IDA Indoor Climate and Energy 4.5 
© EQUA Simulation AB 2013 
41 
The geometry of the building is defined by the corners of one or more building body parts 
(see above figure). The corners’ x and y co-ordinates are indicated in a local coordinate 
system for the building (called the building system below) that moves and rotates with the 
building. Before editing, the origin of coordinates for the building system coincides with the 
lower left corner of the building. The building system is then also at the origin of coordinates 
for the global coordinate system (which is marked by the origin marker
). 
The shape of building body part is limited to 
 prisms with flat vertical walls  
 a part of such prism limited by the roof. The roof may consist of one or more flat 
polygons with slope from 0° (horizontal, outer side upward) to 90° (vertical). 
 a custom polyhedral that may be imported but not edited in ICE. 
The zone geometry is described relative to a point in the building system, where the z-
coordinate gives the height of the floor above ground level. 
The zone is defined by its height plus the corners of the floor. The corners’ x and y co-
ordinates are indicated in a local coordinate system for the zone (called the zone system 
below) that moves and rotates with the zone. The zone system is defined by the origin’s 
coordinates (in the building system) and the rotation angle around the z-axis. 
The shape of the zones is limited to prisms with vertical walls. If the prism is intersecting with 
the roof, only the part under the roof is included in the zone. 
A local coordinate system (called the surface system) is defined on every enclosing surface. 
For vertical walls, the origin of coordinates is located in the lower left corner of the surface 
(from inside the zone). For floors and horizontal ceilings, the surface system coincides with 
the zone system (with z-coordinate omitted). For slanted ceilings (or fragments of ceiling), the 
x-coordinate is always horizontal passes thru the lowest corner of the ceiling (or fragment) 
Convert pdf photo to jpg - Convert PDF to JPEG images in C#.net, ASP.NET MVC, WinForms, WPF project
How to convert PDF to JPEG using C#.NET PDF to JPEG conversion / converter library control SDK
convert multiple page pdf to jpg; best pdf to jpg converter for
Convert pdf photo to jpg - VB.NET PDF Convert to Jpeg SDK: Convert PDF to JPEG images in vb.net, ASP.NET MVC, WinForms, WPF project
Online Tutorial for PDF to JPEG (JPG) Conversion in VB.NET Image Application
changing pdf to jpg; best pdf to jpg converter
IDA Indoor Climate and Energy 4.5 
© EQUA Simulation AB 2013 
42 
and the y-coordinates is located in the ceiling's plane, is perpendicular to the x-axis and passes 
thru the leftmost corner of the ceiling (or fragment).  
The surface system is used to indicate the position for features (such as openings) on the 
surface: 
x
dy
y
dx
Feature
Wall
The geometry for objects like windows and heating devices is defined by a rectangle. The 
insertion point of the rectangle (lower left corner) is given in the surface system. If the surface 
(wall, floor, or ceiling) is not rectangular, the position of an object is the intersection of the 
rectangle with surface.  
See also Building and zone geometry import. 
7.1.2. Objects in IDA Indoor Climate and Energy (in alphabetical order) 
IDA Indoor Climate and Energy contains a number of objects of interest to the user.  
See also Objects in hierarchical order. 
Active beam  
Air handling unit  
Balcony, screen and marquee  
Building  
Building body  
Chimney  
Choice of output  
Climate definition  
Climate file  
Control of integrated shading  
Controller setpoints  
Convective interior mass  
Cooling coil  
Cooling device  
Double-glass Façade 
Electric radiator  
Equipment  
External window shading  
Extra energy and losses  
Fan coil  
Face
Floor heating  
Ground conditions  
Heat exchanger  
C# PDF insert image Library: insert images into PDF in C#.net, ASP
Support various image formats, like Jpeg or Jpg, Png, Gif, Bmp, Tiff and other Import graphic picture, digital photo, signature and logo into PDF document.
change pdf to jpg format; convert pdf image to jpg online
VB.NET PDF insert image library: insert images into PDF in vb.net
Support various image formats, like Jpeg or Jpg, Png, Gif, Bmp, Tiff and other Import graphic picture, digital photo, signature and logo into PDF document.
