adobe pdf viewer c# : Add pdf files together reader application Library utility azure .net html visual studio m07590333_00000000_1en15-part731

5 - Editors in CoDeSys 
CoDeSys V2.3 
5-13 
... 
FUNCTION_BLOCK afB 
VAR 
b : bfb {flag nowrite}; 
c : INT; 
END_VAR 
... 
FUNCTION_BLOCK bfB 
VAR 
d : INT {flag noread}; 
e : INT {flag nowrite}; 
END_VAR 
„a.b.d": Will not be exported 
„a.b.e": Will be exported only with read permission 
„a.c": Will be exported with read and write permission. 
Pragma {bitaccess...} for the Bitaccess 
This pragma can be used to get a correct display of a variable, which is doing a bitaccess with 
the help of a global constant, in the input assistant, in the "Intellisense function" and at 
monitoring in the declaration window. Further on it will effect that, when this variable is 
monitored in the declaration window of the particular POU, the used global constants are shown 
below the respective structure variable. 
Please regard: The project option 'Replace constants' (category Build) must be activated ! 
The pragma must be inserted in the declaration of the structure in a separate line. The line is 
not terminated by a semicolon. 
Syntax:
{bitaccess <Global Constant> <Bitnumber> '<comment>'} 
<Global Constant>: Name of the global constant, which must be defined in a global variables 
list. 
<Bitnumber>: Value of the global constant, as defined in the global variables list.  
See for an example in Chapter Appendix B: Operands in CoDeSys, Addressing bits in 
variables. 
Pragma {link} for linking a POU during code generation 
Normally a POU (program, function, function block) or a data unit type definition (DUT) which is 
not called within the project, will not be linked during code generation. But it might be desired 
that a function, e.g. included in the project via a library, should be available after download on 
the runtime system  even if it is not used by the application program directly (e.g. for any check 
operations). For this purpose you can add the {link} pragma at any desired position in the 
declaration part of a POU or in a DUT in order to force a linking of the POU anyway. 
Pragma for Controlling the Display of Library Declaration Parts 
During creation of a library in CoDeSys you can define via pragmas which parts of the declaration 
window should be visible resp. not visible in the Library Manager later when the library will be included 
in a project. The display of the implementation part of the library will not be affected by that.  
Thus comments or any variables declarations can be concealed from the user. The pragmas {library 
private} and {library public} each affect the rest of the same line resp. the subsequent lines, as long as 
they are not overwritten by the each other one. 
Syntax{library public}  The subsequent test will be displayed in the Library Manager. 
{library private} :The subsequent test will be not displayed. 
Add pdf files together reader - Merge, append PDF files in C#.net, ASP.NET, MVC, Ajax, WinForms, WPF
Provide C# Demo Codes for Merging and Appending PDF Document
best pdf merger; c# merge pdf
Add pdf files together reader - VB.NET PDF File Merge Library: Merge, append PDF files in vb.net, ASP.NET, MVC, Ajax, WinForms, WPF
VB.NET Guide and Sample Codes to Merge PDF Documents in .NET Project
break a pdf into multiple files; add pdf together
Declaration Editor 
5-14 
CoDeSys V2.3 
Example: See below the declaration part of a library, which is created in CoDeSys. The comment 
"(* this is for all *)" should be displayed in the Library Manager after having included the library in a 
project., the comment "(* but this is not for all ")" however should not be displayed. The variables 
local and in2 also should not be displayed: 
{library public} 
FUNCTION afun : BOOL 
VAR_INPUT 
in: BOOL; 
END_VAR 
{library private} 
VAR 
local: BOOL; 
END_VAR 
{library public} 
VAR_INPUT 
in2: BOOL; 
{library private} 
in3: BOOL; 
{library public} 
END_VAR 
Pragma instructions for Parameter Manager entries 
Pragma instructions can be inserted in variable declarations in order to create entries for these 
variables in parameter lists which are handled in the Parameter Manager. It depends on the target 
system, whether the Parameter Manager is available in the CoDeSys programming system. This 
means it must be activated in the target settings, category Networkfunctionality. 
