adobe pdf viewer c# : Reader combine pdf control SDK platform web page wpf .net web browser m07590333_00000000_1en35-part753

Appendix D:  - The CoDeSys Libaries 
CoDeSys V2.3 
10-51 
Examples in ST: 
FLAG:=EXTRACT(X:=81, N:=4); (* Result : TRUE, because 81 is binary 1010001, so the 
4th bit is 1 *) 
1, so the 
bit '0' is 1 *) 
PACK 
This function is capable of delivering back eight input bits B0, B1, ..., B7 from type BOOL as a BYTE. 
The function block UNPACK is closely related to this function. 
PUTBIT 
The input to this function consists of a DWORD X, a BYTE N and a BOOLean value B. 
PUTBIT sets the N
th
bit from X on the value B, whereby it starts counting from the zero bit. 
Example in ST: 
A:=38;    (* binary 100110 *) 
B:=PUTBIT(A,4,TRUE); (* Result : 54 = 2#110110 *) 
C:=PUTBIT(A,1,FALSE); (* Result : 36 = 2#100100 *) 
UNPACK 
UNPACK converts the input B from type BYTE into 8 output variables B0,...,B7 of the type BOOL, and 
this is the opposite to PACK. 
Example in FBD: Output:  
10.18.3 
Mathematic Auxiliary Functions 
DERIVATIVE 
This function block approximately determines the local derivation. 
The function value is delivered as a REAL variable by using IN. TM contains the time which has 
passed in msec in a DWORD and the input of RESET of the type BOOL allows the function block to 
start anew through the delivery of the value TRUE. 
The output OUT is of the type REAL.  
In order to obtain the best possible result, DERIVATIVE approximates using the last four values, in 
order to hold errors which are produced by inaccuracies in the input parameters as low as possible. 
Reader combine pdf - Merge, append PDF files in C#.net, ASP.NET, MVC, Ajax, WinForms, WPF
Provide C# Demo Codes for Merging and Appending PDF Document
acrobat combine pdf files; combine pdfs online
Reader combine pdf - VB.NET PDF File Merge Library: Merge, append PDF files in vb.net, ASP.NET, MVC, Ajax, WinForms, WPF
VB.NET Guide and Sample Codes to Merge PDF Documents in .NET Project
break a pdf into multiple files; add pdf together one file
Appendix D:  - The CoDeSys Libaries 
10-52 
CoDeSys V2.3 
Block in FBD: 
INTEGRAL 
This function block approximately determines the integral of the function. 
In an analogue fashion to DERIVATIVE, the function value is delivered as a REAL variable by using 
IN. TM contains the time which has passed in msec in a DWORD and the input of RESET of the type 
BOOL allows the function block to start anew with the value TRUE. 
The output OUT is of the type REAL.  
The integral is approximated by two step functions. The average of these is delivered as the 
approximated integral. 
Block in FBD:  Example: Integration of a linear function: 
LIN_TRAFO 
This function block (util.lib. transforms a REAL-value, which lies in a value range defined by a lower 
and upper limit value, to a corresponding REAL-value which lies in another range also defined by a 
lower and upper limit. The following equation is basis of the conversion: 
(IN - IN_MIN) : (IN_MAX - IN) = (OUT - OUT_MIN) : (OUT_MAX - OUT) 
Input variables:  
Variable 
Data type 
Description 
IN 
REAL 
Input value 
IN_MIN 
REAL 
Lower limit of  input value range 
IN_MAX 
REAL 
Upper limit of  input value range 
OUT_MIN 
REAL 
Lower limit of  output value range 
OUT_MAX REAL 
Upper limit of  output value range 
C# PDF: C#.NET PDF Document Merging & Splitting Control SDK
PDF Merging & Splitting Application. This C#.NET PDF document merger & splitter control toolkit is designed to help .NET developers combine PDF document files
scan multiple pages into one pdf; .net merge pdf files
VB.NET PDF: Use VB.NET Code to Merge and Split PDF Documents
Combine End Sub Private Sub Combine(source As List(Of [String]), destn As [String]) Implements PDFDocument.Combine End Sub. APIs for Splitting PDF document in
acrobat split pdf into multiple files; combine pdfs online
Appendix D:  - The CoDeSys Libaries 
CoDeSys V2.3 
10-53 
Output variables: 
Variable 
Data type 
Description 
OUT 
REAL 
Output value 
ERROR BOOL 
Error occurred: TRUE, if IN_MIN = IN_MAX, or if IN is outside of the 
specified input value range 
Application example: 
A temperature sensor provides Volt-values (input IN). These are to be converted to temperature 
values in degree centigrade (output OUT). The input(Volt) values range is defined by the limits 
IN_MIN=0 and IN_MAX=10. The output(degree centigrade) value range is defined by the limits 
OUT_MIN=-20 and OUT_MAX=40. 
Thus for an input of 5 Volt a temperature of 10 degree centigrade will result. 
STATISTICS_INT 
This function block calculates some standard statistical values: 
The input IN is of the type INT. All values are initialised anew when the BOOLean input RESET is 
TRUE. 