convert pdf to high quality jpg; best way to convert pdf to jpg
IDA Indoor Climate and Energy 4.5 
© EQUA Simulation AB 2013 
43 
Heating coil  
Heating device  
Heated/cooled floor  
Heated/cooled panel  
Holidays 
Ideal cooling device  
Ideal heating device  
Infiltration  
Integrated shading  
Leak  
Lights  
Location  
Material  
Occupant  
Opening  
Opening control  
Piecewise proportional controller  
Pressure coefficients  
Primary system  
Profile  
Project data  
Results  
Roof  
Schedule  
Simulation data  
Site object  
Skylight  
Surfaces  
System parameters  
Thermal bridges (building level)  
Thermal bridges (zone level) 
Thermal mass  
Wall definition  
Wall, Floor and Ceiling  
Wall part  
Water radiator  
Wind profile  
Window  
Window (detailed) 
Zone  
Zone defaults  
7.1.3. Objects in IDA Indoor Climate and Energy (in hierarchical order) 
The hierarchical structure for the objects in IDA Indoor Climate and Energy are shown in the 
formation below. Objects are edited either in forms or dialogs. 
See also Objects in alphabetical order. 
Building 
Location  
VB.NET Image: How to Save Image & Print Image Using VB.NET
and printing multi-page document files, like PDF and Word different image encoders, including tif encoder, jpg encoder, png VB.NET Code to Save Image / Photo.
convert pdf to jpg; change pdf to jpg
VB.NET Image: Tutorial for Flipping Image Using Our .NET Image SDK
SDK, an image (including BMP, PNG, JPG, etc) can be becomes a mirror reflection of the photo on the powerful & profession imaging controls, PDF document, tiff
convert pdf file to jpg online; change from pdf to jpg on
IDA Indoor Climate and Energy 4.5 
© EQUA Simulation AB 2013 
44 
Wind profile 
Climate data 
Holidays 
Zone defaults  
Site object  
Simulation data 
System parameters  
Choice of output 
Project data  
Climate file 
Ground conditions 
Thermal bridges 
Infiltration  
Extra energy and losses 
Results objects  
Air handling unit 
Primary system 
Building body  
Faces 
Roof  
Faces 
Zone   
Controller setpoints 
Thermal bridges 
Results objects  
Surfaces  
Construction 
Inner surface  
Outer surface  
Wall part  
Window  
Glass construction 
Integrated shading  
Schedule for integrated shading 
Control of integrated shading  
External shading   
Balcony, screen and marquee 
Opening schedule  
Opening control  
Window (detailed)  
Detailed Glazing System  
Double-glass Façade 
Schedule for integrated shading 
Control of integrated shading  
External shading   
Balcony, screen and marquee 
Opening schedule  
Opening control  
Opening  
Opening schedule 
C# PDF remove image library: remove, delete images from PDF in C#.
NET delete PDF pages, VB.NET convert PDF to SVG. vector image, graphic picture, digital photo, scanned signature remove multiple or all images from PDF document.
.pdf to jpg; convert pdf file to jpg format
VB.NET PDF remove image library: remove, delete images from PDF in
NET convert PDF to text, C#.NET convert PDF to images vector image, graphic picture, digital photo, scanned signature or all image objects from PDF document in
convert pdf to gif or jpg; change from pdf to jpg
IDA Indoor Climate and Energy 4.5 
© EQUA Simulation AB 2013 
45 
Leak  
Chimney  
Skylight  
Active beam  
Heating device  
Electric radiator  
Cooling device  
Floor heating  
Heated/cooled floor 
Heated/cooled panel 
Fan coil  
Local AHU  
Ideal cooling device  
Ideal heating device  
Heating device with unspecified position 
Electric radiator with unspecified position 
Cooling device with unspecified position 
Heated/cooled panel with unspecified position 
Active beam with unspecified position 
Lights 
Schedule 
Occupant  
Schedule 
Equipment 
Schedule 
Convective internal mass  
Thermal mass  
Energy meter  
Energy cost 
VB.NET PDF copy, paste image library: copy, paste, cut PDF images
pasting and cutting from adobe PDF file in image formats, including Jpeg or Jpg, Png, Gif and cut vector image, graphic picture, digital photo, scanned signature
batch convert pdf to jpg online; convert multiple pdf to jpg online
VB.NET Image: Create Image from Stream; Stream to Image Converter
to capture image from web url, convert image to like image sharpening and old photo effect adding powerful & profession imaging controls, PDF document, tiff
convert pdf pictures to jpg; convert pdf picture to jpg
IDA Indoor Climate and Energy 4.5 
© EQUA Simulation AB 2013 
46 
7.2. Building simulation 
7.2.1. General tab 
7.2.1.1. The building’s form 
An object of the Building type is presented in a form on the screen. This contains all the 
objects connected to the building. The building’s form is automatically displayed each time 
the user selects to open an already existing, or a new, document (please see Working with 
IDA systems). The form above shows a sample appearance of the building form. It contains 
standard versions of the air handling unit, the primary system and energy meters in the 
HVAC-system and Energy meter list boxes.  
