Rockwell 
Automation 
Publicatio
n 1756-RM084U-EN-P - November 2015 
271 
Appendix B 
Import/Export revision history 
This appendix contains a history of enhancements made to the import/export 
feature since L5K version 1.1, major revision 1, and minor revision 1 that was 
included with Logix Designer, version 8.0. 
These releases of the import/export feature L5K version correspond to these 
releases of Logix Designer and the Logix Designer application. 
RSLogix 5000 /Logix Designer Version 
Import/Export 
L5K 
Version 
28.xx 
2.19 
27.xx 
2.18 
26.xx 
2.17 
24.XX 
2.15 
23.xx 
2.14 
21.xx 
2.12 
20.xx 
2.11 
19.xx 
2.10 
18.xx 
2.9 
17.xx 
2.8 
16.xx 
2.7 
15.xx 
2.6 
13.xx 
2.4 
12.xx 
2.3 
11.xx 
2.2 
10.xx 
2.1 
9.00 
2.0 
5.02 
1.2 
8.xx, 7.xx, 6.xx, 2.xx 
1.1 
1.23, 1.21 
1.0 
1.11, 1.10 
0.4 
Introduction 
Convert pdf to txt format online - Convert PDF to txt files in C#.net, ASP.NET MVC, WinForms, WPF application
C# PDF to Text (TXT) Converting Library to Convert PDF to Text
convert pdf to word editable text; convert pdf file to text document
Convert pdf to txt format online - VB.NET PDF Convert to Text SDK: Convert PDF to txt files in vb.net, ASP.NET MVC, WinForms, WPF application
VB.NET Guide and Sample Codes to Convert PDF to Text in .NET Project
convert pdf to rich text format; convert pdf to text
Appendix B                  Import/Export revision history 
272 
Rockwell 
Automation 
Publicatio
n 1756-RM084U-EN-P - November 2015 
The import/export feature supports backward compatibility for import 
operations. Therefore, the application can import .L5K or .L5X files that are 
generated by a previous version of the programming software. In some cases, an 
older .L5K file might not correctly import into a newer version of the application. 
The revision history in this appendix lists any conditions when backward 
compatibility for an import operation does not work as expected. 
The import/export feature does not support backward compatibility for export 
operations. Therefore, older versions of the application cannot read .L5K or .L5X 
files that are created with newer versions of the application. In some cases, a .L5K 
or .L5X file created with a newer version of the application may import with 
warnings into an older version of the application. In these cases, attributes on 
components may be set to default values during import. 
Each version of the application exports .L5K files with a specific import/export 
L5K version number. The application imports any .L5K file with the same major 
revision number and the same or lower minor revision number. The major L5K 
revision number increments when there are conditions such that the application 
cannot support backward compatibility for L5K import operations. The minor 
L5K revision number increments whenever there is a change in the file, such as a 
new module, an attribute is added, or the set of options for an attribute is changed, 
that does not affect backward compatibility for L5K import operations. 
.L5X files use the XML open standard format. L5X files do not have a revision 
number associated with them. 
Important: 
Use caution when copying and pasting components between different versions of the application. The Logix Designer only supports pasting to the same version 
or newer version of the application. Pasting to a prior version of RSLogix 5000 software is not supported. When pasting to a prior version, the paste action may 
succeed, but the results may not be what you expect. 
Version 2.19 of the Import/Export feature that is included with the Logix 
Designer application, version 28, includes these major enhancements: 
 Added Equipment Sequence functionality. 
 Added the Primary Action Set controller security attribute. 
 Added the Permission Set controller attribute. 
Version 2.18 of the Import/Export feature that is included with the Logix 
Designer application, version 27, includes these major enhancements: 
 Added the custom properties functionality. 
 Added the DownloadCustomProperties controller attribute. 
 Added the HMI Button Control (HMIBC) instruction. 
