification
Policies view.
Button icon  Create Notification Policy 
in the  Notification Policies view.
• Right-click menu Add Thresholds to Notification Policy in the   Navigation  view.
• Right-click menu Add Thresholds to Notification Policy in the  Threshold Alarm
Configuration view.
One menu and one button icon in the  Notification Policies view provide access to the
Edit Notification Policy display:
• Right-click menu  Edit in the  Notification Policy Name pane.
Button icon  Edit Notification Policy (
).
Element
Description
Policy Name
Identify the name of the notification policy.
Actions
Displays the actions and action options included
in the notification policy.
You can click on any column head
( Action Delay (min), Repeat, or  Interval
(min) ) to sort the list.
Add
Click to add actions to the notification policy.
Note:  To add alarm actions, use the "Manage
Alarm Actions" display, accessed by the
Manage Actions button.
Edit
Click to edit the options for the selected alarm
action.
Note:  To edit alarm actions, use the "Manage
Alarm Actions" display, accessed by the
Manage Actions button.
Remove
Click to delete an action from the notification
policy.
Note:  The action is deleted from the notification
policy only, and remains on the  StruxureWare
Data Center Expert server for future use. To
delete alarm actions from the  StruxureWare
Data Center Expert server, use the "Manage
Alarm Actions" display, accessed by the
Manage Actions button in the Add and Edit
Alarm Action displays, or the  Manage Alarm
Actions option in the  Alarm Configuration
menu.
Thresholds
Displays the thresholds included in the
notification policy.
Choose Thresholds
Click to select thresholds to include in the
notification policy.
StruxureWare Data Center Expert 7.2.1
168
Devices
Displays the devices included in the notification
policy.
Choose Devices
Click to select devices to include in the
notification policy
"Add or Edit Alarm Action" display
This display allows you to create or modify alarm actions for the notification policy selected.
Element
Description
List
The alarm actions on the  StruxureWare Data
Center Expert server.
Manage Actions
Accesses the "Manage Alarm Actions" display to
create, modify, or delete alarms from the
StruxureWare Data Center Expert server.
Options
Delay (minutes): Define how long the
StruxureWare Data Center Expert server
will wait to generate a notification after it
becomes aware of an alarm.
Repeat (number of times): Specify how
often the notification policy will repeat the
alarm action.
Repeat Until Alarm Clears: Select to
repeat the notification until the alarm
condition is resolved.
Interval (minutes): Define how long the
notification policy will wait before it repeats
the alarm action.
Include graph (if supported): Select to
include graphs in the notification, available
for threshold alarms only.
"Choose Thresholds" display
This display allows you to select the thresholds that will be part of a new or existing
notification policy.
You select a device group or device in the navigation tree to display the thresholds that can
be added to the notification policy for the selection.
You can add all the thresholds, or choose only those thresholds you want to add to the
notification policy.
Note:  You can hold the Ctrl key down to select multiple items in both the navigation tree
and the thresholds list.
The number of thresholds in the notification policy is displayed. You must click  OK  in the
"Choose Thresholds" display, and the "Create or Edit Notification Policy" display to apply
your changes.
You can use the search feature, table columns, and button icons to do the following:
StruxureWare Data Center Expert 7.2.1
169
• Type text in the  Search  field to filter the navigation tree or the thresholds list. You
can broaden or narrow your search using the Boolean operators AND, OR and NOT.
Only items that contain the text you specify in the  Search field are displayed. When
the results of a search are displayed, the background of the search field is shaded.
When you clear the  Search field, the background shading is removed and all items
are displayed.
Note:   Search  fields support the Boolean operators AND, OR, and NOT only.
• Access the "Configure Navigation Tree Labels" display to select up to three labels to
specify how monitored devices appear in the navigation tree ( Configure Navigation
Tree Labels icon 
).
Note:  Changes to the navigation tree labels in this display affect the navigation tree
in the   Navigation  view.
• Access the Configure Columns display to select the attribute columns that appear in
the list. ( Configure columns icon 
).
Note:  Changes to the columns in this display affect the columns in the
Thresholds view.
• Enable filters to specify the threshold attributes that appear in the list ( Filter
Thresholds icon 
).
• Click a column title to sort the list in ascending or descending order based on that
column's information.
The  Add Selected Thresholds and  Remove Selected Thresholds buttons are used to
add thresholds to or remove thresholds from the notification policy. When you add
thresholds to the notification policy, a 'plus-sign' icon (
) indicates which thresholds were
added. When you remove a threshold from the notification policy, the icon is removed.
Note:  When you remove thresholds from the notification policy, the thresholds remain in
the list for the device group or device, and can be readded, if desired.
"Choose Devices" display
This display allows you to select the devices that will be part of a new or existing notification
policy.
You checkmark the device groups or devices in the navigation tree to add all the alarms
reported by the devices for that selection to the notification policy. You can then modify the
configurations for individual device alarms in the  Device Alarm Configuration view.
Note:  All the devices monitored by the  StruxureWare Data Center Expert server are added
to the  Default notification policy at device discovery.
Note:  You must click  OK in the "Choose Devices" display, and the "Create or Edit
Notification Policy" display to apply your changes.
You can use the search feature to do the following:
• Type text in the  Search  field to filter the navigation tree or the thresholds list. You
can broaden or narrow your search using the Boolean operators AND, OR and NOT.
Only items that contain the text you specify in the  Search field are displayed. When
the results of a search are displayed, the background of the search field is shaded.
When you clear the  Search field, the background shading is removed and all items
are displayed.
Note:   Search  fields support the Boolean operators AND, OR, and NOT only.