Configuration
51
MBTCP DAServer User’s Guide
Checked 
selected
Not checked 
not selected
The default is checked.
• 
Use Concept data structures (Reals): Select to read data from the PLC in 
concept data structure format for Real item types. If checked, the 
DAServer will process the data in the same register order as the Concept 
programming software.
Checked 
selected
Not checked 
not selected
The default is checked.
• 
Bit order format: The format of the bit order entered into the PLC.
When the Bit order format is selected as B1 B2 … B16, it means the 
bit order starts from left to right (the Most Significant Bit = Bit 1 and 
the Least Significant Bit = Bit 16).
When the Bit order format is selected as B16 B15 … B1, it indicates 
that the bit order starts from right to left (MSB = Bit 16 and LSB = Bit 
1).
The default is bit order starts from left to right.
• 
String variable style: PLC string-data format. Select the option for the 
style used by the device to store strings in its registers.
Full length (space padded)
C style (null terminated)
Pascal style (includes length specifier)
The default style is Full length.
• 
Register type: Select either Binary or BCD for the register type being 
used.
Binary
BCD
The default register type is Binary.
• 
Maximum address range: There are five sub-elements in this Maximum 
addressable registers box. The maximum addressable registers can be 
obtained from the Modicon Concept or Modsoft configuration programs. 
The PLC will return an error if a register outside of this range is used to 
read data. The MBTCP DAServer filters out registers outside of this range 
and logs error messages.
Discrete input: Enter the maximum number of addressable discrete 
inputs or read coils in the PLC.
The minimum value is 1 (one).
The maximum value is 65536.
The default value is 65536.
C# merge pdf - Merge, append PDF files in C#.net, ASP.NET, MVC, Ajax, WinForms, WPF
Provide C# Demo Codes for Merging and Appending PDF Document
split pdf into multiple files; acrobat merge pdf files
C# merge pdf - VB.NET PDF File Merge Library: Merge, append PDF files in vb.net, ASP.NET, MVC, Ajax, WinForms, WPF
VB.NET Guide and Sample Codes to Merge PDF Documents in .NET Project
c# merge pdf; break pdf file into multiple files
52
Chapter 2
MBTCP DAServer User’s Guide
Coil: Enter the maximum number of addressable write coils in the 
PLC.
The minimum value is 1 (one).
The maximum value is 65536.
The default value is 65536.
Input register: Enter the maximum number of addressable input 
registers in the PLC.
The minimum value is 1 (one).
The maximum value is 65536.
The default value is 65536.
Holding register: Enter the maximum number of addressable holding 
registers in the PLC.
The minimum value is 1 (one).
The maximum value is 65536.
The default value is 65536.
Extended register: Enter the maximum number of addressable 
extended registers in the PLC.
The minimum value is 1 (one).
The maximum value is 98303.
The default value is 98303.
• 
Block I/O size: The Block I/O Sizes box contains seven sub-elements. 
The DAServer uses Block I/O Sizes to maximize data throughput. The 
MBTCP DAServer uses a 256-byte buffer to read or write data to the PLC. 
The maximum value is the maximum number of registers that can be read 
or written from/to the PLC in one command.
Discrete input/coil read: Enter the maximum number of discrete 
inputs or coils to read at one time.
The minimum value is 1 (one).
The maximum value is 1976. 
The default value is 1976.
Coil write: Enter the maximum number of coils to write at one time.
The minimum value is 1 (one).
The maximum value is 800.
The default value is 800.
Holding register read: Enter the maximum number of holding 
registers to read at one time.
The minimum value is 1 (one).
The maximum value is 123.
The default value is 123.
C# WPF PDF Viewer SDK to view, annotate, convert and print PDF in
C#, C# convert PDF to HTML, C# convert PDF to Word, C# extract text from PDF, C# convert PDF to Jpeg, C# compress PDF, C# print PDF, C# merge PDF files, C# view
batch pdf merger online; combine pdf online
C# HTML5 PDF Viewer SDK to view PDF document online in C#.NET
C#, C# convert PDF to HTML, C# convert PDF to Word, C# extract text from PDF, C# convert PDF to Jpeg, C# compress PDF, C# print PDF, C# merge PDF files, C# view
best pdf combiner; pdf merger online
Configuration
53
MBTCP DAServer User’s Guide
Holding register write: Enter the maximum number of holding 
registers to write at one time.
The minimum value is 1 (one).
The maximum value is 100.
The default value is 100.
Input register read: Enter the maximum number of input registers to 
read at one time.
The minimum value is 1 (one).
The maximum value is 123.
The default value is 123.
Extended register read: Enter the maximum number of extended 
registers to read at one time.