The output MN contains the minimum, MX of the maximum value from IN. AVG describes the 
average, that is the expected value of IN. All three outputs are of the type INT. 
Block in FBD: 
STATISTICS_REAL 
This function block corresponds to STATISTICS_INT, except that the input IN is of the type REAL like 
the outputs MN, MX, AVG. 
VARIANCE 
VARIANCE calculates the variance of the entered values.  
The input IN is of the type REAL, RESET is of the type BOOL and the output OUT is again of the type 
REAL. 
This block calculates the variance of the inputted values. VARIANCE can be reset with 
RESET=TRUE. 
The standard deviation can easily be calculated as the square root of the VARIANCE. 
VB.NET Image: Barcode Reader SDK, Read Intelligent Mail from Image
How to combine PDF Document Processing DLL with Barcode As String = FolderName & "Sample.pdf" Dim reImage own customized Word Intelligent Mail Barcode Reader.
combine pdf files; add pdf pages together
C# PowerPoint - Merge PowerPoint Documents in C#.NET
Combine and Merge Multiple PowerPoint Files into One Using C#. This part illustrates how to combine three PowerPoint files into a new file in C# application.
break pdf into multiple files; pdf combine files online
Appendix D:  - The CoDeSys Libaries 
10-54 
CoDeSys V2.3 
10.18.4 
Controllers 
PD 
The library util.lib provides the following PD controller function block: 
Inputs of the function block: 
Variable 
Data type 
Description 
ACTUAL 
REAL 
Current value of the controlled variable 
SET_POINT 
REAL 
Desired value, command variable 
KP 
REAL 
Proportionality coefficient, unity gain of the P-part 
TV 
REAL 
Derivative action time, unity gain of the D-part  in seconds, e.g. 
"0.5" for 500 msec 
Y_MANUAL 
REAL 
Defines output value Y in case of MANUAL = TRUE 
Y_OFFSET 
REAL 
Offset for the manipulated variable Y 
Y_MIN, 
Y_MAX 
REAL 
Lower resp. upper limit for the manipulated variable Y. If Y 
exceeds these limits, output LIMITS_ACTIVE will be set to 
TRUE and Y will be kept within the prescribed range. This 
control will only work if Y_MIN<Y_MAX. 
MANUAL 
BOOL 
If TRUE, manual operation will be active, i.e. the manipulated 
value will be defined by Y_MANUAL. 
RESET 
BOOL 
TRUE resets the controller; during reinitialization Y = 
Y_OFFSET. 
Outputs of the function block: 
Variable 
Data type 
Description 
REAL 
Manipulated value, calculated by the function block (see 
below) 
LIMITS_ACTIVE 
BOOL 
TRUE indicates that Y has exceeded the given limits (Y_MIN, 
Y_MAX). 
Y_OFFSET, Y_MIN und Y_MAX are used for the transformation of the manipulated variable within a 
prescribed range. 
MANUAL can be used to switch on and off manual operation. RESET serves to reset the controller. 
C# Word - Merge Word Documents in C#.NET
Combine and Merge Multiple Word Files into One Using C#. This part illustrates how to combine three Word files into a new file in C# application.
merge pdf; pdf merger
C# PDF File Split Library: Split, seperate PDF into multiple files
Split PDF document by PDF bookmark and outlines. Also able to combine generated split PDF document files with other PDF files to form a new PDF file.
batch pdf merger; reader combine pdf pages
Appendix D:  - The CoDeSys Libaries 
CoDeSys V2.3 
10-55 
In normal operation (MANUAL = RESET = LIMITS_ACTIVE = FALSE) the controller calculates the 
controller error e
as difference SET_POINT – ACTUAL, generates the derivation with respect to time 
e/ t and stores these values internally. 
The output, i.e. the 
manipulated variable Y
is calculated as follows: 
Y = KP  ( + TV /t) + Y_OFFSET whereby =SET_POINT-ACTUAL 
So besides the P-part also the current change of the controller error (D-part) influences the 
manipulated variable. 
Additionally Y is limited on a range prescribed by Y_MIN and Y_MAX. If Y exceeds these limits, 
LIMITS_ACTIVE will get TRUE. If no limitation of the manipulated variable is desired, Y_MIN and 
Y_MAX have to be set to 0. 
As long as MANUAL=TRUE,  Y_MANUAL will be written to Y. 
 P-controller can be easily created by setting TV=0. 
PID 
The library util.lib provides the following PID controller function block: 
Unlike the PD controller, this function block contains a further REAL input TN for the readjusting time 
in sec (e.g. "0.5" for 500 msec).  
Inputs of the function block: 
Variable 
Data 
type 
Description 
ACTUAL 
REAL 
Current value of the controlled variable 
SET_POINT 
REAL 
Desired value, command variable 
KP 
REAL 
Proportionality coefficient, unity gain of the P-part 
TN 
REAL 
Reset time, reciprocal unity gain of the I-part;  
given in seconds, e.g. "0.5" for 500 msec 
TV 
REAL 
Derivative action time, unity gain of the D-part  in seconds, e.g. 
