Edit Notification Policy option
This option allows you to edit a notification policy used by the  StruxureWare Data Center
Expert server to generate alarm notifications.
In the  Notification Policies view of the  Alarm Configuration perspective, you can select
a notification policy, and change the policy name, choose the thresholds and devices to
include in the notification policy; and add, edit, and remove alarm actions.
Note:  A notification policy must include at least one threshold or device and one alarm
action before it can be used to generate alarm notifications.
The right-click menu  Edit in the  Notification Policy Name list, and the  Edit Notification
Policy icon 
of the  Notification Policies  view, provide access to the "Edit Notification
Policy" display.
Delete Notification Policy option
This option in the Alarm Configuration perspective allows you to delete a notification policy
used by the   StruxureWare Data Center Expert  server to generate alarm notifications.
The right-click menu  Delete in the  Notification Policy Name list, and the  Delete
Notification Policy icon (
) of the  Notification Policies  view, allow you to delete the
selected notification policies.
Note:  The  Default notification policy cannot be deleted.
StruxureWare Data Center Expert 7.2.1
171
Best convert pdf to jpg - Convert PDF to JPEG images in C#.net, ASP.NET MVC, WinForms, WPF project
How to convert PDF to JPEG using C#.NET PDF to JPEG conversion / converter library control SDK
convert pdf to gif or jpg; convert pdf document to jpg
Best convert pdf to jpg - VB.NET PDF Convert to Jpeg SDK: Convert PDF to JPEG images in vb.net, ASP.NET MVC, WinForms, WPF project
Online Tutorial for PDF to JPEG (JPG) Conversion in VB.NET Image Application
convert pdf image to jpg; convert multipage pdf to jpg
Manage Alarm Actions option (Alarm Configuration menu)
This option allows you to create, modify, delete, and test the alarm actions that can be
included in the notification policies the  StruxureWare Data Center Expert server uses to
generate alarm notifications.
Alarm notifications can alert you, or other members of your organization, when the following
events occur:
• A threshold violation at a sensor the  StruxureWare Data Center Expert server
monitors.
• An alarm at a monitored SNMP or Modbus device.
You can create multiple versions of an alarm action, each with unique settings, for example,
assigning different severities that apply to the alarm action.
Once alarm actions have been created, you must add at least one action, and one alarm
or threshold, to at least one notification policy to generate alarm notifications.
Note:  Device alarms for every device the  StruxureWare Data Center Expert server
monitors are added to the  Default notification policy at discovery. You must manually add
alarm actions to this policy before the  StruxureWare Data Center Expert server can use it
to generate alarm notifications.
Two displays, "Add Alarm Action" and "Edit Alarm Action" in the  Notification Policies view,
also provide access to the  Manage Alarm Actions display.
"Manage Alarm Actions" display
Use this display to create, modify, delete and test alarm actions that can be included in
policies used by the  StruxureWare Data Center Expert server to generate alarm
notifications.
Type
Description
List
Displays the alarm actions currently configured
on the  StruxureWare Data Center Expert server.
You can click any column head ( Action or
Action Type ) to sort the list.
Create
Click to create a new alarm action.
Edit
Click to edit the selected alarm action.
Delete
Click to delete the selected alarm action from
the  StruxureWare Data Center Expert server.
Test
Click to test the selected alarm action.
Manage Alarm Actions
You use the "Alarm Action" wizard to create alarm actions that can be included in the
notification policies used by the  StruxureWare Data Center Expert server for alarm
notifications.
StruxureWare Data Center Expert 7.2.1
172
Online Convert Jpeg to PDF file. Best free online export Jpg image
Online JPEG to PDF Converter. Download Free Trial. Convert a JPG to PDF. You can drag and drop your JPG file in the box, and then start
best convert pdf to jpg; convert pdf to jpg
Online Convert PDF to Jpeg images. Best free online PDF JPEG
Download Free Trial. Convert a PDF File to JPG. Easy converting! We try to make it as easy as possible to convert your PDF files to JPG.
convert pdf into jpg format; batch pdf to jpg converter
Creating an alarm action
You must create at least one alarm action, and add it to a notification policy, before your
StruxureWare Data Center Expert server can generate alarm notifications.
All alarm actions are created using the same basic procedure.
1. Select  Manage Alarm Actions in the  Alarm Configuration menu.
2. Click  Create  to access the Alarm Action wizard.
3. In the "Choose Alarm Action Type" display, select the type of alarm action you want
to create, and click  Next.
4. In the "Configure Alarm Action" display for the selected action, define the settings you
want the action to use, and click  Finish to exit the wizard.
Note:  For information about the settings for the action you are creating, see the help
section for that action and its settings display.
Modifying an alarm action
You can use the same basic procedure to modify any type of alarm action.
