Configuration
31
MBTCP DAServer User’s Guide
• 
Use Concept data structures (Longs): Select to read data from the PLC 
in concept data structure format for Long item types. If checked, the 
DAServer will process the data in the same register order as the Concept 
programming software.
Checked 
selected
Not checked 
not selected
The default is checked.
• 
Use Concept data structures (Reals): Select to read data from the PLC in 
concept data structure format for Real item types. If checked, the 
DAServer will process the data in the same register order as the Concept 
programming software.
Checked 
selected
Not checked 
not selected
The default is checked.
• 
Bit order format: The format of the bit order entered into the PLC.
When the Bit order format is selected as B1 B2 … B16, it means the 
bit order starts from left to right (the Most Significant Bit = Bit 1 and 
the Least Significant Bit = Bit 16).
When the Bit order format is selected as B16 B15 … B1, it indicates 
that the bit order starts from right to left (MSB = Bit 16 and LSB = Bit 
1).
The default is bit order starts from left to right.
• 
String variable style: PLC string-data format. Select the option for the 
style used by the device to store strings in its registers.
Full length (space padded)
C style (null terminated)
Pascal style (includes length specifier)
The default style is Full length.
• 
Register type: Select either Binary or BCD for the register type being 
used.
Binary
BCD
The default register type is Binary.
• 
Maximum address range: There are five sub-elements in this Maximum 
addressable registers box. The maximum addressable registers can be 
obtained from the Modicon Concept or Modsoft configuration programs. 
The PLC will return an error if a register outside of this range is used to 
read data. The MBTCP DAServer filters out registers outside of this range 
and logs error messages.
Discrete input: Enter the maximum number of addressable discrete 
inputs/read coils in the PLC.
The minimum value is 1 (one).
Combine pdf - Merge, append PDF files in C#.net, ASP.NET, MVC, Ajax, WinForms, WPF
Provide C# Demo Codes for Merging and Appending PDF Document
acrobat split pdf into multiple files; break a pdf into multiple files
Combine pdf - VB.NET PDF File Merge Library: Merge, append PDF files in vb.net, ASP.NET, MVC, Ajax, WinForms, WPF
VB.NET Guide and Sample Codes to Merge PDF Documents in .NET Project
reader combine pdf; pdf merger
32
Chapter 2
MBTCP DAServer User’s Guide
The maximum value is 65536.
The default value is 65536.
Coil: Enter the maximum number of addressable write coils in the 
PLC.
The minimum value is 1 (one).
The maximum value is 65536.
The default value is 65536.
Input register: Enter the maximum number of addressable input 
registers in the PLC.
The minimum value is 1 (one).
The maximum value is 65536.
The default value is 65536.
Holding register: Enter the maximum number of addressable holding 
registers in the PLC.
The minimum value is 1 (one).
The maximum value is 65536.
The default value is 65536.
Extended register: Enter the maximum number of addressable 
extended registers in the PLC.
The minimum value is 1 (one).
The maximum value is 98303.
The default value is 98303.
• 
Block I/O size: This Block I/O Sizes box contains seven sub-elements. 
The DAServer uses the block I/O sizes to maximize data throughput. The 
MBTCP DAServer uses a 256-byte buffer to read or write data to the PLC.  
The maximum value is the maximum number of registers that can be read 
or written from/to the PLC in one command.
Discrete input/coil read: Enter the maximum number of discrete 
inputs or coils to read at one time.
The minimum value is 1 (one).
The maximum value is 1976. 
The default value is 1976.
Coil write: Enter the maximum number of coils to write at one time.
The minimum value is 1 (one).
The maximum value is 800.
The default value is 800.
Holding register read: Enter the maximum number of holding 
registers to read at one time.
The minimum value is 1 (one).
Online Merge PDF files. Best free online merge PDF tool.
RasterEdge C#.NET PDF document merging toolkit (XDoc.PDF) is designed to help .NET developers combine PDF document files created by different users to one PDF
append pdf files reader; reader combine pdf pages
C# PDF: C#.NET PDF Document Merging & Splitting Control SDK
PDF Merging & Splitting Application. This C#.NET PDF document merger & splitter control toolkit is designed to help .NET developers combine PDF document files
pdf mail merge; pdf merge
Configuration
33
MBTCP DAServer User’s Guide
The maximum value is 123.
