An alert profile can include multiple alert sequences which allow you to customize which
alert actions are triggered, and when. For example, if sending e-mails to user 1 has not
resulted in an alarm returning to its normal condition within 20 minutes, you can start sending
e-mails to user 2, and start sending data to an FTP server.
How many alert profile sequences you use, and what actions they use, will depend on
exactly what you want to happen, and when, for alarm conditions, including alert threshold
violations, associated with the alert profile.
Managing alert profiles
Use the "Alert Profiles" wizard to add, modify, or delete one profile at a time.
1. Select "Alert Profiles" in the  Alert Settings option in the  NetBotz Appliance
Configuration option in the  Device menu.
2. In the "Select Parent Device" display, highlight the parent device (the individual
NetBotz Appliance) associated with the profile you want to configure, and click
Next.
Note:  Only one parent device can be selected: each NetBotz Appliance is the parent
device for the sensor, camera, and other serial devices, as well as the SNMP devices
it monitors.
3. In the "Select Alert Profile" display, do one of the following.
• Select the existing profile, and click  Next, to modify that profile's settings.
• Click  Add Profile, and then click  Next, to configure a new profile.
Select a profile, and click  Remove Profile.
Note:  If you delete a profile that is associated with an alert threshold, the alert
threshold will then use the default profile.
4. In the "Configure Alert Profile" display, do any of the following, and click  Finish .
• Edit the profile's name.
• Edit the  Suppress Alert Notifications until settings.
• Use the  Remove Sequence  button to delete any sequences you no longer want
a profile to use.
Use the  Add  and  Edit Sequence  buttons to access the "Edit Alert Profile
Sequence" display to configure the sequences you want the profile to use.
"Alert Profiles" wizard
This wizard uses a set of displays that step you through the process of adding, editing, or
deleting alert profiles.
"Select Parent Device" display
Use this display to select the parent device that can use the alert profile.
Note:  Each NetBotz Appliance is the parent device for the sensor, camera, and other serial
devices, as well as for the SNMP devices it monitors.
Parent
Description
NetBotz Appliance
Associates the alert profile with the selected
NetBotz Appliance for use with its alert
thresholds.
StruxureWare Data Center Expert 7.2.1
201
Bulk pdf to tiff converter - SDK Library API:C# PDF Convert to Tiff SDK: Convert PDF to tiff images in C#.net, ASP.NET MVC, Ajax, WinForms, WPF
Online C# Tutorial for How to Convert PDF File to Tiff Image File
www.rasteredge.com
Bulk pdf to tiff converter - SDK Library API:VB.NET PDF Convert to Tiff SDK: Convert PDF to tiff images in vb.net, ASP.NET MVC, Ajax, WinForms, WPF
Free VB.NET Guide to Render and Convert PDF Document to TIFF
www.rasteredge.com
"Select Alert Profile" display
Use this display to select the profile you want to manage.
Element
Description
List
Lists the existing alert profiles on the selected
parent device.
Add profile
Click to add a new profile.
Remove profile
Click to delete a profile. The default profile,
indicated by an asterisk, can never be deleted.
Note:  If you delete a profile that is associated
with an alert threshold, the alert threshold will
then use the default profile.
"Configure Alert Profile" display
Use this display to manage the alert sequences.
Each alert sequence allows you to add a new set of alert actions. Alert sequences allow
you to stagger notifications based on the duration of an alarm condition.
Note:  The alert profile must be associated with an alert threshold in order for it to operate.
Element
Description
Profile name
Identify a name for the profile.
List
Identifies the alert sequences associated with the
profile, by  Sequence Name, and their  Delay
(minutes) Repeats, and  Interval (minutes)
values.
Add sequence
Click to add a new alert sequence.
Edit sequence
Click to edit a selected alert sequence.
Remove sequence
Click to remove a selected alert sequence.
Suppress alert notifications
Select to suppress notifications for a defined
period of time for the alert thresholds that use the
profile.
"Add or Edit Alert Profile Sequence" display
Use this display to add or edit the alert sequences you want a profile to use.
Note:  Alert notifications will cease as soon as the triggering event clears; a cleared
notification is sent for each alert action, unless the alert action has  Do Not Send Return-
to-Normal Messages selected in the  Advanced tab of the alert action's configuration
display.
Element
Description
Label
Identify a name for the sequence.
Delay (minutes)
Define how long the NetBotz Appliance will wait
after it becomes aware of a threshold violation,
or other alarm, associated with the alert profile,
before it generates an alert notification.
