Publication 1756-RM084L-EN-P - January 2007
Define a TAG Component        Chapter 6 Page 71
HSeverity
Specify the severity (1...500) of a high alarm condition.
Specify 
HSeverity := value
LLimit
Specify the low limit (REAL) for the alarm condition.
Specify 
LLimit := value
LSeverity
Specify the severity (1...500) of a low alarm condition.
Specify 
LSeverity := value
LLLimit
Specify the low-low limit (REAL) for the alarm condition.
Specify 
LLLimit := value
LLSeverity
Specify the severity (1...500) of a low-low alarm condition.
Specify 
LLSeverity := value
MinDurationPRE
Specify the minimum time (DINT) an alarm condition to remain true for the alarm to be 
considered active.
Specify 
MinDurationPRE := value
Deadband
Specify the deadband (REAL) for the high-high, high, low, and low-low levels.
Specify 
Deadband := value
ROCPosLimit
Specify the positive rate-of-change limit (REAL) for the alarm condition.
Specify 
ROCPosLimit := value
ROCPosSeverity
Specify the severity (1...500) of a positive rate-of-change alarm condition.
Specify 
ROCPosSeverity := value
ROCNegLimit
Specify the negative rate-of-change limit (REAL) for the alarm condition.
Specify 
ROCNegLimit := value
ROCNegSeverity
Specify the severity (1...500) of a negative rate-of-change alarm condition.
Specify 
ROCNegSeverity := value
ROCPeriod
Specify the time period (seconds) to evaluate rate-of-change conditions.
Specify 
ROCPeriod := value
AssocTag1
Specify a tag associated with the alarm.
Specify 
AssocTag1 := text
AssocTag2
Specify a tag associated with the alarm.
Specify 
AssocTag2 := text
AssocTag3
Specify a tag associated with the alarm.
Specify 
AssocTag3 := text
AssocTag4
Specify a tag associated with the alarm.
Specify 
AssocTag4 := text
HMICmd
Specify a command string for the HMI.
Specify 
HMICmd := text
Attribute
Description
Conversion pdf to jpg - Convert PDF to JPEG images in C#.net, ASP.NET MVC, WinForms, WPF project
How to convert PDF to JPEG using C#.NET PDF to JPEG conversion / converter library control SDK
.net convert pdf to jpg; change from pdf to jpg on
Conversion pdf to jpg - VB.NET PDF Convert to Jpeg SDK: Convert PDF to JPEG images in vb.net, ASP.NET MVC, WinForms, WPF project
Online Tutorial for PDF to JPEG (JPG) Conversion in VB.NET Image Application
convert pdf file into jpg format; changing pdf to jpg on
Publication 1756-RM084L-EN-P - January 2007
Chapter 6 Page 72        Define a TAG Component
Specify an ALMMSG Record for an ALARM_ANALOG Tag
Each ALARM_ANALOG tag can have its own alarm message.
ALMMSG:<language> <scope> <tag_name> <message_text> <alarm_type>
Where:
Specify Parameters for an 
DIGITAL_ALARM Tag
A DIGITAL_ALARM tag has these attributes.
Item
Identifies
language
Languages: EN-US (United States English), DE (Germany 
German), ES (Spain Spanish), FR (France French), IT 
(Italian), PT (Brazil Portuguese), JA (Japanese), KO 
(Korean), ZH (Chinese)
scope
Whether the alarm tag is program-scope or 
controller-scope.
tag_name
Name of the associated digital alarm tag.
message_text
Alarm message.
Enclose the message in double quotes (“ “). This is a 
unicode string.
alarm_type
Specify an analog alarm type.
Specify
For
HH
high-high alarm
H
high alarm
L
low alarm
LL
low-low alarm
POS
rate-of-change positive alarm
NEG
rate-of change negative alarm
Parameter
Description
EnableIn
Specify whether to enable the alarm tag. Enter 0 to disable the tag; enter 1 to enable the 
tag.
Specify 
EnableIn := BOOL
In
Specify the analog input to the alarm.
Specify 
In := BOOL
InFault
Specify the quality of the input fault data. Enter 1 for bad quality; enter 0 for good quality.