All alarm actions are modified using the same basic procedure.
1.
Select  Manage Alarm Actions in the  Alarm Configuration menu.
2. Select the alarm action you want to modify, and click  Edit  to access the configuration
display for that action.
3. Define the settings you want the action to use, and click  Finish to exit the wizard.
Note:  For information about the settings for the action you are creating, see the help
section for that action and its settings display.
Deleting an alarm action
You can use the same basic procedure to delete any type of alarm action.
All alarm actions are deleted using the same basic procedure.
1. Select  Manage Alarm Actions in the  Alarm Configuration menu.
2. Select the alarm action you want to remove, and click  Delete .
3. Click  Finish to exit the wizard.
Note:  Deleting an alarm action in the Manage Alarm Actions display removes the
action from the  StruxureWare Data Center Expert server.
Testing an alarm action
You can test alarm actions to ensure that your  StruxureWare Data Center Expert server
can generate alarm notifications.
All alarm actions are tested using the same basic procedure.
StruxureWare Data Center Expert 7.2.1
173
C# Create PDF from images Library to convert Jpeg, png images to
Best and professional C# image to PDF converter SDK for Visual Studio .NET. Batch convert PDF documents from multiple image formats, including Jpg, Png, Bmp, Gif
batch convert pdf to jpg online; batch pdf to jpg converter online
VB.NET PDF Convert to Images SDK: Convert PDF to png, gif images
Best adobe PDF to image converter SDK for Visual Studio .NET. Convert PDF documents to multiple image formats, including Jpg, Png, Bmp, Gif, Tiff, Bitmap
convert pdf file to jpg file; reader convert pdf to jpg
1. Select  Manage Alarm Actions in the  Alarm Configuration menu.
2. Select the action you want to test, click  Test, and then click  OK.
Note:  You will need to verify the test was successful. For example, for a  Send
SNMPv1 Trap, verify the trap was received at the trap receiver; for a  Send E-mail,
verify the e-mail was received.
"Choose Alarm Action Type" display
Use this display to select the type of action you want to create.
Alert Action
Description
Send E-mail
Sends a message that uses the standard e-mail
format.
Send Short Message E-mail
Sends a message that uses the short-message
e-mail format.
Send Data to FTP Server
Sends data to an FTP server.
Send HTTP POST
Sends an HTTP POST.
Send SNMPv1 Trap
Sends an SNMPv1 trap.
Send SNMPv3 Inform
Sends an SNMPv3 inform.
"Alarm Action" displays
Each type of alarm action has its own configuration display.
Common alarm action settings
All alarm action types share a name field, severity selections, and an "Alarm Action
Scheduling" display.
Alarm action severity settings
Every alarm action type allows you to select up to five severities. The alarm action will only
trigger when used in a notification policy that is tied to an alarm threshold with a matching
severity.
In the following example, User1 will only receive an sms message if a critical severity
threshold is violated.
• An alarm action named "send_user1_sms” is created, and defined to send User1 an
SMS e-mail for critical events only.
• The “send_user1_sms” action is added to a notification policy called “sms messaging.”
• The "sms messaging" notification policy includes various thresholds and device
alarms. The alarms are of varying severity - some are set for critical, and some are
set for warning. If an alarm occurs, User1 will only receive an SMS message for those
thresholds and device alarms defined as critical.
You must select at least one severity.
StruxureWare Data Center Expert 7.2.1
174
VB.NET PDF - Convert PDF with VB.NET WPF PDF Viewer
Best WPF PDF Viewer control as well as a powerful PDF converter. Convert PDF to image file formats with high quality, support converting PDF to PNG, JPG
change from pdf to jpg on; convert pdf to jpg for
VB.NET Create PDF from images Library to convert Jpeg, png images
Best and professional image to PDF converter SDK Components to batch convert PDF documents in Visual Basic Support create PDF from multiple image formats in VB
.pdf to .jpg online; convert pdf file to jpg online
Severity
Description
Information
Typically used to set up an alarm action to
respond to events considered to be unimportant,
but important enough to require alert notifications
when they occur.
Warning
Typically used by SNMP devices to indicate a
condition exists that may require attention to
make sure it does not deteriorate into a critical
state. For example, a UPS that is running on
battery power during a power failure will shut
down its load equipment if its battery power is
depleted before power returns to normal.
Error
Typically used to indicate a sensor threshold
violation requires immediate attention. For
example, a high temperature violation that could
lead to equipment damage.
Critical
Typically used by SNMP devices to indicate an
operational failure requires immediate attention.
For example, a battery that needs to be replaced
can result in the loss of data at the UPS load
equipment if a power failure occurs.
Failure
Typically used to indicate an operational failure
requires immediate attention. For example,
communication with a camera pod was lost which
could lead to an undetected security violation.