StruxureWare Data Center Expert 7.2.1
202
SDK Library API:C# TIFF: Online C# Guide for TIFF to SVG Conversion
better testing or using of our .NET TIFF Converter SDK in new TIFFDocument(@"C:\Source\ Tiff\sample.tif"); // bulk operation for converting TIFF document to
www.rasteredge.com
SDK Library API:C# TIFF: How to Convert TIFF to GIF Using Sample C# Code
Converting Library, conversions from TIFF to PDF & vector SVG TIFFDocument doc = new TIFFDocument(@"C:\Source\Tiff\sample.tif"); // bulk operation for
www.rasteredge.com
Interval (minutes)
Define how long the sequence will wait before it
repeats the alert notification.
Repeat (number of times)
Identify how many times the sequence will repeat
itself.
Repeat until Alert Cleared
Select to have the sequence repeat itself
continuously.
Capture Settings
Select the capture settings for  Graphs,
Pictures, and  Maps that may be included with
the sequence's alert notifications:  Capture if
Requested Always Capture, or  Never
Capture.
Actions
Add Action: click to add an available alert action
to the actions list for the alert sequence.
Note:  Only alert actions available for the parent
device selected for the alert profile will be shown.
Remove Action: click to permanently
remove a selected alert action from the alert
sequence.
View Action: click to review or modify a
selected alert action's configuration.
Test Action: click to test a selected alert
action.
Alert Thresholds options
The  StruxureWare Data Center Expert allows you to create alert threshold settings for any
sensor value reported for monitored NetBotz Appliances.
Two basic types of alert thresholds are available: those that use numeric settings, and those
that use state settings.
• Numeric thresholds:
• Air Flow
• Audio
• Current (Amps)
• Dew Point
• Humidity
• Other Numeric Sensors
• Power (VA)
• Power (Watts)
• Temperature
• Voltage
• State thresholds:
• Door
• Door (Handle)
• Door (Lock)
• Dry Contact
• Motion Sensor
• Other State Sensors
Both types of thresholds allow you to do the following:
StruxureWare Data Center Expert 7.2.1
203
SDK Library API:VB.NET Image: How to Process & Edit Image Using VB.NET Image
VB.NET Image Processing Control SDK FAQs. Q 1: Does this VB.NET image processing control SDK allow developers to process & edit image in bulk?
www.rasteredge.com
SDK Library API:VB.NET TIFF: Convert TIFF to HTML Web Page Using VB.NET TIFF
like VB.NET PDF to HTML converter toolkit to convert PDF document to this VB.NET TIFF to HTML converter SDK support converting TIFF files to HTML in bulk?
www.rasteredge.com
• Create alert thresholds at one time for multiple sensors that monitor the same value
(for example, all are  Humidity sensors, or all are  Door sensors) at the NetBotz
Appliances monitored by the  StruxureWare Data Center Expert server.
• Assign a NetBotz Appliance alert profile to the specific sensor at the NetBotz
Appliance the profile was created on, and to all the sensors on the devices it monitors.
• Specify the severity for any defined threshold.
The Alert Settings menu in the  NetBotz Appliance Configuration  option of the
Device menu provides access to the alert thresholds. Each  Alert Threshold option allows
you to search some or all of the NetBotz Appliances monitored by the  StruxureWare Data
Center Expert server for sensors that match the selected option. You can then edit or add
thresholds for one of those sensors, or configure the same threshold for any number of
those sensors, simultaneously.
Alert thresholds and supported devices
Which alert thresholds can be used for sensors at the monitored devices depends on the
type of device.
• For a NetBotz Appliance, all alert threshold options, except  Power(VA) and  Power
(Watts), can be used to define alert thresholds on camera pods, sensor pods, and
other devices managed by the NetBotz Appliance.
NetBotz Appliances
When you create alert thresholds for a NetBotz Appliance, its sensor pods, camera pods,
and monitored SNMP devices, the threshold settings are set at the NetBotz Appliance. It is
the NetBotz appliance that stores the settings and sends the alerts to the  StruxureWare
Data Center Expert server.
Note:  Because NetBotz Appliance alert profiles are device-specific, you will not be able to
configure the profile for a threshold setting when configuring that setting for multiple
appliances.
Numeric alert thresholds
Numeric alert thresholds are thresholds defined for sensors that report numeric values.
There are nine specific types of numeric thresholds that can be set on numeric sensors.
Numerical threshold options
• All alert threshold options, except  Power (VA) and  Power (Watts), can be used to
set threshold settings at a NetBotz Appliance for itself, its sensor and camera pods,
and other devices it manages.
The  Other Numerical Sensors and  Other State Settings options, and for some
third-party devices,  Voltage , can be used to set threshold settings at a NetBotz device
for the full SNMP support devices it monitors.