Specify 
InFault := BOOL
Condition
Specify the whether the alarm condition exists. Enter 1 for yes; enter 0 for no.
Specify 
Condition := BOOL
AckRequired
Specify whether the alarms requires acknowledgement. Enter 1 to enable; enter 0 to 
disable.
Specify 
AckRequired := BOOL
Latched
Specify the whether the alarm output is latched. Enter 1 for yes; enter 0 for no.
Specify 
Latched := BOOL
Online Convert Jpeg to PDF file. Best free online export Jpg image
start immediately to sort the files, try out some settings and then create the PDF files with the button at the bottom. The perfect conversion tool. JPG is the
change format from pdf to jpg; convert multiple pdf to jpg online
Online Convert PDF to Jpeg images. Best free online PDF JPEG
takes a few seconds. Web Security. Your PDF and JPG files will be deleted from our servers an hour after the conversion. No-one has
conversion of pdf to jpg; conversion pdf to jpg
Publication 1756-RM084L-EN-P - January 2007
Define a TAG Component        Chapter 6 Page 73
ProgAck
Specify whether the program can acknowledge the alarm condition. Enter 1 to enable; 
enter 0 to disable.
Specify 
ProgAck := BOOL
OperAck
Specify whether an operator can acknowledge the alarm condition. Enter 1 to enable; 
enter 0 to disable.
Specify 
OperAck := BOOL
ProgReset
Specify whether the program can reset the alarm condition. Enter 1 to enable; enter 0 to 
disable.
Specify 
ProgReset := BOOL
OperReset
Specify whether an operator can reset the alarm condition. Enter 1 to enable; enter 0 to 
disable.
Specify 
OperReset := BOOL
ProgSuppress
Specify whether the program can suppress an alarm. Enter 1 to enable; enter 0 to disable.
Specify 
ProgSuppress := BOOL
OperSuppress
Specify whether an operator can suppress an alarm. Enter 1 to enable; enter 0 to disable.
Specify 
OperSuppress := BOOL
ProgUnsuppress
Specify whether the program can unsuppress an alarm. Enter 1 to enable; enter 0 to 
disable.
Specify 
ProgUnsuppress := BOOL
OperUnsuppress
Specify whether an operator can unsuppress an alarm. Enter 1 to enable; enter 0 to 
disable.
Specify 
OperUnsuppress := BOOL
ProgDisable
Specify whether the program can disable an alarm. Enter 1 to enable; enter 0 to disable.
Specify 
ProgDisable := BOOL
OperDisable
Specify whether an operator can disable an alarm. Enter 1 to enable; enter 0 to disable.
Specify 
OperDisable := BOOL
ProgEnable
Specify whether the program can enable an alarm. Enter 1 to enable; enter 0 to disable.
Specify 
ProgEnable := BOOL
OperEnable
Specify whether an operator can enable an alarm. Enter 1 to enable; enter 0 to disable.
Specify 
OperEnable := BOOL
AlarmCountReset
Specify whether to reset the alarm count. Enter 1 to reset; enter 0 to not reset.
Specify 
AlarmCountReset := BOOL
UseProgTime
Specify how to timestamp alarm events. Enter 1 for programmatic timestamp; enter o for 
controller timestamp.
Specify 
UseProgTime := BOOL
ProgTime
Specify the programmatic timestamp (LINT).
Specify 
UseProgTime := value
Severity
Specify the severity (1...500) of the alarm condition.
Specify 
Severity := value
MinDurationPRE
Specify the minimum time (DINT) an alarm condition to remain true for the alarm to be 
considered active.
Specify 
MinDurationPRE := value
AssocTag1
Specify a tag associated with the alarm.
Specify 
AssocTag1 := text
AssocTag2
Specify a tag associated with the alarm.