The syntax:
The pragma instruction is enclosed in curly brackets, upper- and lower-case are ignored: { <Instruction 
text> }. If it is included in "normal" variable declarations, it must be set before the terminating 
semicolon of the declaration.  
Pragmas, which are used in the VAR_CONFIG interface, are set each in a single line and are not 
terminated with a semicolon ! 
The key definitions are written separated by space characters, all together enclosed in square 
brackets. 
<name>: Name of the parameter list in the Parameter Manager. If the list does not yet exist, it will be 
created. 
<key>: Name of the attribute, i.e. column title in the parameter list; e.g. "Name", "Value", "Accesslevel" 
etc.;  It depends on the definition of the customer specific parameter list type, which keys can be 
defined in the pragma. The key definitions are written separated by space characters, all together 
enclosed in square brackets. Regard the syntax for entries in instance lists for arrays, structure 
resp. function block components.(see below, 3.). 
<value>: Value of the attribute which is defined by <key>. If <value> contains empty spaces it must be 
enclosed in double quotation marks, e.g. ...accessright="read only"... 
Please note: The pragma instructions will be effective as soon as the focus is changed, that means as soon as a 
precompile is done e.g. via leaving the editor window. Erroneous inputs will not be messaged until 
the project is compiled. 
The following entries can be generated: 
1. Entries in parameter lists of type 'Variables'
(a) from the declaration part of programs and global variables lists:
C# Word - Merge Word Documents in C#.NET
empowers C# programmers to easily merge and append Word files with mature input Word documents can be merged and appended together according to Add references:
c# merge pdf files; combine pdfs online
C# PowerPoint - Merge PowerPoint Documents in C#.NET
together according to its loading sequence, and then saved and output as a single PowerPoint with user-defined location. C# DLLs: Merge PowerPoint Files. Add
adding pdf pages together; reader merge pdf
5 - Editors in CoDeSys 
CoDeSys V2.3 
5-15 
For a variable defined in a PROGRAM- or VAR_GLOBAL declaration an entry in a parameter list of 
type 'Variables' can be created, if it is declared like described in the following: (If the parameter list 
does not yet exist, it will be created automatically) 
Syntax: {parameter list=<name> [ <key>=<value> <key>=<value>  ...further keys  ] }    
Example: Variable bvar is declared in a program. It should be entered in the parameter list parlist1 
type 'Variables') with symbolic name bvar1, value 102, index 16#1200 and subindex 16#2l.  
VAR
bvar:INT{parameter list=parlist1 [name=bvar1 value=102 index=16#1200 
subindex=16#1 ] };
END_VAR
(b) via a declaration in the VAR_CONFIG Interface:
There is the possibility to create an entry for a variable in a parameter list of type 'Variables' by 
placing a pragma in a VAR_CONFIG window (independent of variable configurations, which also 
are done in the VAR_CONFIG interface):  (If the parameter list does not yet exist, it will be created 
automatically) 
Syntax{parameter list=<name> path=<path> [ <key>=<value> <key>=<value>  ...further keys  ] } 
<path> Path of the variable, for which the entry should be generated, e.g. "PLC_PRG.act1.var_x" 
Example: For variable var_x an entry is created in parameter list "varlist1", symbolic name is 
xvar". 
VAR_CONFIG
{parameter list=varlist1 path=PLC_PRG.act1.var_x [ name=xvar ] }
END_VAR 
2. Entries in parameter lists of type 'Template' via function blocks and structures
Pragmas in  variable declarations in function blocks and structures can be used to create entries in 
parameter lists of type 'Template'. (If the template does not yet exist, it will be created 
automatically.) 
