IDA Indoor Climate and Energy 4.5 
© EQUA Simulation AB 2013 
61 
When instead fixed flows are specified, constant envelope air flows to and from each zone are 
introduced. However, small envelope “natural ventilation” leaks are also introduced to absorb 
pressure differences because of for example imbalances in mechanical supply and return 
flows.  
A common problem when fixed flows are used in combination with unbalanced mechanical 
ventilation is that pressure difference over the envelope becomes unrealistically large. A 
warning for this is then issued during the simulation and the remedy is to specify larger leak 
areas in zones with unbalanced mechanical ventilation. 
7.2.1.11. Pressure Coefficients 
Pressure Coefficients are used to calculate wind pressure on the different external surfaces of 
a building in relation to the speed of wind at roof height. See ASHRAE Fundamentals. The 
wind only influences airflow through the building if non-zero pressure coefficients are given . 
Pressure coefficients are dependent on the building’s shape as well as on surrounding 
aerodynamic conditions. CFD calculations or wind tunnel measurements are required for 
good precision. In simple cases, handbook data can give acceptable results (at least much 
better than using fixed infiltration flows). A common handbook data set (from the Air 
Infiltration and Ventilation Centre) can be accessed by selecting a face or faces and pressing 
Auto fill. 
The wind contribution to pressure is assumed to be constant over the whole surface and is 
given by the following expression: 
P_OUT := (PRESSURE-COEFF * RHO * ON-SITE-WIND**2)/2, 
where the applicable PRESSURE-COEFF depends on facade and wind direction (linear 
interpolation between given directions), RHO is the air density and ON-SITE-WIND is the 
speed of wind at the roof height of the building. 
Convert pdf pages to jpg - Convert PDF to JPEG images in C#.net, ASP.NET MVC, WinForms, WPF project
How to convert PDF to JPEG using C#.NET PDF to JPEG conversion / converter library control SDK
.net convert pdf to jpg; convert multiple pdf to jpg
Convert pdf pages to jpg - VB.NET PDF Convert to Jpeg SDK: Convert PDF to JPEG images in vb.net, ASP.NET MVC, WinForms, WPF project
Online Tutorial for PDF to JPEG (JPG) Conversion in VB.NET Image Application
conversion pdf to jpg; convert multi page pdf to jpg
IDA Indoor Climate and Energy 4.5 
© EQUA Simulation AB 2013 
62 
7.2.1.12. Extra energy and losses 
In this form, losses from HVAC distribution systems, hot water use and other energy use 
items (external lighting etc.) are specified.  
Domestic Hot Water Use
may be specified here using different units. Note that when a unit 
that includes the number of building occupants is used, the relevant number of occupants 
should be set here as well. The Number of occupants field is by default bound to the sum of 
all defined occupant thermal gains. However, in many situations, this number is quite 
different from a relevant “water consuming occupant”, for example a conference room will 
hold a lot of occupant loads that have their normal “base” in some other room. 
The domestic hot water use may, additionally or alternatively, also be given for individual 
zones (on the zone advanced tab). 
Distribution of hot water use
as a function of time is given by a schedule. The signal is 
automatically rescaled to yield correct totals on a yearly basis (as specified by the Average hot 
water use parameter), i.e. only the shape of the given curve is used. A good convention is to 
set maximum use in the schedule = 1. 
C# Image Convert: How to Convert Adobe PDF to Jpeg, Png, Bmp, &
C# sample code for PDF to jpg image conversion. This demo code convert PDF file all pages to jpg images. // Define input and output files path.
convert pdf to jpg for online; conversion of pdf to jpg
C# Image Convert: How to Convert Tiff Image to Jpeg, Png, Bmp, &
RasterEdge.XDoc.Office.Inner.Office03.dll. RasterEdge.XDoc.PDF.dll. This demo code convert TIFF file all pages to jpg images.
pdf to jpeg converter; changing file from pdf to jpg
IDA Indoor Climate and Energy 4.5 
© EQUA Simulation AB 2013 
63 
Distribution System Losses
are specified to account for leakage from pipes and ducts that pass 
through the building without having to describe their exact path and insulation properties. For 
water circuits, the sign is positive when heating the zone for DHW and heat, and positive 
when cooling for cold water circuits. The loss from air ducts is defined as positive when the 
duct is cooler than the zone. 
Duct losses include both thermal conduction and air leakage losses, although the actual loss of 
mass through the duct wall is not modeled. Duct losses take account of actual temperature 
difference between the duct system and zones, while water circuit losses are independent of 
actual temperatures.  
Units for heat and cold distribution may be changed for convenience. 
NB! That the distribution losses also include heat and cold delivered by local ideal units. This 
is in order to be able to use ideal units as proxies for real room units that are connected to 
central systems via a distribution system (which has losses). 
