IDA Indoor Climate and Energy 4.5 
© EQUA Simulation AB 2013 
131 
The dialog for an integrated shading is opened from the Right button menu with the cursor 
over an object of the integrated shading type (e.g. Light dense curtain between the panes) in 
the Integrated shading field in the form for one window or in the form for IDA-resources. 
7.4.15.10. Editing an external shading 
This form is used to edit an object of the External shading type. The window and the external 
wall are shown in a side view. External shading is a combination of the shading elements 
Balcony with sides, Simple screen, Side fins and Marquee with sides. The window’s external 
recess depth is also included in its external shading. 
The Shading editor form is opened by double clicking on the Drawing view from the side to 
describe external shading button, in the window form. A new shading object is inserted by 
dragging from palette or by selecting New object… in the Insert menu with the Shading editor 
being the active window. In the Insert object dialog then opened there are four alternatives: 
Simple screen 
Side fins 
Marquee with sides  
When the selection is made the editor is redisplayed. Place the cursor beside the wall to the 
right of the window, hold down the left button and drag the shading to the desired size. For 
the Simple screen alternative, draw a polyline by clicking a start point, break points, and end 
point in the form. End by clicking once with the Right button and selecting OK. The small 
Convert pdf into jpg online - Convert PDF to JPEG images in C#.net, ASP.NET MVC, WinForms, WPF project
How to convert PDF to JPEG using C#.NET PDF to JPEG conversion / converter library control SDK
convert pdf pages to jpg; change pdf to jpg
Convert pdf into jpg online - VB.NET PDF Convert to Jpeg SDK: Convert PDF to JPEG images in vb.net, ASP.NET MVC, WinForms, WPF project
Online Tutorial for PDF to JPEG (JPG) Conversion in VB.NET Image Application
changing pdf file to jpg; convert pdf file to jpg on
IDA Indoor Climate and Energy 4.5 
© EQUA Simulation AB 2013 
132 
number field is for the width of the shading (for side fins, the distance between them), i.e. the 
extension perpendicular to the editor plane. Repeat this procedure to insert further shading 
objects. 
The shading elements may be moved using Shift dialog; 
The window’s position in the wall, the so-called recess depth, is changed by dragging the 
window line to the desired position. The cursor changes appearance when it is placed over the 
window line.  
The faint horizontal line in the wall over the window indicates ceiling height in the zone 
where the window is located. 
In the Shading editor there is a tab Control. Via this, one can specify limits when Marquees 
(awnings) and/or Simple screens should be withdrawn due to strong wind or low solar 
radiation. 
7.4.15.11. Form for marquee, side fins and screens 
This form describes one of the objects Balcony with sides, Simple screen, Side fins and 
Marquee with sides.  
Field description:
Width The extension of the shading device perpendicular to the editor plane (m) 
Shading type Fixed or controllable device; select parameters for all controllable devices 
under the tab Control. 
Vertices  (m) 
The form for a shading object is opened from the Right button menu with the cursor over an 
object of this type (e.g., Balcony with sides) in the Shading editor. 
Shading objects cannot be changed to independent IDA-resources, but will be saved, as 
resources or data base objects, combined with the window’s size and positioning in the wall 
(see Edit an external shading).  
Online Convert Jpeg to PDF file. Best free online export Jpg image
So, feel free to convert them too with our tool. Easy converting! If you want to turn PDF file into image file format in C# application, then RasterEdge
change format from pdf to jpg; convert pdf into jpg online
C# Create PDF from images Library to convert Jpeg, png images to
Batch convert PDF documents from multiple image formats, including for exporting high quality PDF from images for combining multiple image formats into one or
.pdf to .jpg converter online; convert pdf to jpg for online
IDA Indoor Climate and Energy 4.5 
© EQUA Simulation AB 2013 
133 
7.4.15.12. Shading control 
No control 
No automatic control 
Wind 
The shading is withdrawn at high local wind speed 
Radiation 
The shading is drawn (extended) at high solar radiation  
Radiation and wind 
Control by wind and sun; wind has priority 
Wind speed, above which shading is withdrawn 
If the wind speed for this facade exceeds this level, the shades are withdrawn. 