Syntax {template list=<name> [ <key>=<value> <key>=<value>  ...further keys  ] } 
Example: Variable strvar, which is an element of structure "stru1", should be entered in a 
parameter list "templ1" of type 'Template'; symbolic name (member) of the entry is "struvar1, the 
access level is "low" : 
TYPE stru :
STRUCT 
ivar:INT; 
strvar:STRING{template list=vorl1 [member=struvar1 accesslevel=low] };
END_STRUCT
END_TYPE
3. Entries in parameter lists of type 'Instance' (
for arrays, function block- or structure variables) 
(a) via declarations in programs or global variable lists
At the declaration of arrays, function block- or structure variables in a program or in a global 
variables list directly an parameter list of type 'Instance' can be created:  
Syntax
{instance 
list=<name> 
template=<template> 
baseindex=<index> 
basesubindex=<subindex> [ <key>=<value for first element > <key>=<value for first element >  
...further keys for first element  ] | [ <key>=<value for second element > <key>=<value for 
second element >  ..further keys for second element  ] | [keys for further 
elements]}<key>=<value> <key>=<value>  ...further keys  ]  } 
C# PDF Convert to Text SDK: Convert PDF to txt files in C#.net
can be copied and pasted to .txt files by keeping text by a method loses the original PDF document layout and all the paragraphs are joining together, our C#
batch merge pdf; reader create pdf multiple files
VB.NET Word: How to Process MS Word in VB.NET Library in .NET
Imaging.MSWordDocx.dll", which, when used together with other online tutorial on how to add & insert controls, PDF document, image to pdf files and components
add pdf pages together; combine pdf
Declaration Editor 
5-16 
CoDeSys V2.3 
For arrays the key "template" will automatically be defined with the implicitly available template 
"ARRAY", for structures and function blocks an appropriate template must be available in the 
Parameter Manager and must be part of the here described declaration. 
For each particular array- resp. structure or function block element an individual entry can be pre-
defined in the parameter list: For example per each element an own definition 
[name=<elementname>] can be specified.  
The key definitions of each particular element  (all keys of a particular element are enclosed by the 
same square brackets!) re to be arranged in a row, separated by empty spaces. The definition 
packages for the elements will automatically refer to the elements according to the ascending order 
of the index (Member). If there are not as many key-definitions available as there are elements in 
the array resp. the structure or the function block, then the remaining elements will get assigned 
the same values as the last individually defined element (Exception for key "name" for arrays, see 
below)! (see example 1b). 
Automatisms concerning key "name" when entering arrays in parameter lists:  
- If you do not specify a name for an array element in the pragma, that element and all 
following elements automatically will get the names <POU name>_<Array variable 
name>_<corresponding array index number>.   
Example: Array variable ARRVAR [1..8] of INT in POU PLC_PRG is to be entered in a 
variable list via a pragma; If key "name" is not defined in the pragma, the particular array 
elements in the parameter list automatically will be named "PLC_PRG_arrvar_1" to 
"PLC_PRG_arrvar_8". 
- If you define any name "<name>_<first index number of array range>" for the first array 
element via the pragma, the following array elements in the parameter list automatically will 
be named “<name>_<corresponding index number>”.   
Example: Array variable ARRVAR [1..8] of INT in is to be entered in a variable list via a 
pragma; The pragma just specifies [name=xyz_1]“ for the first array element and thus in 
the parameter list the following elements automatically will get the names "xyz_2" to  
"xyz_8". 
Attention: Do not define a value for the key "Member"; this column will be filled automatically by using the 
array index values. 
Examples:  
Example1a:
An array variable arr_1 is declared as described in the following in order to create a 
parameter list arrinst of type 'Instance' (if not yet available), in which the array components get 
entered, whereby each element first will get a symbolic name xname_<index number> (could  
be edited afterwards in the parameter manager) and the subindex will be counted up by 1 for 
each entry, starting with 0 (basesubindex). Accesslevel=low will be applied to all elements. 
basesubindex=16#0 [name=xname_1 accesslevel=low] } 
Example1b:
For an array variable arr_1 just for the elements 1 to 4 already names are defined 
via the pragma, the elements 5 to 8 therefore automatically will get the name of element 4 
extended by a Underline and the appropriate index number, i.e. "xname_5" to " xname_8". 
Regard that further key-definitions for a particular element must be entered within the same 
square brackets as shown here for the first and for the fourth element regarding the 
accesslevel: 
arr_1: ARRAY [1..8] OF INT{instance list=arrinst template=ARRAY baseindex=16#0 
basesubindex=16#0[name=aname 
accesslevel=high] 
[name=bname] 
[name=cname] 
[name=xname accesslevel=medium]}; 
C# TIFF: TIFF Editor SDK to Read & Manipulate TIFF File Using C#.