Specify 
AssocTag2 := text
Parameter
Description
C# Image Convert: How to Convert Adobe PDF to Jpeg, Png, Bmp, &
C# sample code for PDF to jpg image conversion. This demo code convert PDF file all pages to jpg images. C# sample code for PDF to jpg image conversion.
changing pdf to jpg; change from pdf to jpg
C# Image Convert: How to Convert Dicom Image File to Raster Images
RasterEdge.XDoc.PDF.dll. Conversion from Dicom to Jpeg Image. String inputFilePath = @"C:\input.dcm"; String outputFilePath = @"C:\output.jpg"; // Convert dicom
change pdf to jpg on; convert multiple page pdf to jpg
Publication 1756-RM084L-EN-P - January 2007
Chapter 6 Page 74        Define a TAG Component
Specify an ALMMSG Record for an ALARM_DIGITAL Tag
Each DIGITAL_ALARM tag can have its own alarm message.
ALMMSG:<language> <scope> <tag_name> <message_text> <alarm_type>
Where:
AssocTag3
Specify a tag associated with the alarm.
Specify 
AssocTag3 := text
AssocTag4
Specify a tag associated with the alarm.
Specify 
AssocTag4 := text
HMICmd
Specify a command string for the HMI.
Specify 
HMICmd := text
Parameter
Description
Item
Identifies
language
Languages: EN-US (United States English), DE (Germany 
German), ES (Spain Spanish), FR (France French), IT 
(Italian), PT (Brazil Portuguese), JA (Japanese), KO 
(Korean), ZH (Chinese)
scope
The connection.
tag_name
Name of the associated digital alarm tag.
message_text
Alarm message.
Enclose the message in double quotes (“ “). This is a 
unicode string.
alarm_type
Specify AM for digital alarm.
JPEG to PDF Converter | Convert JPEG to PDF, Convert PDF to JPEG
similar software; Support a batch conversion of JPG to PDF with amazingly high speed; Get a compressed PDF file after conversion; Support
best pdf to jpg converter online; convert pdf to jpg file
JPG to DICOM Converter | Convert JPEG to DICOM, Convert DICOM to
Open JPEG to DICOM Converter first; Load JPG images from local folders in "File" in toolbar Windows Explorer; Select "Batch Conversion" & Choose "DICOM" in
change file from pdf to jpg; .net pdf to jpg
Publication 1756-RM084L-EN-P - January 2007
Define a TAG Component        Chapter 6 Page 75
Specify Attributes for an AXIS_CONSUMED, AXIS_GENERIC_DRIVE, AXIS_SERVO, 
AXIS_SERVO_DRIVE, and AXIS_VIRTUAL Tag
The axis tags have theseattributes.
Attribute
Description
Description
Provide information about the tag.
Specify 
Description := ”text
Comment
Provide information about a tag component.
Specify 
Comment<specifier> := ”text
Where the specifier is:
.bitnumber
for a bit in the tag
[element]
for an array element of the tag
.membername for a structure member of the tag
MotionGroup
Enter the name of the associated motion group, or enter <NA>.
Specify 
MotionGroup := text
MotionModule
Enter the name of the associated motion module, or enter <NA>.
Specify 
MotionModule := text
RotationalPosResolution
Specify the number of counts per motor revolution (1...[2
32
-1]).
Specify 
RotationalPosResolution := text
ConversionConstant
Specify the number of feedback counts per position unit. Enter a real number from 
1.0...1.0e
9
.
Specify 
ConversionConstant := value
OutputCamExecutionTargets
Specify the number of output cam execution targets (any positive number).
Specify 
OutputCamExecutionTargets := text
AxisState
Enter Axis-Ready, Direct Drive Control, Servo Control, Axis Faulted, or Axis Shutdown.
Specify 
AxisState := text
PositionUnits
Specify user-defined engineering units (rather than feedback units).
Specify 
PositionUnits := text
AverageVelocityTimebase
Specify the time in seconds for calculating the average velocity of the axis (any 
positivenumber).
Specify 
AverageVelocityTimebase := value
RotaryAxis
Specify the positioning mode for an axis. Enter Rotary or Linear.
Specify 
RotaryAxis := text
PositionUnwind
For a rotary axis, specify the distance (in feedback counts) used to perform electronic 
unwind (any positive number).
Specify 
PositionUnwind := value
HomeMode
Specify the homing mode. Enter Passive, Active, or Absolute.