The default value is 123.
Holding register write: Enter the maximum number of holding 
registers to write at one time.
The minimum value is 1 (one).
The maximum value is 100.
The default value is 100.
Input register read: Enter the maximum number of input registers to 
read at one time.
The minimum value is 1 (one).
The maximum value is 123.
The default value is 123.
Extended register read: Enter the maximum number of extended 
registers to read at one time.
The minimum value is 1 (one).
The maximum value is 122.
The default value is 122.
Extended register write: Enter the maximum number of extended 
registers to write at one time.
The minimum value is 1 (one).
The maximum value is 120.
The default value is 120.
TSXPremium Object
From the TCPIP_PORT branch of the DAServer hierarchy, you can also create 
a TSXPremium object.
To add TSXPremium objects to your MBTCP hierarchy
1. Right-click on your TCPIP_PORT branch.
2. Select Add TSXPremium Object.
A new TSXPremium object is created as a node in the hierarchy tree.
It is named New_TSXPremium_000 by default.
Note  You can add up to 1024 of this type of object to the hierarchy. 
3. Rename as appropriate.
The New_TSXPremium_000 Parameters configuration view is 
displayed.
VB.NET PDF: Use VB.NET Code to Merge and Split PDF Documents
Combine End Sub Private Sub Combine(source As List(Of [String]), destn As [String]) Implements PDFDocument.Combine End Sub. APIs for Splitting PDF document in
merge pdf files; add pdf together
C# PowerPoint - Merge PowerPoint Documents in C#.NET
Combine and Merge Multiple PowerPoint Files into One Using C#. This part illustrates how to combine three PowerPoint files into a new file in C# application.
all jpg to one pdf converter; .net merge pdf files
34
Chapter 2
MBTCP DAServer User’s Guide
This configuration view has 10 elements that are configurable.
• 
Network address: Enter the host name or IP address of the PLC.
The maximum number of characters is 255.
The minimum number of characters is 1 (one).
The first and last characters must be alphanumeric, and the remaining 
characters must be alphanumeric, a "-" (hyphen), or a "." (period). No 
blank spaces are allowed.
The default value is 1.0.0.0.
• 
Reply timeout (sec): Enter the amount of time the server will wait for an 
acknowledgment.
The minimum value is 1 (one).
The maximum value is 60.
The default value is 3 (three).
• 
Maximum outstanding messages: Enter the maximum number of 
outstanding messages in the queue for the PLC.
The minimum value is 1 (one).
The maximum value is 20.
The default value is 4 (four).
• 
Use Concept data structures (Longs): Select to read data from the PLC 
in concept data structure format for Long item types. If checked, the 
DAServer will process the data in the same register order as the Concept 
programming software.
C# Word - Merge Word Documents in C#.NET
Combine and Merge Multiple Word Files into One Using C#. This part illustrates how to combine three Word files into a new file in C# application.
pdf combine files online; build pdf from multiple files
C# PDF File Split Library: Split, seperate PDF into multiple files
Split PDF document by PDF bookmark and outlines. Also able to combine generated split PDF document files with other PDF files to form a new PDF file.
add pdf files together online; pdf combine pages
Configuration
35
MBTCP DAServer User’s Guide
Checked 
selected
Not checked 
not selected
The default is checked.
• 
Use Concept data structures (Reals): Select to read data from the PLC in 
concept data structure format for Real item types. If checked, the 
DAServer will process the data in the same register order as the Concept 
programming software.
Checked 
selected
Not checked 
not selected
The default is checked.
• 
Bit order format: The format of the bit order entered into the PLC.
When the Bit order format is selected as B1 B2 … B16, it means the 
bit order starts from left to right (the Most Significant Bit = Bit 1 and 
the Least Significant Bit = Bit 16).
When the Bit order format is selected as B16 B15 … B1, it indicates 
that the bit order starts from right to left (MSB = Bit 16 and LSB = Bit 
1).
The default is bit order starts from left to right.
• 
String variable style: PLC string-data format. Select the option for the 
style used by the device to store strings in its registers.
Full length (space padded)
C style (null terminated)
Pascal style (includes length specifier)
The default style is Full length.