Backward compatibility 
Import/Export version 2.19 
Logix Designer application 
version 28 
Import/Export version 2.18 
Logix Designer application 
version 27 
C# Create PDF from Text to convert txt files to PDF in C#.net, ASP
Now you can convert text file to PDF document using Sample code for text to PDF converting in C# DocumentConverter.ToDocument(@"C:\input.txt", @"C:\output.pdf
convert pdf to word for editing text; convert pdf to word and edit text
C# PDF Converter Library SDK to convert PDF to other file formats
integrated into your C# program and convert PDF to .txt file with If you want to transform and convert PDF document to Jpeg image file format, this article
convert pdf file to text online; convert pdf to openoffice text document
Import/Export revision history                  Appendix B 
Rockwell 
Automation 
Publicatio
n 1756-RM084U-EN-P - November 2015 
273 
Version 2.17, major revision 2, minor revision 17, of the Import/Export feature 
that is included with the Logix Designer application, does not include any major 
enhancements.  
Version 2.15, major revision 2, minor revision 15, of the Import/Export feature 
that is included with the Logix Designer application, version 24 includes these 
major enhancements: 
 Removed support for the 1789-L60 controller. 
 Added the ParameterConnections controller element with the EndPoint1 
and EndPoint2 attributes. 
 Added the SafetyEnabled and NATActualAddress module attributes. 
 Added the SignatureID, SignatureTimestamp, SafetySignatureID Encoded 
Add-On Instruction attributes. 
 Added the Sequencing tag attribute. 
 Added the Alternate1UpdateMultiplier and Alternate2UpdateMultiplier 
motion group tag attributes. 
 Added the AxisUpdateSchedule axis tag attribute. 
 Added the UseAsFolder program attribute. 
 Added the ChildPrograms program element with the child_program_name 
attribute. 
There were no feature changes for the Import/Export feature for version 2.14, 
major revision 2, minor revision 14, included with the Logix Designer application, 
version 23. 
Version 2.12, major revision 2, minor revision 12, of the Import/Export feature 
included with Logix Designer application, version 21 includes these major 
enhancements: 
 Removed support for the following controllers: 1756-L61, 1756-L61S, 
1756-L62, 1756-L62S, 1756-L63, 1756-L63S, 1756-L64, 1756-L65, 1768-
L43, 1768-L43S, 1768-L45, 1768-L45S, 1769-L23E-QBF1, 1769-L23E-
QBFC1, 1769-L23-QBFC1, 1769-L31, 1769-L32C, 1769-L32E, 1769-
L35CR, 1769-L35E 
 Added the PassThroughConfiguration controller attribute. 
Import/Export version 2.17 
Logix Designer application 
version 26 
Import/Export version 2.15 
Logix Designer application 
version 24 
Import/Export version 2.12 
Logix Designer application 
version 21 
VB.NET PDF - Convert PDF with VB.NET WPF PDF Viewer
Description. 1. To Word. Convert PDF to Word DOCX document. 2. To TIFF. Export PDF to TIFF file format. 3. To TXT. Export and convert PDF to TXT file. 4. To Image
convert pdf into text file; .pdf to .txt converter
How to C#: File Format Support
PDF. Write pdf. DPX. Read 48-bit DPX. PGM. TIFF(TrueType Font File). Read all truetype convert to image. TXT(A text format). Convert ANSI-Encoding text format to
convert pdf to plain text online; converting pdf to searchable text format
Appendix B                  Import/Export revision history 
274 
Rockwell 
Automation 
Publicatio
n 1756-RM084U-EN-P - November 2015 
 Added Engineering Unit, State0, State1, Max, and Min attributes to 
datatype and tag components and Add-On Instructions parameters and 
local tags. 
 Added new attributes for analog alarm tags: HHOperShelve, HOperShelve, 
LOperShelve, LLOperShelve, ROCPosOperShelve, ROCNegOperShelve, 
ProgUnshelveAll, HHOperUnshelve, HOperUnshelve, LOperUnshelve, 
LLOperUnshelve, HHMinDurationEnable, HMinDurationEnable, 
LMinDurationEnable, LLMinDurationEnable, ROCPosOperUnshelve, 
ROCNegOperUnshelve, ShelveDuration, MaxShelveDuration. 