Field descriptions, etc:
Location  
Location of the building. The chosen location does not have to correspond exactly to the 
location of the climate file. 
Climate  
Choice of climate object. The object contains a reference to a climate file and information 
about this file or indicates that synthetic climate is to be used (design day data for 
summer or winter in the Location object). 
Wind profile  
Choice of wind profile object. Wind profile is only important for studies where pressure 
coefficients are given. 
Holidays  
Optional choice of list of holidays. The holidays are treated either as Sundays or using 
special rules – for time schedules that define such rules. 
Project data  
Object for documentation of the simulation object and the current choice of parameters. 
Project data are written on reports etc. 
Defaults  
VB.NET PowerPoint: Use .NET Converter to Convert PPT to Raster
so it is not widely used for digital photo. If temp IsNot Nothing Then temp.Convert( imageStream, ImageFormat & profession imaging controls, PDF document, image
convert pdf to 300 dpi jpg; changing pdf to jpg on
VB.NET Image: VB.NET Planet Barcode Generator for Image, Picture &
gif, jpeg, bmp and tiff) and a document file (supported files are PDF, Word & TIFF to decide the output barcode image format as you need, including JPG, GIF, BMP
convert pdf file to jpg; bulk pdf to jpg
IDA Indoor Climate and Energy 4.5 
© EQUA Simulation AB 2013 
47 
Default settings for all zones and HVAC systems. 
Site shading and orientation 
Building orientation (compass arrow) and definition of separate shading objects, e.g. 
trees, hills and neighboring buildings. 
Thermal bridges 
Coefficients for calculation of loss factors for thermal bridges in zones. 
Ground properties 
Model and parameters for temperature conditions below the building. 
Infiltration 
Method and parameters for building air leakage  
Pressure coefficients 
Coefficients for calculation of wind pressure on external surfaces of the building. 
Extra energy and losses 
Losses from HVAC distribution systems, hot water and other energy use items 
HVAC System 
List of central hydronic and air handling units. 
New AHU ... 
Add an extra AHU (If the existing one is not needed: Do 'Replace' instead) 
Replace AHU ... 
Replace the selected AHU with a new one. 
Supervisory control 
A controller that collects signals from the environment (utility signals etc.) and from 
building sensors and computes supervisory control signals that are relevant to the whole 
building. 
Energy meters  
List of energy account items, with info on cost, CO2, and primary energy factor  
Click “Usage” to list all references to energy meters 
Details 
This table shows the main parameters of zones and other objects. The row of radio 
buttons allows selecting the category of objects to be shown in the table. In the table, you 
may: 
- edit parameters (except in grey fields) 
- select cells and copy/paste their contents to and from other applications 
- open objects (double click the object in the left column) 
- sort the contents by clicking a column header 
- show a parameter on the 3D plan (click "box" image in the column header) 
- export all tables to Excel 
- reorder the zones (in the Zones table only). The selected zone may be moved up and 
down by clicking Alt+Up and Alt+Down. This order will be used when combining the 
results into a single document (see Results tab, Make report). 
IDA Indoor Climate and Energy 4.5 
© EQUA Simulation AB 2013 
48 
7.2.1.2. Dialog for location 
This dialog describes an object of the Location type. It contains the geographical position and 
design weather data for the place where the calculation object, i.e. simulated building, is 
assumed to lie.  