Threshold
Value
Description
Air Flow
<n> ft/min
Settings for sensors that
measure air movement as feet
per minute.
Note:  Sensors that use a
different measurement, such as
cubic feet per minute (CFM) will
StruxureWare Data Center Expert 7.2.1
204
SDK Library API:C# PDF: Start to Create, Load and Save PDF Document
and it contains all document information of PDF file. It is an extension of BaseDocument. C# programmers can use PDFDocument object to do bulk operations like
www.rasteredge.com
SDK Library API:C# TIFF: Complete TIFF to PNG Image Conversion Using C# Project
a TIFF document TIFFDocument doc = new TIFFDocument(@"C:\Source\Tiff\sample.tif"); // bulk operation for It supports converting TIFF to PDF document, TIFF
www.rasteredge.com
be displayed under the  Other
Numeric Sensors option.
Audio
Relative number (0 - 100)
Settings for sensors that
measure the volume of sound.
Current (Amps)
Amps (0.0 - 100.0)
Settings for sensors that
measure current as total
amperage (amps).
Dew Point
°F (-40.0 - 122.0)/ °C (4.5 - 50.0)
Settings for sensors that
measure dew point as degrees
Fahrenheit (
°
F) or Celsius (
°
C).
Humidity
% (0 - 95)
Settings for sensors that
measure relative humidity as a
percentage (%).
Other Numeric Settings
Varied
Settings for sensors that
measure numeric settings not
reported for other  Alert
Thresholds options.
Power (VA)
VA
Settings for sensors that
measure power as total Volt-
amperes (VA).
Note:  Sensors that measure
power as a percentage of VA
will be displayed under the
Other Numeric Sensors
option.
Power (Watts)
W
Settings for sensors that
measure power as total watts
(W).
Temperature
°F (-40.0 - 122.0)/ °C (4.5 - 50.0)
Settings for sensors that
measure temperature as
degrees Fahrenheit (
°
F) or
Celsius (
°
C).
Voltage
V
Settings for sensors that
measure either AC or DC
voltage as total volts (V).
Numerical threshold types
Setting
Description
Minimum Value Threshold
An alarm occurs when the sensor's value is
below the  Minimum  setting.
Maximum Value Threshold
An alarm occurs when the sensor's value is
above the  Maximum  setting.
Range Threshold
An alarm occurs when the sensor's value is
outside the range defined by the  Minimum  and
Maximum settings.
Below Value for Time Threshold
An alarm occurs if the sensor's value is below
the  Minimum  setting for longer than the  Time
Allowed Below Minimum setting's delay.
Above Value for Time Threshold
An alarm occurs if the sensor's value is above
the  Maximum  setting for longer than the  Time
Allowed Above Maximum setting's delay.
StruxureWare Data Center Expert 7.2.1
205
SDK Library API:VB.NET Image: VB.NET Example to Load Image from .NET Graphics in .
are enabled to load an image or bulk ones from formats such as png, jpeg, gif, tiff and bmp provide powerful & profession imaging controls, PDF document, image
www.rasteredge.com
SDK Library API:VB.NET Image: VB Code to Download and Save Image from Web URL
able to download, view and save the bulk of image change the sample PNG to BMP/JPEG/TIFF/GIF provide powerful & profession imaging controls, PDF document, image
www.rasteredge.com
Rate of Increase Threshold
An alarm occurs if the sensor value increases by
more than the  Maximum Increase setting since
the last time the sensor's value was sampled. For
example, at a sensor that measures amps,  1
would result in an alarm when the amps
measured by the sensor increases by one amp.
Rate of Decrease Threshold
An alarm occurs if the sensor value decreases by
more than the  Maximum Decrease setting since
the last time the sensor's value was sampled. For
example, at a sensor that measures total watts
(W),  100 would result in an alarm when the watts
measured by that sensor goes down 100 watts.
Other numeric thresholds
The  Other Numeric Sensors  option allows you to set thresholds for numeric sensors that
monitor values not covered by the nine threshold-specific numeric options.
The following lists identify some common examples of numeric sensors you can configure
using the  Other Numeric Sensors option. The actual sensors will depend on the device
types managed by the  StruxureWare Data Center Expert server.
Note:  You can configure multiple sensors discovered for the  Other Numeric Sensors
option, when the sensors you select can all use the same threshold settings. For example,
battery and UPS age sensors, can be configured to use the same thresholds, as can utility,
input, and output voltage sensors.