 Added new attributes for digital alarm tags: OperShelve, ProgUnshelve, 
OperUnshelve, ShelveDuration, MaxShelveDuration 
Version 2.11, major revision 2, minor revision 11, of the import/export feature 
included with Logix Designer, version 20 includes these major enhancements: 
 Additional controllers supported. 
 SecurityAuthorityID, SecurityAuthorityURI, ChangesToDetect, and 
Trusted Slots attributes added to the controller component. 
 SignatureRunModeProtect attribute added to the safety controller system. 
 ShutdownParentOnFault, DrivesADCMode, DrivesADCEnabled, and 
UserDefinedCatalogNumber added to the module component. 
 ConfigScript sub section added to the L5K and L5X formats of the module 
component. 
 Priority, InputConnectionType, OutputRedundantOwner, 
InputProductionTrigger, ConnectionPath, InputTagSuffix, and 
OutputTagSuffix attributes added to the module connection component. 
 LargePackageUsage attributed added for message tags. 
 MasterInputConfigurationBits and MasterPositionFilterBandwidth 
attributes added for coordinate system tags. 
 AdditionalBusCapacitance and InterpolatedPositionConfiguration 
attributes added for axis tags. 
 Internet Protocol, Ethernet Ports, and Ethernet Network controller 
configuration objects added for controllers that have embedded Ethernet 
ports in them. 
Version 2.10 (major revision 2, minor revision 10) of the import/export feature 
included with Logix Designer, version 19 includes these major enhancements: 
 Procedures for configuring source-protected components in encrypted or 
clear text format. 
Import/Export version 2.11 
Logix Designer version 20 
Import/Export version 2.10 
Logix Designer version 19 
C# WPF PDF Viewer SDK to convert and export PDF document to other
Description. 1. To Word. Convert PDF to Word DOCX document. 2. To TIFF. Export PDF to TIFF file format. 3. To TXT. Export and convert PDF to TXT file. 4. To Image
c# convert pdf to text file; batch convert pdf to txt
VB.NET TIFF: TIFF Text Extractor SDK; Extract Text Content from
In this online tutorial, we will offer you information on new rectangle(0, 0, 300, 300), @"C:/extract.txt"). extracted text content to other format files, like
convert pdf to text for; change pdf to text file
Import/Export revision history                  Appendix B 
Rockwell 
Automation 
Publicatio
n 1756-RM084U-EN-P - November 2015 
275 
 ControlLogix 1756-L73 and 1756-L75 controllers added to the list of 
processor types. 
Version 2.8, major revision 2, minor revision 9, of the import/export feature 
included with Logix Designer, version 18 includes these major enhancements: 
 Addition of ControlLogix 1756-L73 and 1756-L75 controller types and 
Compact GuardLogix®1768-L43S and 1768-L45S controller types. 
 Addition of CanUseRPIFromController attribute to the Controller 
component. 
 Addition of the WatchList element to a Controller declaration. 
 Addition of TagType and AliasFor parameters to the L5X format of the 
Add-On Instruction definition 
 Addition of safety abilities to Add-On Instructions. 
 Addition of the External Access and Constant attributes to Tag 
components. 
 Addition of new attributes to axis tags, 
This version of import/export also supports the AXIS_CIP_DRIVE tag. For 
information, see the Integrated Motion on the Ethernet/IP Network 
Configuration and Startup User Manual, publication MOTION-UM003. 
 Addition of MinimumRPI, MaximumRPI, and DefaulRPI attributes to ta 
produced Tag component. 
 Addition of attributes to support unicast communication for I/O modules 
on EtherNet/IP networks: 
 Unicast attribute added to the Connection element of the Module 
component. 
 Unicast attribute added to the SafetyProducedTag component. 
 UnicastPermitted attribute added to the SafetyConsumedTag 
component. 