The given weather data for winter and summer design conditions are used when synthetic 
weather has been selected in Heating or Cooling load calculations. This data is also used for 
Custom simulations when the Synthetic (winter or summer) option has been selected in the 
Climate field in the building form 
Field descriptions, etc:
Location: Choice of location. The rest of the dialog shows the details of the selected location. 
Position: Country country or geographical area for calculation  
Position: City place for calculation 
Position: Latitude calculation object’s latitude (Deg). To avoid sign confusion, the directions 
from equator are denoted by N (north) and S (south) 
IDA Indoor Climate and Energy 4.5 
© EQUA Simulation AB 2013 
49 
Position: Longitude calculations object’s longitude (Deg). To avoid sign confusion, the 
directions from Greenwich are denoted by E (east) and W (west) 
Position: Elevation calculation object’s height over sea level (m) 
Position: Time zone calculation object’s time zone (h). To avoid sign confusion, the 
directions from Greenwich are denoted by E (east) and W (west), e.g. 1 E for Central Europe. 
Design days: Dry-bulb min Lowest dry bulb temperature during the day (°C) 
Design days: Dry-bulb max Highest dry bulb temperature during the day is considered to 
occur at 15:00.  (°C) 
Design days: Wet-bulb maxHighest wet bulb temperature during the day is considered to 
occur at 15:00.  (°C) 
Design days: Wind direction The wind is only relevant to the airflow through the building if 
pressure coefficients are given and more than one leak or opening has been defined. (Deg) 
The wind from
North has direction 0°, from East 90°, etc. 
Design days: Wind speed Wind direction and speed is kept constant during the day  (m/s) 
Design days: Clearness number  Reduction factor for direct and diffuse sunlight. 0 = dark, 1 
= clear, dry and cloudless atmosphere, 1.15 = extremely clear conditions.  (-) 
Climate description  Default climate file for given location 
Object: name and description  
The Dialog for a location is opened when the Right button is pressed with the cursor over an 
object of the Location type (e.g. Malmö) in the Location field in the building form or in the 
form for IDA-resources. 
For synthetic climate, the outdoor air temperature varies sinusoidally between the given min 
and max values. The warmest time of day is assumed to be at 15:00, for dry as well as for wet 
bulb temperature. 
A clearness number indicates the presence of clouds or unclear atmospheric conditions. For a 
clear, dry and cloudless sky, 1 is given. A normal daily average for a clear day summer day 
can be 0.8. Under extremely clear conditions, particularly in northern countries, 1.15 may 
occur. Further information about clearness number and additional references can be found in 
ASHRAE Fundamentals. 
IDA Indoor Climate and Energy 4.5 
© EQUA Simulation AB 2013 
50 
7.2.1.3. Form for climate definition 
This form describes a Climate object, which provides information about an actual climate data 
file on disk. Indicated here is the path to the file (.prn) which contains the data, geographical 
position of the station, height of the wind measurement, etc.  
The description gives qualitative information about the data, its selection, extreme weather 
periods etc. 
Field descriptions, etc:
Filename the name and place for the data file, which must have a special IDA-format, is 
given here.  
Wind measurement height wind speed data in the file corresponds to measurements at this 
height over the ground (m) 
Position: Station name of measuring station 
Position: Country country or geographical area of measuring station 
Position: Latitude measuring station’s latitude (Deg) To avoid sign confusion, the directions 
from equator are denoted by N (north) and S (south) 
Position: Longitude measuring station’s longitude (Deg). To avoid sign confusion, the 
directions from Greenwich are denoted by E (east) and W (west) 
Position: Elevation measuring station’s height over the sea level (m) 
Position: Time zone measuring station’s time zone (h). To avoid sign confusion, the 
directions from Greenwich are denoted by E (east) and W (west), e.g., 1 E for Central Europe.  
Object: Name and description  
Note that the descriptive weather station data given here is not in any way tied to the data 
given in the Location object. It is the data in the Location object that describes the physical 
location of the simulated building and is used to calculate, e.g., the sun’s position wrt. the 
simulated building. 
Documents you may be interested