Radiation, incident on window, above which shading is used 
If the radiation in the plane of the window, with shades withdrawn, exceeds this level, the 
shades are extended. 
The form also contains the list of shading elements. In this list the user may select (by 
marking the check box) which elements are controlled by the shading control. It is also 
possible to modify the width of elements and to remove elements. 
VB.NET PDF Convert to Images SDK: Convert PDF to png, gif images
Convert PDF documents to multiple image formats, including Jpg, Png, Bmp, Gif, Tiff, Bitmap, .NET Graphics, and REImage. Turn multipage PDF file into image
convert pdf file to jpg online; batch convert pdf to jpg online
C# Image Convert: How to Convert Adobe PDF to Jpeg, Png, Bmp, &
Adobe PDF document can be easily loaded into your C#.NET String inputFilePath = @"C:\input.pdf"; String outputFilePath = @"C:\output.jpg"; // Convert PDF to jpg
conversion of pdf to jpg; convert pdf file into jpg
IDA Indoor Climate and Energy 4.5 
© EQUA Simulation AB 2013 
134 
7.4.15.13. Detailed Glazing System (Expert edition only) 
The Detailed Glazing System dialog is used to describe optical and thermal properties of the 
window glazing for the detailed window model. The dialog shows the list of layers (panes, 
shading devices, and gaps), the parameters of the currently selected layer and the buttons used 
to add, remove, and reorder the layers. 
A detailed glazing system should consist of one or more glass panes, optional shading layers, 
and cavity layers between pane/shading layers. 
Two types of shadings are currently supported: plain shading and Venetian blind. 
Layer parameters
Pane layer 
Pane A reference to a pane description. The button with the right arrow gives a menu of 
possible operations: Open the Pane dialog; create a new pane description; load a 
pane from database; save the pane to database. 
Cavity layer 
Material 
A reference to a gas description. The button with the right arrow 
gives a menu of possible operations: Open the Gas dialog; create a new gas 
description; load a gas from database; save the gas to database. 
Thickness The thickness of the cavity 
Shade layer 
C# PDF Convert to Tiff SDK: Convert PDF to tiff images in C#.net
with specified zoom value and save it into stream The magnification of the original PDF page size Description: Convert to DOCX/TIFF with specified resolution and
convert pdf pages to jpg online; bulk pdf to jpg converter online
VB.NET PDF insert image library: insert images into PDF in vb.net
Support various image formats, like Jpeg or Jpg, Png, Gif, Bmp Insert images into PDF form field in VB.NET. to PDF in preview without adobe PDF control installed.
c# pdf to jpg; change from pdf to jpg
IDA Indoor Climate and Energy 4.5 
© EQUA Simulation AB 2013 
135 
Material 
A reference to a shade material description. The button with the 
right arrow gives a menu of possible operations: Open the Shade material dialog; 
create a new shade material description; load a shade material from database; 
save the shade material to database. 
Venetian blind layer 
Device A reference to a Venetian blind description. The button with the right arrow 
gives a menu of possible operations: Open the Venetian blind dialog; create a 
new Venetian blind description; load a Venetian blind type from database; save 
a Venetian blind to database. 
7.4.15.14. Glass pane 
The Glass pane dialog is used to describe the properties of a glass pane (for use in a Detailed 
Glazing System for the  Detailed window model). 
Glass panes are resource objects, i.e. the same pane object may be referenced from multiple 
glazing systems (or multiple layers of the same glazing system). 
Pane parameters
Glass pane Choice of Glass pane object. The rest of the dialog shows the details of the 
selected object. 
The optical parameters are grouped in three columns: transmittance (same for both 
directions), and two columns for reflectance, from the front side and from the back side. 