Specify 
HomeMode := text
HomeDirection
For active homing sequences, except for the immediate sequence type, specify the desired 
homing direction. Enter Uni-directional Forward, Bi-directional Forward, Uni-directional 
Reverse, or Bi-directional Reverse.
Specify 
HomeDirection := text
HomeSequence
Specify the event that will cause the home position to be set. Enter Immediate, Switch, 
Marker, Switch-Marker, Torque Level, or Torque Level-Marker.
Specify 
HomeSequence := text
JPG to GIF Converter | Convert JPEG to GIF, Convert GIF to JPG
Open JPEG to GIF Converter first; Load JPG images from local folders in "File" in toolbar Windows Explorer; Select "Batch Conversion" & Choose "GIF" in "Output
convert pdf to jpg converter; convert .pdf to .jpg online
JPG to PNG Converter | Convert JPEG to PNG, Convert PNG to JPG
Open JPEG to PNG Converter first; Load JPG images from local folders in "File" in toolbar Windows Explorer; Select "Batch Conversion" & Choose "PNG" in "Output
change pdf into jpg; convert pdf into jpg online
Publication 1756-RM084L-EN-P - January 2007
Chapter 6 Page 76        Define a TAG Component
HomeConfigurationBits
Specify the home configuration bits. Enter a hexadecimal number.
Specify 
HomeConfigurationBits := 16#value
HomePosition
Specify the desired absolute position, in positioning units, for the axis after the homing 
sequence is complete (any positive number).
Specify 
HomePosition := value
HomeOffset
Specify the desired offset (any positive number) in position units the axis is to move, upon 
completion of the homing sequence, to reach the home position. In most cases, this value 
will be zero.
Specify 
HomeOffset := value
HomeSpeed
Specify the speed of the jog profile used in the first leg of the homing sequence (any 
positive number). The homing speed should be less than the maximum speed and greater 
than zero.
Specify 
HomeSpeed := value
HomeReturnSpeed
Specify speed of the jog profile used in the return leg(s) of an active homing sequence (any 
positive number). The return speed should be less than the maximum speed and greater 
than zero.
Specify 
HomeReturnSpeed := value
MaximumSpeed
Specify the maximum speed (any positive number).
Specify 
MaximumSpeed := value
MaximumAcceleration
Specify the maximum acceleration rate of the axis in position units/second (any 
positivenumber).
Specify 
MaximumAcceleration := value
MaximumDeceleration
Specify the maximum deceleration rate of the axis in position units/second (any 
positivenumber).
Specify 
MaximumDeceleration := value
ProgrammedStopMode
Specify how a specific axis will stop when the controller changes mode or a motion group 
stop (MGS) instruction is executed. Enter Fast Disable, Fast Stop, FastShutdown, 
HardDisable, or HardShutdown.
Specify 
ProgrammedStopMode := text
MasterInputConfigurationBits
Specify the master input configuration bits. Enter a hexadecimal number.
Specify 
MasterInputConfiguration := 16#value
MasterPositionFilter
Bandwidth
Specify the bandwidth in Hertz of the master position filter. 
Specify 
MasterPositionFilterBandwidth := value
AxisType
Specify the intended use of the axis. Enter Servo or Feedback Only. 
Specify 
AxisType := text
ServoLoopConfiguration
Specify the configuration of the loop. Enter Custom, Position Servo, Aux Position Servo, 
Dual Position Servo, Aux Command Servo, Dual Command Servo, Velocity Servo, or 
TorqueServo.
Specify 
ServoLoopConfiguration := text
FaultConfigurationBits
Specify the fault configuration bits. Enter a hexadecimal number.
Specify 
FaultConfigurationBits := 16#value
Attribute
Description
Publication 1756-RM084L-EN-P - January 2007
Define a TAG Component        Chapter 6 Page 77
AxisInfoSelect1
Specify an axis attribute to transmit, along with the actual position data, to the controller. 