The minimum value is 1 (one).
The maximum value is 122.
The default value is 122.
Extended register write: Enter the maximum number of extended 
registers to write at one time.
The minimum value is 1 (one).
The maximum value is 120.
The default value is 120.
ModbusPLCRS Object
The ModbusPLCRS object is added to the DAServer hierarchy from the 
ModbusBridge branch.
To add ModbusPLCRS objects to your MBTCP hierarchy
1. Right-click on your ModbusBridge branch.
2. Select Add ModbusPLCRS Object from the shortcut menu.
A new ModbusPLCRS object is created as a node in the hierarchy 
tree.
It is named New_ModbusPLCRS_000 by default.
Note  You can add up to 247 of this type of object to the hierarchy. 
3. Rename as appropriate.
The New_ModbusPLCRS_000 Parameters configuration view is 
displayed.
C# PDF Image Extract Library: Select, copy, paste PDF images in C#
PDF. |. Home ›› XDoc.PDF ›› C# PDF: Extract PDF Image. A powerful C#.NET PDF control compatible with windows operating system and built on .NET framework.
acrobat combine pdf files; add pdf together one file
C# PDF Convert to Jpeg SDK: Convert PDF to JPEG images in C#.net
›› C# PDF: Convert PDF to Jpeg. C# PDF - Convert PDF to JPEG in C#.NET. C#.NET PDF to JPEG Converting & Conversion Control. Convert PDF to JPEG Using C#.NET.
attach pdf to mail merge in word; batch pdf merger
54
Chapter 2
MBTCP DAServer User’s Guide
This configuration view has 11 configurable elements.
• 
PLC unit ID: Enter the PLC unit ID.
The Bridge's internal configuration contains a UnitID parameter which 
can be set to override the Unit_ID address received in the message from 
the server. In other words, when the Unit_ID box is 0 (zero) the bridge 
routes the message to its configured Slave device. If the server's Unit_ID 
is set to 0 (zero), the message will be delivered to the Slave device whose 
address is defined in the UnitID box of the Bridge. If the server's Unit_ID 
is set to a non-zero value (range 1…255), the message will be delivered to 
the Slave device at that numerical address, regardless of the contents of the 
UnitID box in the Bridge.
The minimum value is 0 (zero).
The maximum value is 255.
The default value is 1 (one).
• 
Reply timeout (sec): Enter the amount of time the server will wait for an 
acknowledgment.
The minimum value is 1 (one).
The maximum value is 60.
The default value is 3 (three).
• 
Use Concept data structures (Longs): Select to read data from the PLC 
in concept data structure format for Long item types. If checked, the 
DAServer will process the data in the same register order as the Concept 
programming software.
C# PDF Text Extract Library: extract text content from PDF file in
XDoc.PDF ›› C# PDF: Extract PDF Text. C# PDF - Extract Text from PDF in C#.NET. Best C#.NET PDF text extraction library and component for free download.
pdf merge files; pdf mail merge plug in
C# PDF insert image Library: insert images into PDF in C#.net, ASP
Merge several images into PDF. Insert images into PDF form field. Access to freeware download and online C#.NET class source code.
c# merge pdf pages; reader merge pdf
Configuration
55
MBTCP DAServer User’s Guide
Checked 
selected
Not checked 
not selected
The default is checked.
• 
Use Concept data structures (Reals): Select to read data from the PLC in 
concept data structure format for Real item types. If checked, the 
DAServer will process the data in the same register order as the Concept 
programming software.
Checked 
selected
Not checked 
not selected
The default is checked.
• 
Support multiple coil write: Select for the PLC to write to multiple coils 
in one message. If not selected, the PLC will write to a single coil in one 
message.
Checked 
selected
Not checked 
not selected
The default is checked.
• 
Support multiple register write: Select for the PLC to write to multiple 
registers in one message. If not selected, the PLC will write to a single 
register in one message.
Checked 
selected
Not checked 
not selected
The default is checked.
Note  Certain things have to be understood when the Support Multiple 
Register Write Parameter is not selected in the Generic PLC configuration.  
When this parameter is not selected, it implies that the PLC does not 
support multiple register writes and the server will only write single 
registers to the PLC.
What this implies is that items that contain more than one register cannot 
be written either. For example, items such as 4xxxxx L, 4xxxxx I, 4xxxxx 
U, 4xxxxx F, 4xxxxx-4xxxxx M, 5 HRL, 5 HRF, 5 PV, 5 HRU, and 
4xxxxx-4xxxxx cannot be written. When you try to write to the PLC with 
this parameter not selected, the following error message will be logged to 
the logger, "Cannot write to multiple register item: 4xxxxx L on Node: 
TCPPort.GenPLC. The PLC configurable parameter Support Multiple 
Register Write is not checked."