Total shortwave 
VB.NET Create PDF from images Library to convert Jpeg, png images
Components to batch convert PDF documents in Visual Basic control for exporting high quality PDF from images. Turn multiple image formats into one or multiple
convert from pdf to jpg; reader pdf to jpeg
C# PDF insert image Library: insert images into PDF in C#.net, ASP
Support various image formats, like Jpeg or Jpg, Png, Gif, Bmp Insert images into PDF form field. Access to freeware download and online C#.NET class source code
convert pdf to high quality jpg; change pdf to jpg format
IDA Indoor Climate and Energy 4.5 
© EQUA Simulation AB 2013 
136 
The coefficients of transmittance and reflectance represent average values over the full 
solar wavelength spectrum. The coefficients should be valid for radiation that is 
perpendicular to the pane. Coefficients for other incidence angles and for diffuse 
radiation are calculated by the model. 
Visible 
Ditto for the visible range. 
Diffusion 
The coefficients of diffusion (dissipance), i.e., the fraction or the transmitted/reflected 
direct radiation that becomes diffuse after transmission or reflection. These coefficients 
do not depend on the incidence angle. 
NB! Diffusion coefficients are not stored in the database. 
Thermal and other properties
Longwave 
The table contains emissivity and transmittance. The transmittance is not stored in the 
database. 
Thickness [mm] 
Thermal conductivity [W/(K.m)] 
7.4.15.15. Venetian blind 
The Venetian blind dialog is used to describe the properties of a Venetian blind (for using as 
shading layer in Detailed Glazing System for detailed window model). 
The Venetian blinds are resource objects; that means that the same Venetian blind description 
may be referenced from multiple glazing systems. 
IDA Indoor Climate and Energy 4.5 
© EQUA Simulation AB 2013 
137 
7.4.15.16. Shade material 
The Shade material dialog is used to describe the properties of the material used in Shading 
layers and in Venetian blinds in a Detailed Glazing System for the Detailed window model. 
Shade materials are resource objects, i.e. Shading layers and Venetian blinds in multiple 
glazing systems may reference the same Shade material description. 
Shade material parameters
Shade materials Choice of Shade material object. The rest of the dialog shows the details of 
the selected object. 
The optical parameters are grouped in three columns: transmittance (same for both 
directions), and two columns for reflectance, from the front side and from the back side. 
Total shortwave 
The coefficients for transmittance and reflectance represent average values over the full 
solar wavelength spectrum. The coefficients are applied both to direct and diffuse 
radiation and do not depend on incidence angles. The transmitted/reflected radiation is 
assumed to become fully diffuse. 
Visible 
Ditto for the visible range. 
Thermal and other properties
Longwave 
The table contains emissivity and transmittance.  
Thickness [mm] 
Thermal conductivity [W/(K.m)] 
IDA Indoor Climate and Energy 4.5 
© EQUA Simulation AB 2013 
138 
7.4.15.17. Gas properties 
The Gas properties dialog is used to describe the properties of a cavity (for use in a Detailed 
Glazing System for the Detailed window model). 
Gases are resource objects, i.e. the same gas may be referenced from multiple glazing systems 
(or from multiple cavities of the same glazing system). 
7.4.16. Heating, cooling, ventilation 
7.4.16.1. Zone equipment for cooling and heating 
Local heating or cooling is supplied in the zone by defining room units either directly in the 
zone (ideal heater and cooler, fan coil, local AHU) or on the walls, in the ceiling, or on the 
floor. There is general equipment for  waterborne cooling (for both radiative and convective 
equipment), a water radiator (or convector), floor heating, and an electric radiator. The Expert 
edition supports also heated and cooled floor/ceiling. 
See further the IDA ICE Manual. 
7.4.16.2. Ideal cooler 
The ideal cooler is a room unit that cools the zone when no detailed information about an 
actual room unit, such as a fan coil or active chilled beam, is available or this amount of detail 
is unmotivated. It has no given physical location on any room surface and is not connected to 
the plant of the building. Physically, think of it as a standalone air conditioner with fixed 
performance parameters. 