Rough estimates of possible loss levels are provided for convenience via sliders, but these 
levels vary greatly between countries. 
A given percentage of the heat (or cold) from each distribution system is deposited to the zone 
heat balance. Remaining heat is simply lost to ambient. 
Plant losses
can be set to account for permanent conductive losses from chillers and boilers. 
They are defined in terms of extra electricity or fuel (heating value) use. This energy is lost. 
Plant pumping power
calculation method is selected for plant pumps. Depending on the plant 
type selected, this information may be possible to refine further in the Plant object. 
Ideal unit pumping power
calculation method is selected. This allows association of pumping 
power with ideal units, should they be used as proxies for real room units. 
Any number of Additional Energy Use
items may be specified (right click to rename them). 
This is energy which should be accounted for in total delivered energy (from the utility), but 
does not enter the building heat balance. Ice melting equipment or external lights are 
examples. 
For each item, both an absolute and a per-floor-area contribution may be given. The total of 
both is displayed for convenience. Each item must also refer to a schema and an energy meter. 
Note that defined energy meters can be renamed and new ones can be added in the building 
form. 
7.2.1.13. Energy meters 
C# Create PDF from images Library to convert Jpeg, png images to
Batch convert PDF documents from multiple image formats, including Jpg, Png, Bmp, Gif, Tiff, Bitmap, .NET Graphics, and REImage.
pdf to jpeg; convert pdf file into jpg format
VB.NET PDF Convert to Images SDK: Convert PDF to png, gif images
Resize converted image files in VB.NET. Convert PDF to Jpg, Png, Bmp, Gif, Tiff and Bitmap in ASP.NET. Embed PDF to image converter in viewer.
c# pdf to jpg; convert online pdf to jpg
IDA Indoor Climate and Energy 4.5 
© EQUA Simulation AB 2013 
64 
Energy meters represent items in the Delivered energy report. Sometimes they are also 
referred to as energy accounts.  
Equipment that use or convert energy will always report to a specific meter. 
The user may specify default energy meters for different energy carriers (electric, fuel, district 
heat/cold) and typical usage (heating, cooling, lighting, etc.) on the page Defaults. If a non-
default meter is required needed for a particular device, the default can be overridden by a 
local choice in the device. 
Energy meters can be renamed by right clicking. 
New energy meters can also be dragged from the Palette on the Side bar. 
Field descriptions, etc:
Energy meter type Shows meter type (corresponding to energy carrier). Fuel is measured in 
terms of its heating (calorific) value. To change the meter type, replace it with another meter 
of appropriate type. 
Energy rate plan Select object with time dependent energy price information. 
Primary energy factor Used energy is multiplied by this factor to compute primary energy 
use. 
CO2 emission per kWh Used to compute CO2 emissions from used energy. 
Role This choice influences how the used energy is reported. 
Color for presentation Used for graphical result presentation of energy use. 
Total energy consumption and costs are presented in the Delivered energy report. Click on 
Requested output in the simulation form. 
The form for energy meter is opened by double clicking on an object of the Energy meter type 
(e.g. Electric meter) in the Energy meters box in the building form. 
7.2.1.14. System parameters 
System parameters are global settings that affect the simulation but that should not normally 
be changed by the user. In the Outline view (Expert edition only), additional parameters and 
tolerances may be found that may be relevant to expert users. 
VB.NET PDF - Convert PDF with VB.NET WPF PDF Viewer
Create multiple pages Tiff file from PDF document. Convert PDF to image file formats with high quality, support converting PDF to PNG, JPG, BMP and GIF.
bulk pdf to jpg converter; convert pdf to jpg 300 dpi
C# TIFF: C#.NET Code to Convert JPEG Images to TIFF
Use C# Code to Convert Jpeg to Tiff. string[] imagePaths = { @"C:\demo1.jpg", @"C:\demo2.jpg", @"C:\demo3.jpg" }; // Construct List<REImage> object.
change pdf to jpg file; .pdf to .jpg converter online
IDA Indoor Climate and Energy 4.5 
© EQUA Simulation AB 2013 
65 
7.2.1.15. Dialog for energy price 
In this dialog a description of the objects of the Energy price type can be given. 
Field descriptions, etc:
Currency Currency name. 
Fixed cost, Kr/year Fixed yearly cost. 
Energy rate, Kr/kWh  
Schedule for rate Choose a schedule that selects rate at different times. Output signal should 
be 1,2,3 or 4 at all times. 
Object: Name and description  
The dialog for an energy price is opened from the Energy meter form by opening the object in 
the Energy rate plan field.  