• 
Bit order format: The format of the bit order entered into the PLC.
When the Bit order format is selected as B1 B2 … B16, it means the 
bit order starts from left to right (the Most Significant Bit = Bit 1 and 
the Least Significant Bit = Bit 16).
When the Bit order format is selected as B16 B15 … B1, it indicates 
that the bit order starts from right to left (MSB = Bit 16 and LSB = Bit 
1).
The default is bit order starts from left to right.
C# PDF Page Insert Library: insert pages into PDF file in C#.net
RasterEdge offers detailed guidances for each of those page processing functions, such as how to merge PDF document files by C# code, how to rotate PDF
pdf merge comments; break pdf into multiple files
C# WinForms Viewer: Load, View, Convert, Annotate and Edit PDF
overview. It provides plentiful C# class demo codes and tutorials on How to Use XDoc.PDF in C# .NET Programming Project. Plenty
acrobat merge pdf files; reader create pdf multiple files
56
Chapter 2
MBTCP DAServer User’s Guide
• 
Register size (digits): Select the correct register size for addressing the 
PLC.
4-digit is used for addressing the Modbus Generic 4-Digit PLCs.
5-digit applies to the Modbus Generic 5-Digit PLCs.
6-digit is used for addressing the Modbus Generic 6-Digit PLCs.
The default value is 6, for the Modbus Generic 6-Digit PLCs.
Note  The selection for the Register size determines the maximum 
address range. They are changeable as in other supported PLCs listed in 
Appendix A, Supported DASMBTCP Hardware and Firmware.
For 4-digit, the maximum value is 999.
For 5-digit, the maximum value is 9999.
For 6-digit, the maximum value is 65536.
• 
String variable style: PLC string-data format. Select the option for the 
style used by the device to store strings in its registers.
Full length (space padded)
C style (null terminated)
Pascal style (includes length specifier)
The default style is Full length.
• 
Register type: Select either Binary or BCD for the register type being 
used.
Binary
BCD
The default register type is Binary.
• 
Block I/O size: This Block I/O Sizes box contains four sub-elements. The 
DAServer uses Block I/O Sizes to maximize data throughput. The 
MBTCP DAServer uses a 256-byte buffer to read or write data to the PLC. 
The maximum value is the maximum number of registers that can be read 
or written from/to the PLC in one command.
Discrete input/coil read: Enter the maximum number of discrete 
inputs or coils to read at one time.
The minimum value is 1 (one).
The maximum value is 1976. 
The default value is 1976.
Coil write: Enter the maximum number of coils to write at one time.
The minimum value is 1 (one).
The maximum value is 800.
The default value is 800.
Register read: Enter the maximum number of extended registers to 
read at one time.
The minimum value is 1 (one).
Configuration
57
MBTCP DAServer User’s Guide
The maximum value is 122.
The default value is 122.
Register write: Enter the maximum number of holding registers to 
write at one time.
The minimum value is 1 (one).
The maximum value is 100.
The default value is 100.
The logical endpoint for each branch of the MBTCP hierarchy tree is a 
hardware device (PLC).
Note  The default name created from adding a hierarchy object is in the format 
of New_ObjectName_###, where ObjectName is the name of the object type 
and ### is a numeric value starting from "000" enumerated sequentially per 
hierarchy object. The hierarchy object name is up to 32 characters long. The 
link name for the OPC items is constructed by assembling the respective object 
names of the nodes along the hierarchy tree in the logical order, starting from 
this DAServer’s TCPIP_PORT root down to the leaf. Therefore, the link name 
is always unique for the DAServer.
Note  In order to use the DAServer, you must activate it. See the DAServer 
Manager documentation for information about how to activate and deactivate 
the DAServer.
String-Data Handling
The MBTCP DAServer can process three different configurable string variable 
styles:
• 
Full Length
• 
C Style
• 
Pascal
Depending on what string style the PLC is using, you can configure the server 
using the user interface in the PLC configuration view in order to use the 
appropriate string variable style.
Full Length Sytle
If strings are read using the Full Length Style, each string always uses all of the 
registers allocated. The PLC string is stored in the server string as is.
If a string is written and the string is shorter than the allocation of registers, it is 
padded with ASCII space characters (hex 20).
For example:
58
Chapter 2
MBTCP DAServer User’s Guide
If the string "Wonderware" is stored in the string item "400001-400010 m," 
registers 400001 through 400005 contain the string "Wonderware" and 
registers 400006 through 400010 contain spaces.