An ideal cooler is inserted by default when a new zone is created (unless it has been removed 
from the zone template). The default capacity of the ideal cooler is given per m
2
floor area in 
the zone template and should normally be selected to be large enough to safely be able to cool 
the zone under all conditions. A PI controller will then be used to keep the room air (or 
operative) temperature at the cooling setpoint (as specified in the Setpoint collection.) 
In order to study the performance of a specific type of room unit, or a room unit which is 
hydronically connected to the plant, remove the ideal room unit from the zone form, and 
insert instead a physical room unit to a zone surface or, alternatively, drag in a fan coil or 
similar device from the palette to the zone form. 
7.4.16.3. Ideal heater 
The ideal heater is a room unit that heats the zone when no detailed information about an 
actual room unit, such as a radiator or convector, is available or this amount of detail is 
unmotivated. It has no given physical location on any room surface and is not connected to 
the plant of the building. Physically, think of it as a standalone fuel or electric heater with 
fixed performance parameters and no flue gas emissions. 
An ideal heater is inserted by default when a new zone is created (unless it has been removed 
from the zone template). The default capacity of the ideal heater is given per m
2
floor area in 
the zone template and should normally be selected to be large enough to safely be able to heat 
IDA Indoor Climate and Energy 4.5 
© EQUA Simulation AB 2013 
139 
the zone under all conditions. A PI controller will then be used to keep the room air (or 
operative) temperature at the heating setpoint (as specified in the Setpoint collection.) 
In order to study the performance of a specific type of room unit, or a room unit which is 
hydronically connected to the plant, remove the ideal room unit from the zone form, and 
insert instead a physical room unit to a zone surface or, alternatively, drag in a fan coil or 
similar device from the palette to the zone form. 
7.4.16.4. Fan coil 
A fan coil takes a stream of air from a zone, conditions it, and then returns it to the same zone. 
The heat from the coil is recorded under room units in the zone Energy report. If the physical 
unit also exchanges air (or heat) directly with outdoor conditions, it should be modeled as a 
local air handling unit. 
ICE provides three models of fan coils: VAV heating fan coil, VAV cooling fan coil, and air-
to-air conditioner. 
There are also available an “undefined” fan coil that may be used (in the Expert edition only) 
to build a custom model out of available components. 
7.4.16.5. Local AHU 
A local air handling unit works in just the same way as a central air handling unit, except it 
serves only a single zone and can only be reached from that zone. The heat and air from the 
unit in the zone is recorded as coming from mechanical ventilation. 
A local air handling unit is introduced in a zone by following the More… link in the 
Ventilation section of the zone form. Then press Add AHU, and select among available local 
air handling units. 
Local AHUs may only operate in CAV, with flows given in the table. 
IDA Indoor Climate and Energy 4.5 
© EQUA Simulation AB 2013 
140 
7.4.16.6. Active Beam 
Use manufacturer's data Automatically selected when product data has been imported 
from manufacturer’s database 
Simplified model Select in order to give parameters manually 
Power at design air flow, Cooling Waterborne cooling power at design air flow and given 
temperatures (°C) 
Power at design air flow, Heating Waterborne heating power at design air flow and given 
temperatures (°C) 
Power at zero air flow, Cooling Waterborne cooling power at zero air flow and given 
temperatures (°C) 
Power at zero air flow, Heating Waterborne heating power at zero air flow and given 
temperatures (°C) 
Design air flow Air flow through device at design conditions (l/s) 
Design conditions 
dT(coolant - zone air) at max power, Cooling Average temperature difference 
between coolant and room air at design power (°C) 
dT(coolant - zone air) at max power, Heating Average temperature difference 
between hot water and room air at design conditions (°C) 
dT(coolant) at max power, Cooling Temperature rise of coolant at design power (°C) 
dT(coolant) at max power, Heating Temperature drop of hot water at design power 
(°C) 
Controller Method of control of device output. Choose between built-in (proportional and PI) 
and user-defined controllers. The temperature setpoint is fetched from Controller setpoints. 
Sensor Choice of the target of the control (air temperature or operative temperature) 
Active beams are air supply terminals combined with coils for cooling and sometimes also for 
heating. In addition to providing natural convection, which is active also without any 