Version 2.8, major revision 2, minor revision 8, of the import/export feature 
included with Logix Designer, version 17 includes these major enhancements: 
 1756-L63S GuardLogix® safety controller and safety relay ladder 
instructions. 
Import/Export version 2.8 
Logix Designer version 18 
Import/Export version 2.8 
Logix Designer version 17 
C# PDF - Extract Text from Scanned PDF Using OCR SDK
NET convert PDF to text, C#.NET convert PDF to images C:\input.pdf"); BasePage page = pdf.GetPage(0 ocrPage.Recognize(); ocrPage.SaveTo(MIMEType.TXT, @"C:\output
pdf image to text; changing pdf to text
C# TIFF: Use C#.NET Code to Extract Text from TIFF File
Moreover, text content, style, and format of original Tiff image can be retained txt"; // Save ocr result as other documet formats, like txt, pdf, and svg.
c# read text from pdf; batch convert pdf to text
Appendix B                  Import/Export revision history 
276 
Rockwell 
Automation 
Publicatio
n 1756-RM084U-EN-P - November 2015 
 1756-L65, 1768-L45, 1769-L23E-QB1, 1769-L23E-QBFC1, 1769-L23-
QBFC1 controllers. 
 A tag IncludeConnectionStatus attribute is no longer exported. 
 The L5X format for rung export has been modified such that rung UIDs are 
no longer included in the export format. 
Version 2.7, major revision 2, minor revision 7, of the import/export feature 
included with Logix Designer, version 16 includes these major enhancements: 
 1756-L61S and 1756-L62S GuardLogix safety controllers and safety relay 
ladder instructions. 
 1756-L64 ControlLogix controller. 
 Updated CONTROLLER example. 
 Add-On Instructions. 
 Alarms 
 New alarm instructions: ALMA, ALMD. 
 Digital and analog alarm tags. 
 New instructions 
 Motion instructions: MCT, MCTP. 
 Safety instructions: DIN, RIN, ESTOP, ENPEN, LC, FPMS, ROUT, 
THRS. 
 Addition of ShareUnusedTimeSlice and 
InhibitAutomaticFirmwareUpdate attributes to the CONTROLLER 
component. 
 Addition of UserDefinedVendor, UserDefinedProductType, 
userDefinedProductCode, UserDefinedMajor, and UserDefinedMinor 
attributes to the MODULE component. 
 Addition of LINT data type. 
 Addition of Unicast and UnicastPermitted attributes to the TAG 
component. 
 Additional attributes and valid values for existing attributes to AXIS tags. 
 Additional attributes for COORDINATE_SYSTEM tags. 
 Source protected routines and Add-On-Instructions appear as encrypted 
data in export files. In previous releases, source protected data was not 
exported at all. 
Import/Export version 2.7 
Logix Designer version 16 
C# PDF Text Extract Library: extract text content from PDF file in
PDF text to another PDF file, TXT and SVG or partial text content from target PDF document file text content, and export extracted text with customized format.
convert pdf to text vb; convert pdf to text on
Import/Export revision history                  Appendix B 
Rockwell 
Automation 
Publicatio
n 1756-RM084U-EN-P - November 2015 
277 
 Addition of SynchronizeRedundancyDataAfterExecution attribute to the 
PROGRAM component. 
 Additional CONFIG attributes. 
 New export TXT format for rungs and logic comments that uses tabs to 
separate values. This format is similar to the CSV format that uses commas 
to separate values. 
The CSV and TXT formats also include text box comments from function 
block and sequential function chart logic. 
Version 2.6, major revision 2, minor revision 6, of the import/export feature 
included with Logix Designer, version 15 includes these major enhancements: 
 Support for the 1769-L32C, 1769-L32CR CompactLogix and 1768-L43 
CompactLogix controllers. 
This release also removed support for the 1756-L1 CompactLogix,  
1794-L33 FlexLogix, 1769-L20 CompactLogix, 1769-L30 CompactLogix, 
and PowerFlex 700 S controllers. 
 Equipment Phase program type and its relay ladder and structured text 
instructions. 