UPS Battery Sensors:
• Battery Age
• Battery Runtime
Remaining
• Battery Capacity
Remaining
• Time Running on
Battery
Other UPS Sensors:
• UPS Age
• Input Frequency
• Output Frequency
• Output Load
• Output Power
Percent VA
Other Sensors:
• Max Number of
Output Relays
• Max Number of Input
Contacts
• Runhours of Fan
• Air Flowrate of Fan (in
cfm)
• Total Air Flow (in cfm)
• RPM Speed of Fan
State alert thresholds
State thresholds are thresholds defined for sensors that report state values.
State threshold options
Threshold
Value
Description
StruxureWare Data Center Expert 7.2.1
206
SDK Library API:C# Word: How to Compress, Decompress Word in C#.NET Projects
formats, such as JBIG2, JPEG2000, TIFF and other it easy to create single or bulk Word compression powerful & profession imaging controls, PDF document, image
www.rasteredge.com
SDK Library API:C# Imaging - Planet Barcode Generation Guide
formats. Creating single or bulk PLANET bar codes on documents such as PDF, Office Word, Excel, PowerPoint and multi-page TIFF. Empower
www.rasteredge.com
Door
Open or  Closed
Settings for sensors that
determine whether a door is
open or closed.
Door (Handle)
Up or  Down
Settings for sensors that
determine whether a door
handle is up or down.
Door (Lock)
Locked or  Unlocked
Settings for sensors that
determine whether a door lock
is locked or unlocked.
Dry Contact
Unknown No Fault, or  Fault
Settings for sensors that
determine the fault status of dry
contacts.
Motion Sensor
No Motion or  Motion Detected
Settings for sensors that detect
motion.
Other State Sensors
Varied
Settings for sensors that
measure state settings not
reported for other  Alert
Thresholds options.
State threshold types
Setting
Description
Alert State Threshold
An alarm occurs when the sensor's state
matches the  Alert State setting.
State Mismatch Threshold
An alarm occurs when the sensor's state does
not match the  Normal State setting.
Note:  This threshold setting is useful for sensors
that can report more than two states.
Alert State for Time Threshold
An alarm occurs when the sensor's state
matches the  Alert State setting for longer than
the  Time Allowed in Alert State setting's delay.
State Mismatch for Time Threshold
An alarm occurs when the sensor's state does
not match the  Normal State setting for longer
than the time defined by the  Time Allowed in
Abnormal State setting.
Note:  This threshold setting is useful for sensors
that can report more than two states.
State threshold types for rack access
Setting
Description
Door Forced Entry Threshold
An alert occurs when the door is open while the
handle is down and the lock is locked, enabled
by default.
Note:  When the “Allow handle down while door
open” option is selected, returning the handle to
the down position while the door is open will not
generate an alert.
Handle Forced Entry Threshold
An alert occurs when the handle is up while the
lock is locked, enabled by default.
Unscheduled Access Threshold
An alert occurs when unscheduled rack access
is attempted using a card, key, or remote
command, enabled by default.
StruxureWare Data Center Expert 7.2.1
207
Note:  If any of the other “Unscheduled” access
thresholds are used (Card, Key, or Remote), this
threshold should be removed from the lock
sensor.
Unscheduled Remote Access Threshold
An alert occurs when unscheduled rack access
is attempted using a remote command issued
from the NetBotz Appliance Advanced View or
Basic View, or the  StruxureWare Data Center
Expert console.
Note:  To allow remote access without
generating an alert, you must modify the
threshold schedule, disable the threshold for the
desired time frame, and disable the default
“Unscheduled Access Threshold”. An unlock
event will still be generated in the NetBotz
Appliance event log.
Unscheduled Card Access Threshold
An alert occurs when unscheduled rack access
is attempted using a card, or a door is opened
with a card, and left open past that card’s access
schedule.
Unscheduled Key Access Threshold
An alert occurs when unscheduled rack access
is attempted using a key.
Note:  To allow key access without generating an
alert (for example, during normal work hours),
you must modify the threshold schedule, disable
the threshold for the desired time frame, and
disable the default “Unscheduled Access
Threshold”. A key unlock event will still be
generated in the NetBotz Appliance event log.
Other state thresholds
The  Other State Sensors  option allows you to set thresholds for state sensors that monitor
operational states not covered by the three threshold-specific, state options.
The following lists identify some common examples of state sensors you can configure
using the  Other State Sensors option. The actual sensors will depend on the device types
managed by the  StruxureWare Data Center Expert server.
These options use the same set of four threshold settings as the other state threshold
options.
Note:  You can configure multiple sensors discovered for the  Other State Sensors option,
when the sensors you select use the same alert states settings. For example, all sensors
that use  On  and  Off states can be configured to use the same thresholds, as can all sensors
that use  Up  and  Down .