• 
Register type: Select either Binary or BCD for the register type being 
used.
Binary
BCD
The default register type is Binary.
• 
Maximum address range: There are four sub-elements in this Maximum 
addressable registers box. The maximum addressable registers can be 
obtained from the Modicon Concept or Modsoft configuration programs. 
The PLC will return an error if a register outside of this range is used to 
read data. The MBTCP DAServer filters out registers outside of this range 
and logs error messages.
Discrete input: Enter the maximum number of addressable discrete 
inputs or read coils in the PLC.
The minimum value is 1 (one).
The maximum value is 65536.
The default value is 65536.
VB.NET TIFF: Merge and Split TIFF Documents with RasterEdge .NET
filePath As [String], docList As [String]()) TIFFDocument.Combine(filePath, docList) End to provide powerful & profession imaging controls, PDF document, tiff
asp.net merge pdf files; combine pdfs online
VB.NET PowerPoint: Merge and Split PowerPoint Document(s) with PPT
Just like we need to combine PPT files, sometimes, we also want to separate a Note: If you want to see more PDF processing functions in VB.NET, please follow
c# merge pdf files into one; scan multiple pages into one pdf
36
Chapter 2
MBTCP DAServer User’s Guide
Coil: Enter the maximum number of addressable write coils in the 
PLC.
The minimum value is 1 (one).
The maximum value is 65536.
The default value is 65536.
Input register: Enter the maximum number of addressable input 
registers in the PLC.
The minimum value is 1 (one).
The maximum value is 65536.
The default value is 65536.
The default value is 65536.
Holding register: Enter the maximum number of addressable holding 
registers in the PLC.
The minimum value is 1 (one).
The maximum value is 65536.
The default value is 65536.
• 
Block I/O size: The Block I/O Sizes box contains five sub-elements. The 
DAServer uses the block I/O sizes to maximize data throughput. The 
MBTCP DAServer uses a 256-byte buffer to read or write data to the PLC.  
The maximum value is the maximum number of registers that can be read 
or written from/to the PLC in one command.
Discrete input/coil read: Enter the maximum number of discrete 
inputs or coils to read at one time.
The minimum value is 1 (one).
The maximum value is 1000. 
The default value is 1000.
Coil write: Enter the maximum number of coils to write at one time.
The minimum value is 1 (one).
The maximum value is 800.
The default value is 800.
Holding register read: Enter the maximum number of holding 
registers to read at one time.
The minimum value is 1 (one).
The maximum value is 123.
The default value is 123.
Holding register write: Enter the maximum number of holding 
registers to write at one time.
The minimum value is 1 (one).
The maximum value is 100.
Configuration
37
MBTCP DAServer User’s Guide
The default value is 100.
Input register read: Enter the maximum number of input registers to 
read at one time.
The minimum value is 1 (one).
The maximum value is 123.
The default value is 123.
ModbusPLC Object
The ModbusPLC object is created from the TCPIP_PORT branch of the 
DAServer hierarchy. It is intended for PLCs/controllers that use the Modbus 
protocol but not in the list of the supported hardware described in Appendix A, 
Supported DASMBTCP Hardware and Firmware. However, the 
PLCs/controllers need to conform to and comply with the Modbus 
specifications as listed in Appendix B, The Modbus Protocol.
To add ModbusPLC objects to your MBTCP hierarchy
1. Right-click on your TCPIP_PORT branch.
2. Select Add ModbusPLC Object.
A new ModbusPLC object is created as a node in the hierarchy tree.
It is named New_ModbusPLC_000 by default.
Note  You can add up to 1024 of this type of object to the hierarchy. 
3. Rename as appropriate.
The New_ModbusPLC_000 Parameters configuration view is 
displayed.
38
Chapter 2
MBTCP DAServer User’s Guide
This configuration view has 13 elements that are configurable.
• 
Network address: Enter the host name or IP address of the PLC.
The maximum number of characters is 255.
The minimum number of characters is 1 (one).
The first and last characters must be alphanumeric, and the remaining 
characters must be alphanumeric, a "-" (hyphen) or a "." (period). No 
blank spaces are allowed.
The default value is 1.0.0.0.