Enter <none>, Position Command, Position Feedback, Aux Position Feedback, 
PositionError, Position Int. Error, Velocity Command, Velocity Feedback, VelocityError, 
Velocity Int. Error, Accel. Command, Accel. Feedback, Servo Output Level, 
MarkerDistance, Torque Command, Torque Feedback, Positive Dynamic Torque Limit, 
Negative Dynamic Torque Limit, Motor Capacity, Drive Capacity, Power Capacity, 
BusRegulator Capacity, Motor Electrical Angle, Torque Limit Source, DC Bus Voltage, 
Absolute Offset, Analog Input 1, or Analog Input 2.
Specify 
AxisInfoSelect1 := text
AxisInfoSelect2
Specify a second axis attribute to transmit, along with the actual position data, to the 
controller. Enter <none>, Position Command, Position Feedback, Aux Position Feedback, 
PositionError, Position Int. Error, Velocity Command, Velocity Feedback, VelocityError, 
Velocity Int. Error, Accel. Command, Accel. Feedback, Servo Output Level, 
MarkerDistance, Torque Command, Torque Feedback, Positive Dynamic Torque Limit, 
Negative Dynamic Torque Limit, Motor Capacity, Drive Capacity, Power Capacity, 
BusRegulator Capacity, Motor Electrical Angle, Torque Limit Source, DC Bus Voltage, 
Absolute Offset, Analog Input 1, or Analog Input 2.
Specify 
AxisInfoSelect2 := text
LDTTYpe
Specify the LDT device type. Enter PWM, Start/Stop Rising, or Start/Stop Falling.
Specify 
LDTType := text
LDTRecirculations
Only use this field if you specified PWM for LDTType. Specify the number of recirculations 
that the transducer is configured for so the 1756-HYD02 module knows how the LDT is 
configured.
Specify 
LDTRecirculations := value
LDTCalibrationConstant
Specify the calibration constant (also called gradient on some LDTs). This number is 
engraved on each LDT by the manufacturer. It specifies the characteristics of that 
individual transducer.
Specify 
LDTCalibrationConstant := value
LDTCalibrationConstantUnits
Specify the units of the calibration constant. Enter us/in or m/s.
Specify 
LDTCalibrationConstantUnits := text
LDTScaling
Define the relationship between the unit of measurement of the transducer and the 
system. This is necessary for calculating the conversion constant. The LDT length is used 
with the number of recirculations to calculate the minimum servo update period.
Specify 
LDTScaling := value
LDTScalingUnits
Specify the units of scaling. Enter us/in or m/s.
Specify 
LDTScalingUnits := text
LDTLength
Specify the length of the LDT.
Specify 
LDTLength := value
LDTLengthUnits
Specify the units of length. Enter us/in or m/s.
Specify 
LDTLengthUnits := text
SSICodeType
Specify the encoding on the data sent from an SSI transducer. Enter Binary or Grey.
Specify 
SSICodeType := text
SSIDataLength
Specify the data length (8...32 bits) of the SSI transducer. The default value is 13.
Specify 
SSIDataLength := text
SSIClockFrequency
Specify the SSI clock frequency (in kHz). Valid values are 208 (default) or 650.
Specify 
SSIClockFrequency := value
AbsoluteFeedbackEnable
Specify whether to enable absolute feedback. Enter 1 to enable absolute feedback. 
Otherwise, enter 0. Absolute feedback is always enabled for LDT.
Specify 
AbsoluteFeedbackEnable := value
Attribute
Description
Publication 1756-RM084L-EN-P - January 2007
Chapter 6 Page 78        Define a TAG Component
AbsoluteFeedbackOffset
Specify the absolute offset that is used to place the machine zero point at the desired 
location relative to the zero point of the LDT.
Specify 
AbsoluteFeedbackOffset := value
ServoFeedbackType
Specify the type of feedback device. Enter LDT (linear displacement transducer), 
AQB (A quadrature B), or SSI (synchronous serial interface)
Specify 
ServoFeedbackType := text
ServoPolarityBits
Specify the servo polarity bits. Enter a hexadecimal number.
Specify 
ServoPolarityBits := 16#value
VelocityFeedforwardGain
Specify the velocity feedforward gain (any positive number).
Specify 
VelocityFeedforwardGain := value
AccelerationFeedforwardGain
Specify the acceleration feedforward gain (any positive number).