 ControlLogix and SoftLogix  controllers now support 100 programs per 
task. 
 Information about when an imported file modifies a project so that you 
cannot go online and access a previously downloaded controller. 
 Additional values for the Mode attribute of a MODULE component. 
 New SERCOS IDN Read and SERCOS IDN Write message types. 
 New motion AXIS_GENERIC_DRIVE type. 
 Removal of the DescriptionWidth parameter from the STEP, 
TRANSITION, and STOP components in SFC logic. 
 Addition of an Attributes column to the CSV format for exported tags. 
Version 2.4, major revision 2, minor revision 4, of the import/export feature 
included with Logix Designer, version 13 includes these major enhancements: 
 Support for new controllers. 
 ExtendedProp section to MODULE data. 
 Support for new TAG attributes. 
Attributes can be in any order in an import/export file. The order 
shown in this document is the order the attributes export. 
Import/Export version 2.6 
Logix Designer version 15 
Import/Export version 2.4 
Logix Designer version 13 
Appendix B                  Import/Export revision history 
278 
Rockwell 
Automation 
Publicatio
n 1756-RM084U-EN-P - November 2015 
 Support for a TREND object in the import/export .L5K file. 
 New MCSV instruction in ladder logic (chapter 4) and structured text. 
 Online editing support for structured text and sequential function chart 
logic. 
 Updated CSV format now includes rung comments. 
 New L5X format for partial import/export of ladder rungs, tags, and trends. 
Version 2.3, major revision 2, minor revision 3, of the import/export feature 
included with Logix Designer, version 12.01 includes these major enhancements: 
 The structured text component changed from STX_ROUTINE 
to ST_ROUTINE. The LanguageType attribute in SFC routines for 
embedded structured text also changed from STX to ST. 
 Support for new controllers. 
 Addition of the ControlNetSignature attribute to the MODULE 
component. 
 Addition of the ProgrammaticallySendEventTrigger attribute to the TAG 
component. 
 New COORDINATE_SYSTEM tag. 
 Addition of several new attributes to the axis tag types. 
 Addition of DisableFlag attribute to the PROGRAM component. 
 Addition of EventTrigger and EventTag attributes to the TASK 
component to support Event tasks. 
 New EVENT, IOT, MCCD, MCCM, MCLM, MCS, MCSD, and MCSR 
instructions in ladder logic and structured text. 
 Addition of information regarding the LOGIC block when exporting 
online function block logic. 
 Addition of new modules and their valid CommMethod and 
ConfigMethod values. 
Version 2.2, major revision 2, minor revision 2, of the import/export feature 
included with Logix Designer, version 11.10 includes these major enhancements: 
 Support for the 1756-L63 controller. 
 New controller attributes to support sequential function charts. 
 Corrected the DATATYPE attributes and added the FamilyType attribute. 
 Additional information for the CompatibleModule and KeyMask 
attributes of the MODULE component. 
Import/Export version 2.3 
Logix Designer version 12 
Import/Export version 2.2 
Logix Designer version 11 
Import/Export revision history                  Appendix B 
Rockwell 
Automation 
Publicatio
n 1756-RM084U-EN-P - November 2015 
279 
 Addition of RSNetWorxFileName attribute to the MODULE component. 
 Addition of SFC_ACTION, SFC_STEP, and SFC_STOP tag types. 
 Addition of 38400 as a supported serial port baud rate. 
 Addition of structured text instructions. 
 Addition of EOT, SFR, and SFP instructions to relay ladder and structured 
text. 
 Addition of sequential function chart components. 
 Addition of an appendix that lists the valid CommMethod and 
ConfigMethod values for the supported I/O modules. 
Beginning with version 2.2, multi-line rung comments with hard returns are no 
longer exported as one long string in double-quotes. Instead, each line of a multi-
line rung comment is on a separate line in the .L5K file with double-quotes around 
each line. When imported, the multiple quoted strings are concatenated to form 
the rung comment. This improves the readability of the .L5K text file by using the 
existing multiple-string capability of the rung comment syntax. Older formats still 
work on import. 