Support converting other files to Tiff, like Word, Excel, PowerPoint, PDF, and images. Enable to add XImage.OCR for .NET into C# Tiff imaging application
build pdf from multiple files; append pdf files reader
C# Excel - Merge Excel Documents in C#.NET
and appended together according to its loading sequence, and then saved and output as a single Excel with user-defined location. C# DLLs: Merge Excel Files. Add
pdf mail merge plug in; c# combine pdf
5 - Editors in CoDeSys 
CoDeSys V2.3 
5-17 
Parameter Manager Editor,  Example1a  
Parameter Manager Editor,  Example1b 
Example2:
A structure variable of type "stru1" (contains variables a,b,c)  is declared as described in the 
following in order to get entries in a parameter list of type 'Instance' which is basing on the 
template "strulist_temp"; the list will get entries for the components a,b,c, no symbolic names 
are assigned, the access level is set to "high" and each index value defined by the template will 
be increased by 2. Make sure that the template defined in the pragma is available in the 
Parameter Manager: 
struvar:stru1{instance list=strulist template=strulist_templ baseindex=16#2 
basesubindex=16#0 [accesslevel=high] };
C# Image: C# Code to Encode & Decode JBIG2 Images in RasterEdge .
Easy to add C# JBIG2 codec controls to your image and codec into PDF documents for a better PDF compression; text to the new project folder, together with .NET
acrobat merge pdf files; add pdf together one file
VB.NET Image: VB.NET ISSN Barcode Reader & Scanner; Decode Barcode
and recognize ISSN barcode from document files, like PDF from source PDF file, RasterEdge.Imaging.PDF.dll will And all those .NET add-ons can be integrated and
merge pdf; c# merge pdf pages
Declaration Editor 
5-18 
CoDeSys V2.3 
Example2, Entries for structure variable in Template 
(b) via declarations in the VAR_CONFIG interface
For variables which can be instanced, you can directly create entries in an parameter list of type 
'Instance' by a pragma in a VAR_CONFIG window (independent of variable configuration 
definitions which are also done in this interface).  If the template does not yet exist, it will be 
created automatically. 
Make sure that the Template defined in the pragma is already available in the Parameter Manager. 
Syntax{instance list=<name> path=<path>  template=<template> baseindex=<index> 
basesubindex=<subindex>[ <key>=<value> <key>=<value>  ...further keys ] } 
<path>: The instance path of the variable;e.g. "PLC_PRG.fb1inst", whereby fb1inst is an instance 
of function block fb1. 
Example: The following entry in a VAR_CONFIG window will create entries for all variables of 
function block "fb1" in an instance list "varinst1" basing on the template "fb1_templ" (which must be 
already available). For each entry the index offset, which is predefined by the template, will be 
increased by 2 (baseindex), the subindex offset will not be modified (basesubindex). Each entry 
gets a symbolic name "fb1var", which you can edit afterwards in the Parameter Manager. 
VAR_CONFIG 
basesubindex=16#0 [ name=fb1var ]}
END_VAR 
Pragma for nonpersistent data types 
Normally the following is valid: Even if only one local variable in a function block or a structure is 
declared persistent, at usage of an instance automatically all components will be stored in the 
persistent information (persist.dat) on the runtime system. In order to save space you can use the 
pragma 
5 - Editors in CoDeSys 
CoDeSys V2.3 
5-19 
{nonpersistent} 
in the declaration of the function block resp. the structure. It effects that only those components of the 
function block resp. structure, which are declared as "persistent", will be entered to the persistent info. 
Example:  
If an instance of the following function block is declared as persistent, only  the variables local and fblevel3 will 
be written to the persistent info. Without pragma {nonpersistent} all function block variables would be stored 
there. 
FUNCTION_BLOCK FB_Level_2 
{nonpersistent} 
VAR_INPUT 
bvar_in : BOOL; 
END_VAR 
VAR_OUTPUT 
bvar_out : BOOL; 
END_VAR 
VAR 
ivar2 : INT; 
END_VAR 
VAR PERSISTENT 
local : INT := 33; 
fblevel3 : FB_Level_3; 
END_VAR 
Declaration Editor 
5-20 
CoDeSys V2.3 
5 - Editors in CoDeSys 
CoDeSys V2.3 
5-21 
5.3 The Text Editors 
5.3.1 Working in text editors 
Text editors used for the implementation portion (the Instruction List editor and the Structured Text 
editor) of CoDeSys provide the usual Windows text editor functions. 