• 
Port number: Enter the port (socket) number.
The default port number is 502.
Note  The MBTCP DAServer uses port 502 as the default port number to 
contact the PLC. The port number in this display is dimmed and non 
changeable. However, the actual port to be used by the Generic Modbus PLCs 
directly under the TCPIP_PORT object is available at that node and is 
configurable using the ModbusPLC Object. Controllers configured under the 
ModbusBridge object will always use port number 502.
• 
Reply timeout (sec): Enter the amount of time the server will wait for an 
acknowledgment.
The minimum value is 1 (one).
The maximum value is 60.
Configuration
39
MBTCP DAServer User’s Guide
The default value is 3 (three).
• 
Maximum outstanding messages: Enter the maximum number of 
outstanding messages in the queue for the PLC.
The minimum value is 1 (one).
The maximum value is 20.
The default value is 4 (four).
• 
Use Concept data structures (Longs): Select to read data from the PLC 
in concept data structure format for Long item types. If checked, the 
DAServer will process the data in the same register order as the Concept 
programming software.
Checked 
selected
Not checked 
not selected
The default is checked.
• 
Use Concept data structures (Reals): Select to read data from the PLC in 
concept data structure format for Real item types. If checked, the 
DAServer will process the data in the same register order as the Concept 
programming software.
Checked 
selected
Not checked 
not selected
The default is checked.
• 
Support multiple coil write: Select for the PLC to write to multiple coils 
in one message with the Modbus protocol function code 15 (0x0F). If not 
selected, the PLC will write to a single coil in one message with the 
Modbus protocol function code 5 (0x05).
Checked 
selected
Not checked 
not selected
The default is checked.
• 
Support multiple register write: Select for the PLC to write to multiple 
registers in one message with the Modbus protocol function code 16 
(0x10). If not selected, the PLC will write to a single register in one 
message with the Modbus protocol function code 6 (0x06).
Checked 
selected
Not checked 
not selected
The default is checked.
40
Chapter 2
MBTCP DAServer User’s Guide
Note  Certain things have to be understood when the Support Multiple 
Register Write Parameter is not selected in the Generic PLC configuration.  
When this parameter is not selected, it implies that the PLC does not 
support multiple register writes and the server will only write single 
registers to the PLC.
What this implies is that items that contain more than one register cannot 
be written either. For example, items such as 4xxxxx L, 4xxxxx I, 4xxxxx 
U, 4xxxxx F, 4xxxxx-4xxxxx M, 5 HRL, 5 HRF, 5 PV, 5 HRU, and 
4xxxxx-4xxxxx cannot be written. When you try to write to the PLC with 
this parameter not selected, the following error message will be logged to 
the logger, "Cannot write to multiple register item: 4xxxxx L on Node: 
TCPPort.GenPLC. The PLC configurable parameter Support Multiple 
Register Write is not checked."
• 
Bit order format: The format of the bit order entered into the PLC.
When the Bit order format is selected as B1 B2 … B16, it means the 
bit order starts from left to right (the Most Significant Bit = Bit 1 and 
the Least Significant Bit = Bit 16).
When the Bit order format is selected as B16 B15 … B1, it indicates 
that the bit order starts from right to left (MSB = Bit 16 and LSB = Bit 
1).
The default is bit order starts from left to right.
• 
Register size (digits): Select the correct register size for addressing the 
PLC.
4-digit is used for addressing the Modbus Generic 4-Digit PLCs.
5-digit applies to the Modbus Generic 5-Digit PLCs.
6-digit is used for addressing the Modbus Generic 6-Digit PLCs.
The default value is 6, for the Modbus Generic 6-Digit PLCs.
Note  The selection for the Register size determines the maximum 
address range. They are changeable as in other supported PLCs listed in 
Appendix A, Supported DASMBTCP Hardware and Firmware.
For 4-digit, the maximum value is 999.
For 5-digit, the maximum value is 9999.
For 6-digit, the maximum value is 65536.
• 
String variable style: PLC string-data format. Select the option for the 
style used by the device to store strings in its registers.
Full length ( space padded)
C style (null terminated)
Pascal style (includes length specifier)
The default style is Full length.
• 
Register type: Select either Binary or BCD for the register type being 
used.
Binary
BCD