Version 2.1, major revision 2, minor revision 1, of the import/export feature 
included with Logix Designer, version 10.0 includes these major enhancements: 
 Removal of the characters when specifying a controller type. 
 Addition of the SecurityCode attribute to the Controller object. 
 Enhancements to the Message tag structure. See page 264 on page 279
 The Program object now includes a Mode attribute. 
 Correction to valid values for Watchdog and Rate attributes of the 
Task object. 
 Addition of MaxStationAddress and TokenHoldFactor attributes to the 
Config DF1 object. 
 Addition of new instructions: SIZE, SWPB, LOWER, and UPPER. 
 The NumberOfAppendChars of the Config ASCII object is no longer 
exported. If you have an import/export file with any of these attributes, the 
file will correctly import into the software. This attributes will be removed 
when you export the file. 
Changes to support MESSAGE tag enhancements 
Version 2.1 (major revision 2, minor revision 1) of the import/export feature that 
is included with Logix Designer 2 programming software, version 10.0 made 
Import/Export version 2.1 
Logix Designer version 10 
Appendix B                  Import/Export revision history 
280 
Rockwell 
Automation 
Publicatio
n 1756-RM084U-EN-P - November 2015 
significant changes to the MESSAGE tag. For reference, this table shows the 
MESSAGE tag structure of the previous import/export release. 
MESSAGE Tag Structure (Version 2.0) 
Attribute 
Description 
Description 
Provide information about the tag. 
Specify Description := "text" 
Comment 
Provide information about a tag component. 
Specify Comment<specifier> := "text" 
Where the specifier is: 
.bitnumberfor a bit in the tag 
[element]for an array element of the tag 
.membernamefor a structure member of the tag 
MessageType 
Type Block Transfer ReadBlock Transfer WriteCIP Data Table ReadCIP Data Table Write, CIP Generic
PLC2 Unprotected Read, PLC2 Unprotected Write, PLC3 Typed ReadPLC3 Typed WritePLC3 Word Range 
ReadPLC3 Word Range WritePLC5 Typed ReadPLC5 Typed WritePLC5 Word Range ReadPLC5 Word 
Range WriteSLC Typed Read, or SLC Typed Write
Specify MessageType := text 
RequestedLength 
Specify the number of elements in the message instruction (0...32,767). 
Specify RequestedLength := value 
ConnectionPath 
Specify the connection path to the other device. 
Specify ConnectionPath := string 
DF1DHFlag 
If the communication method uses DH+, type 1. If the communication method does not use DH+, type 0. 
Specify DF1DHFlag := value 
LocalTag 
Specify the tag name of the element in the local device. 
Specify LocalTag := text 
RemoteElement 
Specify the tag name of the element in the remote device. 
Specify RemoteElement := value 
DHPlusSourceLink 
If the communication method uses DH+, specify the source link (0...65,535). 
Specify DHPlusSourceLink := value 
DHPlusDestinationLink 
If the communication method uses DH+, specify the destination link (0...65,535). 
Specify DHPlusDestinationLink := value 
DHPlusDestinationNode 
If the communication method uses DH+, specify the destination node number (0...63 octal). 
Specify DHPlusDestinationNode := value 
DHPlusChannel 
If the communication method uses DH+, specify the DH+ channel. Type A or B
Specify DHPlusChannel := letter 
CacheConnections 
If the message is to cache connections, type TRUE. If the message is not to cache connections, type FALSE
Specify CacheConnections := text 
ServiceCode 
If the message type is CIP Generic, specify the service code (0...255 hexadecimal). 
Specify ServiceCode := #16value 
ObjectType 
If the message type is CIP Generic, specify the object type (0...65,535 hexadecimal). 
Specify ObjectType := 16#value 
TargetObject 
If the message type is CIP Generic, specify the target object (0...65,535 decimal). 
Specify TargetObject := value 
Documents you may be interested