The implementation in the text editors is supported by syntax coloring. 
In Overwrite mode the status bar shows a black OV. You can switch between Overwrite mode and 
Insert mode by key <Ins> 
The most important commands are found in the context menu (right mouse button or <Ctrl>+<F10>). 
The text editors use the following menu commands in special ways: 
'Insert' 'Operators' in text editors  
With this command all of the operators available in the current language are displayed in a dialog box. 
If one of the operators is selected and the list is closed with OK, then the highlighted operator will be 
inserted at the present cursor position. (This is managed here just as it is in the Input Assistant). 
'Insert' 'Operand' in text editors  
With this command all variables in a dialog box are displayed. You can select whether you would like 
to display a list of the global, the local, or the system variables. 
If one of the operands is chosen, and the dialog box is closed with OK, then the highlighted operand 
will be inserted at the present cursor position. (This is managed here just as it is in the Input 
Assistant). 
'Insert' 'Function' in text editors  
With this command all functions will be displayed in a dialog box. You can choose whether to have a 
list displaying user-defined or standard functions. 
If one of the functions is selected and the dialog box is closed with OK, then the highlighted function 
will be inserted at the current cursor position. (The management will proceed, as in the input 
selection.) 
The Text Editors 
5-22 
CoDeSys V2.3 
If the With arguments option was selected in the dialog box, then the necessary input and output 
variables will also be inserted. 
'Insert' 'Function Block' in text editors  
With this command all function blocks are displayed in a dialog box. You can choose whether to have 
a list displaying user-defined or standard function blocks. 
If one of the function blocks is selected and the dialog box is closed with OK, then the highlighted 
function block will be inserted at the current cursor position. (This is managed here just as it is in the 
Input Assistant). 
If the With arguments option was selected in the dialog box, then the necessary input variables of the 
function block will also be inserted. However you are not forced to assign these parameters. 
Calling POUs with output parameters in text editors 
The output parameters of a called POU can be directly assigned upon being called in the text 
languages IL and ST. 
Example:  
Output parameter out1 of afbinst is assigned variable a. 
IL:  
CAL afbinst(in1:=1, out1=>a)
ST: 
afbinst(in1:=1, out1=>a);
If the POU is inserted via input assistant (<F2>) with option 'With arguments' in the implementation 
window of a ST or IL POU, it will automatically be displayed with all parameters in this syntax. 
However you are not forced to assign these parameters. 
The text editors in Online mode 
The online functions in the editors are set breakpoint and single step processing (steps). Together 
with the monitoring, the user thus has the debugging capability of a modern Windows standard 
language debugger. 
In Online mode, the text editor window is vertically divided in halves. On the left side of the window 
you will then find the normal program text; on the right side you will see a display of the variables 
whose values were changed in the respective lines. The width of the window halves can be modified 
by drawing the divider with the mouse. 
The display is the same as in the declaration part. That means that when the PLC is running, the 
present values of the respective variables will be displayed.  
The following should be noted when monitoring expressions or Bit-addressed variables: in the case of 
expressions, the value of the entire expression is always displayed. Example: a AND b is displayed in 
blue or with „:=TRUE" if both a and b are TRUE. For Bit-addressed variables, the bit value that is 
addressed is always monitored (e.g. a.3 is displayed in blue or with „:=TRUE, if a has the value 4). 
If you place the mouse pointer briefly above a variable, then the type, the address and the comment 
about the variable will be displayed in a Tooltip. 
'Extras' 'Monitoring Options' 
With this command you can configure your monitoring window. In the text editors, the window is 
divided into two halves during monitoring. The program is located in the left half. In the right half, all 
variables that are located in the corresponding program line are monitored.  
You can specify the Monitor Window Width and which Distance two variables should have in a line. 
An distance declaration of 1 corresponds, in this case, to a line height in the selected font. 
Regard that the width of the window halves also can be modified by drawing the divider with the 
mouse. 