"Alarm Action Schedule" display
Use this display to define the specific periods of time, for each day of the week, during which
an associated activity will be disabled (by default, scheduling is enabled 24 hours a day,
seven days a week).
Note:  This display is used to schedule when an alarm action will be enabled and disabled,
using the action's settings display.
The table provides cells for 15-minute increments, and columns for every day of the week.
You can do all of the following to schedule when an alarm action is enabled:
• Click a column title to enable or disable all of that day's cells.
• Drag your mouse from one cell to another cell in a column, to enable or disable a set
of cells.
• Drag your mouse from a cell in one column to a cell in another column, to enable or
disable an identical set of cells for each of the selected days.
• Click a single cell.
"Send E-mail" display
Use this display to define the settings for a  Send E-mail alarm action on the  StruxureWare
Data Center Expert server.
A name field, severity selections, and the "Alarm Action Scheduling" display that all alarm
action types share, are also available.
StruxureWare Data Center Expert 7.2.1
175
C# WPF PDF Viewer SDK to convert and export PDF document to other
Best PDF Viewer control as well as a powerful .NET WinForms application Convert PDF to image file formats with high quality, support converting PDF to PNG
change pdf to jpg on; convert pdf into jpg
C# PDF Convert to Tiff SDK: Convert PDF to tiff images in C#.net
Best C#.NET PDF converter SDK for converting PDF to Tiff in Visual Studio .NET project. Also supports convert PDF files to jpg, jpeg images.
change pdf into jpg; conversion pdf to jpg
Note:  Make sure the  StruxureWare Data Center Expert server's SMTP settings are all
defined properly.
E-mail tab
Element
Description
Add
Click to add an e-mail address to the address list.
Remove
Click to remove a selected e-mail address from
the address list.
Server E-mail Settings
Select to define the SMTP settings on the
StruxureWare Data Center Expert server.
Locale
Select to specify the locale to be used when
sending email messages or  Use Server
Locale (the default).
Advanced Options tab
Provides elements that further define what an e-mail can include, as well as an  Alarm
Action Scheduling button that allows you to select when an alarm action is enabled (all
time periods are enabled, by default).
Element
Description
Do Not Send Return-to-Normal Messages
Select if you do not want to receive an e-mail
when the threshold violation or alarm condition
returns to normal.
Minimize Header Usage
Select to minimize the size of the e-mail headers.
"Send Short Message E-mail" display
Use this display to define the settings for a  Send Short Message E-mail alarm action on
the  StruxureWare Data Center Expert server.
A name field, severity selections, and the "Alarm Action Scheduling" display that all alarm
action types share, are also available.
Note:  Make sure the  StruxureWare Data Center Expert server's SMTP settings are all
defined properly.
E-mail tab
Element
Description
Add
Click to add an e-mail address to the address list.
Remove
Click to remove a selected e-mail address from
the address list.
Subject
Enter a subject for the message; macros can be
used.
Message
Enter a message; macros can be used.
Server E-mail Settings
Select to define the SMTP settings on the
StruxureWare Data Center Expert server.
Locale
Select to specify the locale for email messages
or  Use Server Locale (the default).
StruxureWare Data Center Expert 7.2.1
176
Advanced tab
Provides elements that further define what an e-mail can include, as well as an  Alarm
Action Scheduling button that allows you to select when an alarm action is enabled (all
time periods are enabled, by default).
Element
Description
Do Not Send Return-to-Normal Messages
Select if you do not want to receive an e-mail
when the threshold violation or alarm condition
returns to normal.
Minimize Header Usage
Select to minimize the size of the e-mail headers.
Send both HTML and Plain Text Message
Select to include HTML formatted messages in
addition to plain text messages.
Message Size Limit (bytes)
Identify the maximum number of bytes used for
a message.
"Send Data to FTP Server" display
Use this display to define the settings for a  Send Data to FTP Server alarm action on
the  StruxureWare Data Center Expert server.
A name field, severity selections, and the "Alarm Action Scheduling" display that all alarm
action types share, are also available.
Primary and Backup tabs
You must define at least the  Primary tab elements.
Note:  The only difference between the two tabs is that the  Backup tab includes backup
settings.
Setting
Description
FTP Server Hostname
Identify the hostname or IP address of the FTP
server that will receive the data.
User ID
Identify the user identification needed to log on
to the FTP server.
Password
Identify the password needed to log on to the
FTP server.
Verify Password
Retype the password.
Target Directory
Identify the relative directory path to be used to
store the data at the FTP server. This should
always be a path relative to the default directory
associated with the user ID used to log on to the
FTP server.
If the directories on the path do not exist they
will be created automatically.
StruxureWare Data Center Expert 7.2.1
177
Note:  This  Target Directory field accepts
macros.
Base Filename
Identify the base filename to be used for storing
the data at the FTP server.