Specify 
AccelerationFeedforwardGain := value
PositionProportionalGain
Specify the position proportional gain (any positive number).
Specify 
ProportionalPositionGain := value
PositionIntegralGain
Specify the position integral gain (any positive number).
Specify 
PositionIntegralGain := value
VelocityProportionalGain
Specify the velocity proportional gain (any positive number).
Specify 
VelocityProportionalGain := value
VelocityIntegralGain
Specify the velocity integral gain (any positive number).
Specify 
VelocityIntegralGain := value
VelocityScaling
Specify the velocity scaling attribute that is used to convert the output of the servo loop 
into equivalent voltage to an external velocity servo drive.
Specify 
VelocityScaling := value
TorqueScaling
Specify the torque scaling attribute that is used to convert the acceleration of the servo 
loop into equivalent % rated torque to the motor.
Specify 
TorqueScaling := value
OutputLPFilterBandwidth
Specify the bandwidth in Hertz of the servo’s low-pass digital output filter.
Specify 
OutputLPFilterBandwidth := value
IntegratorHoldEnable
Enter Disabled or Enabled.
Specify 
IntegratorHoldEnable := value
PositionDifferentialGain
Specify a position differential gain (PosD) to help predict a large overshoot ahead of time 
and make an attempt to correct before the overshoot actually occurs.
Specify 
PositionDifferentialGain := value
DirectionalScalingRatio
Specify the ratio between the extend direction gain and the retract direction gain.
Specify 
DirectionalScalingRatio := value
MaximumPositiveTravel
Specify the maximum positive position (any positive number) to be used for software 
overtravel checking, in position units.
Specify 
MaximumPositiveTravel := value
MaximumNegativeTravel
Specify the maximum negative position (any positive number) to be used for software 
overtravel checking, in position units.
Specify 
MaximumNegativeTravel := value
PositionErrorTolerance
Specify the how position error the servo module will tolerate (any positive number) before 
issuing a position error fault.
Specify 
PositionErrorTolerance := value
PositionLockTolerance
Specify the maximum position error the servo module will accept (any positive number) in 
order to indicate that the position lock status bit is set.
Specify 
PositionLockTolerance := value
Attribute
Description
Publication 1756-RM084L-EN-P - January 2007
Define a TAG Component        Chapter 6 Page 79
OutputLimit
Specify the maximum servo output voltage of a physical axis (any positive number).
Specify 
OutputLimit := value
DirectDriveRampRate
Specify the rate at which the analog output changes from the current value to the 
requested value when an MDO command is given (if ramp control is enabled). The ramp 
rate is specified in Volts per second.
Specify 
DirectDriveRampRate := value
OutputOffset
Specify a fixed voltage value (-10...10V) to add to the servo output value to correct 
axisdrift.
Specify 
OutputOffset := value
VelocityOffset
Specify a dynamic velocity correction to the output of the position servo loop, in position 
units/second (any positive number).
Specify 
VelocityOffset := value
TorqueOffset
Specify a dynamic torque command correction to the output of the velocity servo loop as a 
percentage of the velocity servo loop output (-100...100).
Specify 
TorqueOffset := value
FrictionCompensation
Specify the percentage (0...100) of output level added to a positive current servo output 
value, or subtracted from a negative current servo output value, for the purpose of moving 
an axis that is stuck in place due to static friction.
Specify 
FrictionCompensation := value
FrictionCompensationWindow
This window is defined as: 
command position - window attribute to command position + window attribute
While the command velocity is zero and the actual position is within this window, the 
friction compensation (or deadband compensation, for hydraulics) is applied proportionally 
to the position error. While the command velocity is non-zero, the full friction 
compensation is applied.
Specify 
FrictionCompensationWindow := value
BacklashStabilizationWindow
The window controls the backlash stabilization feature in the servo control loop. 
Mechanical backlash is a common problem in applications that utilize 
mechanicalgearboxes. 
Specify 
BacklashStabilizationWindow := value
BacklashReversalOffset
Specify the backlash reversal error to compensate for positional inaccuracy introduced by 
mechanical backlash.