Active/Inactive:
• Button
• Temperature
Override Status
Open/Closed:
• Input Contact
• Output Relay
Fault/No Fault:
• Contact
• Input State
Connected/
Disconnected:
• Speakers
Multiple Statuses::
• Online
• Device Status
• Battery Status
• UPS Status
StruxureWare Data Center Expert 7.2.1
208
• Bypass
On/Off:
• Switch
• Outlet
• Alarm Device
• Test Relay
Other Settings:
• Ethernet Link
• UPS Input Voltage
(line neutral)
• Current Output
Phase
• External Microphone
Yes/No:
• UPS on Bypass
• UPS on Battery
• Audio Alarm
• Battery Low
• Overload
• Inverter Off
• UPS Over
Temperature
• Utility Power Failure
• Battery Needs
Replacement
• Battery Fault
• Communication
Status
• Alarm State
• Self-Test
• Runtime Calibration
• Reason for Last
Transfer to Battery
• Battery Charge Fault
• Rack ARU Operating
Status of Fan
• ARU Primary Power
Present
Managing numerical and state alert thresholds
All numeric and state thresholds use the same basic procedure and displays to add, edit,
or delete threshold settings.
Note:  The same displays are used to manage the alert threshold settings regardless of
whether you select the  NetBotz Appliance Configuration  option in the  Device menu,
the Device View  right-click menu, or  Map View  right-click menu, except for the "Select
Devices" display that appears only when you use the  Device menu options.
1. Select the sensor type you want to manage from the  NetBotz Appliance
Configuration option in the  Device menu or  Device View right-click menu.
• For a  Device  menu option, go to step 2.
• For a right-click menu option, go to step 3.
2. In the "Select Devices" display, select the devices you want to search for threshold
settings that match the selected sensor type, and click  OK .
3. In the "Select Thresholds" display, select the threshold type you want to manage from
the  Thresholds  drop-down menu; the display will list alert thresholds that have
already been defined for the threshold you select in that menu.
• Click  Add , and go to step 4 to define new threshold settings.
• Select one or more of the listed settings, click  Edit, and go to step 5 to edit those
settings.
• Select one or more of the existing thresholds, and click  Remove Selected , to
delete those threshold settings.
Note:  If you selected  Other Numeric Sensors or  Other State Sensors as
the  Alert Thresholds option, you will only be able to edit or delete one threshold
at a time.
4. In the "Select Sensors" display, select the sensor or sensors you want to add alert
thresholds for, and click  OK .
Note:  If the no sensors are available for the selected sensor type, a "No Sensors
Found" display will appear.
5. In the "Configure Settings" display, define the  Basic Advanced , and  E-Mail tab
settings, and click  OK .
6. In the "Select Thresholds" display, repeat steps 3 through 5, as needed, to edit or add
the settings for another  Thresholds  drop-down menu selection, or click  OK , to exit
the wizard.
StruxureWare Data Center Expert 7.2.1
209
"Select Devices" display
Use this display, which appears when you select the  Alert Thresholds option in the  Alert
Settings option in the  NetBotz Appliance Configuration option in the  Device menu, to
select the devices on which you want to create, edit, or remove an alert threshold.
The display lists all the devices monitored by the discovered NetBotz Appliances. You can
click the column headers to sort the list in ascending or descending order.
Column
Description
Parent Device
The IP address or hostname for a NetBotz
Appliance monitored by the  StruxureWare Data
Center Expert server.
Hostname
Identifies a device by its hostname or IP address,
when no hostname is defined.
Type
Identifies a device by its type.
Model
Identifies a device by its model number, when
known.
Location
Identifies the location of a device, when known.
"Select Thresholds" display
Use this display to edit or delete existing alert thresholds, or to add a new alert threshold.
The display lists all the settings currently defined for the  Thresholds  selection.
Element
Description
Thresholds
Select the alert threshold you want to view in the
display.
Filter
Filter the list based on text you enter in this box:
only existing thresholds that contain the text you
type are listed.
List
Select the previously defined threshold settings
that you want to edit or delete.
The following information is provided for the
listed threshold setting.
Threshold Name: the name of the
threshold setting.
Parent Device: the IP address of hostname
of the NetBotz Appliance that monitors a
camera pod, sensor pod, or other device.
Monitored Device: the device for which the
alert thresholds are displayed.
Sensor: the sensor with the defined setting.
Add
Click to add an alert threshold for the selected
sensor.
Edit
Click to edit a selected alert threshold.
Remove Selected
Click to delete a selected alert threshold from the
list.
StruxureWare Data Center Expert 7.2.1