Alarm data will be stored in a file with this
name, followed by the *.nbalert.xml file
extension.
Note:  This  Base Filename field accepts
macros.
"Send HTTP POST" display
Use this display to define the settings for a  Send HTTP POST alarm action on the
StruxureWare Data Center Expert server.
A name field, severity selections, and the "Alarm Action Scheduling" display that all alarm
action types share, are also available.
Primary and Backup tabs
You must define at least the  Primary tab elements.
Note:  The only difference between the two tabs is that the  Backup tab includes backup
settings.
Element
Description
Target URL
Identify the web address, port and parameters of
the system to which HTTP POST data will be
posted.
Target User ID
Identify the user identification needed to post
HTTP data to the server at the specified  Target
URL.
Target Password
Identify the password needed to post HTTP data
to the server at the specified  Target URL.
Verify Password
Retype the password.
Advanced tab
Provides elements that further define what an HTTP POST can include, as well as an  Alarm
Action Scheduling button that allows you to select when an alarm action is enabled (all
time periods are enabled, by default).
Setting
Description
SSL Verify Options
Select  No verification,  Verify certificate, or
Verify certificate and hostname for HTTP
POSTs.
"Send SNMPv1 Trap" display
StruxureWare Data Center Expert 7.2.1
178
Use this display to define the settings for a  Send SNMPv1 Trap alarm action on the
StruxureWare Data Center Expert server.
A name field, severity selections, and the "Alarm Action Scheduling" display that all alarm
action types share, are also available.
Element
Description
Target Host Address
Identify the hostname or IP address of the
Network Management System (NMS) to which
traps will be sent.
Community String
Identify the community string that will be used
when sending traps to the target NMS.
Trap Port Number
Select the number of the port the target NMS
uses to receive SNMP traps.
Locale
Select to specify the locale to be used when
sending SNMP traps or  Use Server Locale (the
default).
"Send SNMPv3 Inform" display
Use this display to define the settings for a  Send SNMPv3 Inform alarm action on the
StruxureWare Data Center Expert server.
A name field, severity selections, and the "Alarm Action Scheduling" display that all alarm
action types share, are also available.
Element
Description
Target Host Address
Identify the Hostname or IP address of the
Network Management System (NMS) to which
informs will be sent.
Authentication User ID
Identify the user identification to be used when
sending SNMPv3 informs to the target NMS.
Authentication Protocol
Select  SHA-1 or  MD5 as the protocol used when
sending SNMPv3 informs to the target NMS.
Authentication Password
Type in the password to be used when sending
SNMPv3 informs to the target NMS.
Encryption Protocol
Select whether encryption will be used with the
SNMPv3, and if used, which protocol:  None,
DES, or  AES-128.
Encryption Password
Identify the encryption password to be used to
send SNMPv3 informs.
Inform Port Number
Identify the number of the port that the target
NMS identified in the  Primary tab uses to
receive SNMPv3 informs.
Locale
Select to specify the locale to be used when
sending SNMP v3 informs or  Use Server
Locale (the default).
StruxureWare Data Center Expert 7.2.1
179
Macros for alarm action settings
Three basic types of macros can be used for  Send Short Message E-mail and  Send Data
to FTP Server alarm action settings.
Location macros
One location macro is available for use when defining alarm action settings for SNMP and
Modbus devices monitored by the  StruxureWare Data Center Expert server.
Macro
Definition
Example
${LOCATION}
The location for a
StruxureWare Data Center
Expert SNMP or Modbus
device.
Test Lab
Identification macros
Identification macros are available for use when defining alarm action settings for SNMP
and Modbus devices monitored by the  StruxureWare Data Center Expert server.
Macro
Definition
Example
${SERIAL}
The serial number of the device.
WA0450111525
${IP}
The dotted-decimal IP address
of the device.
192.168.2.23
${HOSTNAME}
The hostname of the device.
device.apc.com
${MODEL}
The model of the device.
Symmetra 80K
${SERVERIP}
The dotted-decimal IP address
of the   StruxureWare Data
Center Expert  server.
192.168.2.10
${SERVERHOSTNAME}
The hostname of the
StruxureWare Data Center
Expert  server.
isxc.apc.com
${SERVERMODEL}
The model of the
StruxureWare Data Center
Expert  server.
StruxureWare Data Center
Expert
${TIMESTAMP}
The current UTC time (seconds
since 1/1/1970).
998885130
${DATE}
The current date (year-month-
day).
2010-03-27
${YEAR}
The current year.
2010
${MONTH}
The current month (2-digit
number, January=01).
03
${DAY}
The current day of the month (2-
digit number).
27
${TIME}
The current time (24-hour, hour-
minute-second).
23-30-01
StruxureWare Data Center Expert 7.2.1
180