Specify 
BacklashReversalOffset := value
HardOvertravelFaultAction
Specify the fault action taken when a hardware overtravel error occurs. Enter Shutdown, 
Disable Drive, Stop Motion, or Status Only. 
Specify 
HardOvertravelFaultAction := text
SoftOvertravelFaultAction
Specify the fault action taken when a software overtravel error occurs. Enter Shutdown, 
Disable Drive, Stop Motion, or Status Only.
Specify 
SoftOvertravelFaultAction := text
PositionErrorFaultAction
Enter Shutdown, Disable Drive, Stop Motion, or Status Only.
Specify 
PositionErrorFaultAction := text
FeedbackFaultAction
Specify the fault action to be taken when a feedback loss condition is detected. Enter 
Shutdown, Disable Drive, Stop Motion, or Status Only.
Specify 
FeedbackFaultAction := text
FeedbackNoiseFaultAction
Specify the fault action to be taken when excessive feedback noise is detected. Enter 
Shutdown, Disable Drive, Stop Motion, or Status Only.
Specify 
FeedbackNoiseFaultAction := text
Attribute
Description
Publication 1756-RM084L-EN-P - January 2007
Chapter 6 Page 80        Define a TAG Component
DriveFaultAction
Specify the fault action to be taken when a drive fault condition is detected. Enter 
Shutdown, Disable Drive, Stop Motion, or Status Only.
Specify 
DriveFaultAction := text
TestIncrement
Specify the amount of distance traversed by the axis when executing the output and 
feedback test (any positive number).
Specify 
TestIncrement := value
TuningTravelLimit
Specify the tuning travel limit in revolutions (any positive number).
Specify 
TuningTravelLimit := value
TuningSpeed
Specify the tuning speed in revolutions per second (any positive number).
Specify 
TuningSpeed := value
TuningTorque
Specify the tuning torque % rated (0...300).
Specify 
TuningTorque := value
DampingFactor
Specify the damping factor (0.5...2).
Specify 
DampingFactor := value
DriveModelTimeConstant
Specify the drive model time constant (1.0e
-6f
...1).
Specify 
DriveModelTimeConstant := value
PositionServoBandwidth
Specify the maximum allowable value for position bandwidth (0.001F...1000), given the 
damping factor. This parameter is disabled if the loop configuration is set to velocity.
Specify 
PositionServoBandwidth := value
VelocityServoBandwidth
Specify the unity gain bandwidth that is to be used to calculate the subsequent gains for a 
motion apply axis tuning (MAAT) instruction (0.001F...1000).
Specify 
VelocityServoBandwidth := value
TuningConfigurationBits
Specify the tuning configuration bits. Enter a hexadecimal number.
Specify 
TuningConfigurationBits := 16#value
TorqueLimitSource
Enter Not Limited, Negative Limit, Positive Limit, Bridge Limit, I(t) Limit, or MotorLimit.
Specify 
TorqueLimitSource := text
DriveUnit
Specify the units of the drive. Enter us/in or m/s.
Specify 
DriveUnit := text
PositionDataScaling
Specify the scaling method used on position values (0...255).
Specify 
PositionDataScaling := value
PositionDataScalingFactor
Specify the scaling factor for all position data in a drive (1...65535).
Specify 
PositionDataScalingFactor := value
PositionDataScalingExp
Specify the scaling exponent for all position data in a drive (-32768...32767).
Specify 
PositionDataScalingExp := value
VelocityDataScaling
Specify the scaling method to use for all velocity values (0...127).
Specify 
VelocityDataScaling := value
VelocityDataScalingFactor
Specify the scaling factor for all velocity data (1...65535).
Specify 
VelocityDataScalingFactor := value
VelocityDataScalingExp
Specify the scaling exponent for all velocity data (-32768...32767).
Specify 
VelocityDataScalingExp := value
AccelerationDataScaling
Specify the scaling method for all acceleration values (0...127).
Specify 
AccelerationDataScaling := value
AccelerationData
ScalingFactor
Specify the scaling factor for all acceleration data (1...65535).
Specify 
AccelerationDataScalingFactor := value
Attribute
Description