C# WPF PDF Viewer SDK to convert and export PDF document to other
Create multiple pages Tiff file from PDF document. Convert PDF to image file formats with high quality, support converting PDF to PNG, JPG, BMP and GIF.
to jpeg; convert pdf to jpeg
VB.NET Create PDF from images Library to convert Jpeg, png images
Components to batch convert PDF documents in Visual Basic .NET class. Support create PDF from multiple image formats in VB.NET, including Jpg, Png, Bmp, Gif
convert pdf into jpg format; convert from pdf to jpg
IDA Indoor Climate and Energy 4.5 
© EQUA Simulation AB 2013 
66 
7.2.2. Forms for IDA-resources 
This form contains the IDA-resources currently or previously used in a project. If, for 
example, an Internal wall with insulation is chosen somewhere in the building, the IDA 
resources Internal wall with insulation, Gypsum, Air in 30 mm vertical gap and Lightweight 
insulation will appear in the list. (The Internal wall with insulation contains references to a set 
of material resources). 
A change made in an IDA resource at the building level applies to all the instances in the 
building where it has been used. If, for example, the density is changed for the IDA resource 
concrete from 2300 kg/m
3
to 2400 kg/m
3
at the building level, this change will influence all 
walls and floors in the building that contain concrete. 
Resources that have no references to them (aren’t used) can be deleted. Right click to check 
where a resource is used. 
Resource objects can also be stored in separate resource documents that are accessed by 
pressing the Import... button.  
Resource objects are frequently created from database objects. A list of all available objects 
can be found in the Database objects in IDA Indoor Climate and Energy. 
IDA Indoor Climate and Energy 4.5 
© EQUA Simulation AB 2013 
67 
7.2.3. Floor plan tab 
7.2.3.1. Floor Plan 
The Floor Plan view shows the building body, zones, and imported CAD data at the given 
height. 
All objects are shown in building coordinates. A compass shows the orientation of the 
building. To change the orientation, go to Site view. 
Supported operations on Floor Plan: 
Add, move, resize, edit, rename, and remove parts of building body and zones; 
Move the selected object using Shift dialog; 
Building and zone geometry import; 
CAD import  
See also 
Edit the zone position and size in the floor plan  
The building geometry  
7.2.3.2. Building shape 
The building shape is given as one or more parts of Building Body
The shape of a body part a prism with vertical walls or a part of such a prism limited by the 
roof. The roof may consist of one or more flat polygons that cover the whole roof. 
The body parts may be arranged both vertically and horizontally. The parts should not 
intersect. Zones may traverse several body parts. 
See also Building and zone geometry import. 
To edit a body part 
To replace the rectangular shape of a part of the building body by an arbitrary polygon, 
right click somewhere within the building and select Edit. The perimeter of the building 
is changed to a so-called polyline. A polyline consists of line segments and break points, 
the latter marked by small rectangles. The polyline can be edited in five ways: 
- Its breakpoints can be dragged to the desired positions for the building’s corners. 
- Its line segments can be dragged to the desired positions for the building’s walls. 
- A new breakpoint can be introduced by clicking on or close to the line. 
- An existing breakpoint can be deleted by clicking on it. 
- Breakpoints for non right-angled corners can be introduced by holding the Control key 
down and simultaneously clicking on a segment of the line. 
- If you hold a point or a segment while dragging it near to some other figure shown on 
the drawing, the point (or the segment) is snapped to that figure. 
Click once with the Right button and select OK to end editing, or alternatively press 
Enter (to accept) or Esc (to cancel). As an example, the figure below has had a new 
breakpoint introduced directly to the right of the middle on the building’s south wall. The 
wall to the right of this breakpoint has then been dragged down and an angle-shaped 
building has been created.  
See Edit lines and polygons for more details. 
IDA Indoor Climate and Energy 4.5 
© EQUA Simulation AB 2013 
68 
Note also that the program automatically allocates names to all the facades created by the 
introduction of new breakpoints. This allocation has not yet taken place in the figure 
above, but can be seen in the last figure in this part. 
The building can also be assigned geometry in the form of coordinates. This is done on 
the Properties page for building body part. This page is shown on the Side bar when the 
body part is selected. 
To add a new body part 
Add object of type "Building body". It is also possible to copy a body part from another 
(or the same) building. 
To move a body part 
Drag the body part with mouse. 
To rotate the body part, keep the Alt button pressed. 
To align (or stick) a side of the body part to another object (zone, another body part, a 
line in CAD drawing), place this side near to that object and keep it for a while with left 
mouse button pressed. 
It is also possible to move a body part by editing the coordinates on the Properties view 
of the Side Bar. This is the way to move the body part in z-direction. 
Notes. 1. To avoid confusions, do not move building body far away from the origin of the 
coordinate system. 
2. If you want to move the whole building (relative to the surrounding building) or rotate 
it, it is better to do it on the site view. In that case the building will be moved together 
with the building's coordinate system. 