If the string "Wonderware" is stored in the string item "400001-400005 m," 
registers 400001 through 400005 contain the string "Wonderware" and no 
spaces are stored.
If the string "Wonderwareee" is stored in the string item "400001-400005 m," 
registers 400001 through 400005 contain the string "Wonderware" and no 
spaces are stored.
A message is placed in the logger indicating that the string was truncated.
C Style
If a string is read using the C Style, the string always uses all of the registers 
allocated. The PLC string is stored in the server string as is, except that the last 
character contained in the last register of the string is replaced with a null 
character (hex 00).
If a string is written and the string is shorter than the allocation of registers, it is 
padded with ASCII null characters (hex 00).
For example:
If the string "Wonderware" is stored in the string item "400001-400010 m," 
registers 400001 through 400005 contain the string "Wonderware" and 
registers 400006 through 400010 contain nulls.
If the string "Wonderware" is stored in the string item "400001-400005 m," 
registers 400001 through 400005 contain the truncated string "Wonderwar0" 
with a null character replacing the last character "e."
A message is placed in the logger indicating that the string was truncated.
Pascal Style
If strings are read using the Pascal Style, each string uses a length obtained 
from the first byte of the string to store data in the server. The PLC string is 
stored in the server string as is, up to the length obtained from the first byte of 
the string. If the length is greater than the number of registers defined in the 
item, then the PLC string is stored in the server string as is, up to the maximum 
number of registers.
The first byte written of any string of this style contains the character count. 
The string being written starts in the second byte. If a string is written and the 
string plus the character count are shorter than the allocation of registers, it is 
padded with ASCII null characters (hex 00).
For example:
If the string "Wonderware" is stored in the string item "400001-400010 m," 
registers 400001 through 400006 contain the string "(10)Wonderware0" and 
registers 400007 through 400010 contain nulls. The (10) in the string implies 
one byte containing the character count.
If the string "Wonderware" is stored in the string item "400001-400005 m," 
registers 400001 through 400005 contain the truncated string "(9)Wonderwar."
A message is placed in the logger indicating that the string was truncated.
Configuration
59
MBTCP DAServer User’s Guide
Message Optimization
The MBTCP DAServer uses Multi read and write commands to optimize PLC 
read/write messages. The MBTCP DAServer optimizes the reading and 
writing of data by grouping points that are in consecutive registers. The Block 
I/O sizes parameters control the buffer size. The default is to maximize the 
buffer size.
Note  The number of bytes for the query and response buffers must not exceed 
the Modbus maximum buffer size of 256 bytes.
Configuring Device Group and Device Item 
Definitions
The Device Groups tab in the DAServer Manager user interface is used to 
create new, modify, or delete device group definitions for an object. For 
DDE/SuiteLink communications, one or more device group definitions must 
exist for each PLC that the DAServer will communicate with.
Each device group (topic) definition should contain a unique name for the PLC 
associated with it.
Device Group Definitions
The Device Groups dialog box, which is displayed by clicking the Device 
Groups tab in the New_<Name>PLC_000 Parameters configuration view, is 
used to perform the following activities:
• 
Adding, defining, and deleting device groups.
Note  When you add a new device group, enter a unique name.
• 
Configuring the DAServer to receive unsolicited messages.
• 
Configuring default update intervals.
• 
Editing update intervals for the device groups.
Note  When you select another part of the DAServer tree hierarchy, you are 
prompted to save the modifications to the configuration set.
To create or add device groups
1. Right-click in the Device Groups dialog box.
2. Select the Add command from the shortcut menu.
60
Chapter 2
MBTCP DAServer User’s Guide
When you add a new device group, enter a unique name (up to 32 
characters long).
To make changes on device groups’ names
Change a device group’s name for an object as follows:
• 
In the Name column, double-click on the device group’s name to be 
modified and make the change.
To delete device groups
Deleting a device group from the list can be performed as follows: 
1. Right-click on the device group to be deleted.
2. Select the Delete command from the shortcut menu.
Note  When you select another part of the MBTCP DAServer tree hierarchy, 
you are prompted to save the modifications to the configuration set.
To configure the MBTCP DAServer to receive unsolicited 
messages
This option is available only to the PLC nodes that are directly connected to 
the TCPIP_Port node. PLC nodes that are connected underneath the 
ModbusBridge node do not have this capability.
Note  Some PLCs, for example the TSX Premium PLC, can send Holding 
Register and Coil unsolicited data to the MBTCP DASever, while other PLCs, 
for example the TSX Quantum PLC, can send the Holding Register unsolicited 
data only to the DAServer.
1. Click on the PLC’s name in the PLC branch of the DAServer hierarchy.
2. Select the Device Group tab of the configuration view pane at right.