To resize a body part 
When a body part is selected, the selection mark contains 8 active points at the corner and 
the center of the sides of the body part (of the bounding rectangle if the part is not 
rectangular). 
To resize the body part, drag an active point with mouse. 
To align (or stick) a side of the body part to another object (zone, another body part, a 
line in CAD drawing), drag this side near to that object and keep it for a while with left 
mouse button pressed. 
IDA Indoor Climate and Energy 4.5 
© EQUA Simulation AB 2013 
69 
It is possible to resize several objects (body parts and zones) together. 
It is also possible to resize the body part by editing the sizes on the Properties page of the 
Side Bar. This is the way to change the height of body part. 
To rename a body part 
See Object name. 
To remove a body part 
See Removing components. Note that the building should have at least one body part. 
To edit the roof 
Click the body part with right mouse button and select Edit roof from shortcut menu. See 
Editing roof for details. 
There is also a link on the Properties view of the Side Bar. 
7.2.3.3. Editing Roof 
The Roof Editor view shows the roof of a building body part. The numerical details are 
shown on the Properties page of the Side Bar. 
Initially the roof is flat and horizontal. 
The user can make the roof slanted (by editing the heights of the roof's corner) and/or divide 
the roof in parts. Each part should be a flat polygon and the parts should completely cover the 
roof. The roof may have vertical parts (slope=90), but parts with slope>90 are not supported  
When the user leaves the Roof Editor view, the program calculates the shape of the body part 
's sides and of the walls and the ceiling of the zones that are [partially] inside the body part. 
The user may also press "Apply" button to do the same calculations before leaving the view. 
To divide the roof 
The roof is divided in two steps 
1. Define the vertices (corners) of the roof parts. To do this, press "Edit vertices" button 
and then click with mouse the positions of the vertices. A new vertex is inserted at 
every click. Press "Done" button to finish this step. 
It is also possible to move and delete vertices in "Edit vertices" mode. See Editing 
lines for details. 
The coordinates of the vertices may be also edited on the Properties page of the Side 
Bar. 
2. Define the roof parts. To define a part, press "Add part" button, than mark all vertices 
of this part with mouse and press "Make part" button. Repeat this operation until the 
roof is completely covered by the parts. 
To edit the height of the roof 
Until the user has changed the heights of roof vertices, the height of a [simple horizontal] 
roof is specified on the building body part's Properties page on the Side Bar (the field 
labeled "z max"). 
To define non-horizontal roof (or parts of the roof), the user may edit the z-coordinates of 
the roof corners on the roof's Properties page. But often this is not convenient because 
some of heights might be calculated from other ones (the roof parts are flat, so it is 
enough to specify the height of 3 points on each part). For this reason IDA ICE provides 
a special tool to set the roof height. 
To set the heights of [some of] roof corners, do the following: 
1. Press "Set height" button (on the bottom of the Editing Roof view). IDA ICE will 
display a Mode dialog that indicates that you are now in "Setting roof height" mode. 
2. Select (by clicking with mouse) the vertices those height you would like to change or 
IDA Indoor Climate and Energy 4.5 
© EQUA Simulation AB 2013 
70 
to use for calculating other heights. Every time you click a vertex, its height becomes 
available for editing (just above the vertex in the drawing) and you can change it if 
desired. 
At every step, all heights that a selected or may be calculated from the selected ones 
are shown on the drawing. The changed (either by the user or by the program) are 
written in red, the unchanged are written in blue. The selected vertices are marked 
with green circles around them, the calculated ones are marked with red circle. The 
roof parts are filled in yellow (if flat) or cyan (if non-flat).  
3. If you select a vertex that is already selected, you will be prompted to choose either to 
unselect it or to edit its height.  
4. To accept the changes, click "Ok" button in the Mode dialog. You can also withdraw 
all changes by pressing "Cancel" button. 
Notes:  
1. If you change the height of the body part (field "z max" on the body part's Properties 
page) for a body part where the heights of the roof corners is explicitly defined, the 
whole roof (i.e., all vertices) will be moved up or down by the value of the change of "z 
max". 
2. It is allowed to define roof parts outside of the part of the building body. They will shade 
the building, but will be ignored in calculation of zone shape and adjacency. The roof 
parts should not intersect the boundary of the part of the building body. 
7.2.3.4. Edit the zone position and size in the floor plan 
Clicking on the Floor plan button in the zone’s form opens a form for the floor plan. (Can 
also be reached from the building level, by the Floor plan tab.) The position and size of a zone 
can be changed here. The active zone is indicated by a red border. Any other existing zones in 
the building, both on the same floor and on other floors, (paler gray lines), are also visible. All 
zones in the same floor, plus the building shape, can be edited.  
Documents you may be interested