"0.5" for 500 msec 
Y_MANUAL 
REAL 
Defines output value Y in case of MANUAL = TRUE 
Y_OFFSET 
REAL 
Offset for the manipulated variable Y 
Y_MIN, Y_MAX 
REAL 
Lower resp. upper limit for the manipulated variable Y. If Y 
exceeds these limits, output LIMITS_ACTIVE will be set to TRUE 
and Y will be kept within the prescribed range. This control will 
only work if Y_MIN<Y_MAX. 
MANUAL 
BOOL 
If TRUE, manual operation will be active, i.e. the manipulated 
VB.NET TIFF: Merge and Split TIFF Documents with RasterEdge .NET
filePath As [String], docList As [String]()) TIFFDocument.Combine(filePath, docList) End to provide powerful & profession imaging controls, PDF document, tiff
how to combine pdf files; pdf combine
VB.NET PowerPoint: Merge and Split PowerPoint Document(s) with PPT
Just like we need to combine PPT files, sometimes, we also want to separate a Note: If you want to see more PDF processing functions in VB.NET, please follow
pdf merge files; pdf split and merge
Appendix D:  - The CoDeSys Libaries 
10-56 
CoDeSys V2.3 
value will be defined by Y_MANUAL. 
RESET 
BOOL 
TRUE resets the controller; during reinitialization Y = Y_OFFSET. 
Outputs of the function block: 
Variable 
Data type 
Description 
REAL 
Manipulated value, calculated by the function block (see below) 
LIMITS_ACTIVE 
BOOL 
TRUE indicates that Y has exceeded the given limits (Y_MIN, 
Y_MAX). 
OVERFLOW 
BOOL 
TRUE indicates an overflow (see below) 
Y_OFFSET, Y_MIN und Y_MAX serve for transformation of the manipulated variable within a 
prescribed range. 
MANUAL can be used to switch to manual operation; RESET can be used to re-initialize the 
controller.. 
In normal operation (MANUAL = RESET = LIMITS_ACTIVE = FALSE) the controller calculates the 
controller error e
as difference from SET_POINT – ACTUAL, generates the derivation with respect to 
time  e/t and stores these values internally. 
The output, i.e. the manipulated variable Y unlike the PD controller contains an additional integral part 
and is calculated as follows:  
Y = KP  ( + 1/TN  edt + TV /t) + Y_OFFSET  
So besides the 
P-part
also the current change of the controller error (
D-part
) and the history of the 
controller error (
I-part
) influence the manipulated variable. 
The PID controller can be easily converted to a 
PI-controller
by setting TV=0. 
Because of the additional integral part, an 
overflow
can come about by incorrect parameterization of 
the controller, if the integral of the error  becomes to great. Therefore for the sake of safety a 
BOOLean output called OVERFLOW is present, which in this case would have the value TRUE. This 
only will happen if the control system is instable due to incorrect parameterization. At the same time, 
the controller will be suspended and will only be activated again by re-initialization.  
PID_FIXCYCLE 
The library util.lib provides the following PID_FIXCYCLE controller function block: 
This function block functionally corresponds to the PID controller with the exception that the cycle time 
is not measured automatically by an internal function but is set by input CYCLE (in seconds). 
Appendix D:  - The CoDeSys Libaries 
CoDeSys V2.3 
10-57 
10.18.5 
Signal Generators... 
BLINK 
The function block BLINK generates a pulsating signal. The input consists of ENABLE of the type 
BOOL, as well as TIMELOW and TIMEHIGH of the type TIME. The output OUT is of the type BOOL. 
If ENABLE is set to TRUE, BLINK begins, to set the output for the time period TIMEHIGH to TRUE, 
and then afterwards to set it for the time period TIMELOW to FALSE.  
When ENABLE is reset to FALSE, output OUT will not be changed, i.e. no further pulse will be 
generated. If you explicitly also want to get OUT FALSE when ENABLE is reset to FALSE, you might 
use "OUT AND ENABLE" (i.e. adding an AND box with parameter ENABLE) at the output.  
Example in CFC: 
FREQ_MEASURE 
This function block measures the (average) frequency (Hz) of a boolean input signal. You can specify 
over how many periods it should be averaged. A period is the time between two rising edges of the 
input signal. 
Input variables: 
Variable 
Data type 
Description 
IN 
BOOL 
Input signal 
PERIODS 
INT 
Number of periods, i.e. the time intervals between the rising edges, 
over which the average frequency of the input signal should be 
calculated. Possible values: 1 to 10 
RESET 
BOOL 
Reset of all parameters to 0 
Output variables: 
Variable 
Data type 
Description 
OUT 
REAL 
resulting frequency in [Hz] 
VALID 
BOOL 
FALSE until the first measure has been finished, or if the period > 
3*OUT (indicating something wrong with the inputs) 
GEN 
The function generator generates typical periodic functions: 
The inputs are a composition consisting of MODE from the pre-defined counting type GEN_MODE, 
BASE of the type BOOL, PERIOD of the type TIME, of two INT values CYCLES and AMPLITUDE and 
of the BOOLean RESET input.  
The MODE describes the function which should be generated, whereby the enumeration values 
TRIANGLE and TRIANGLE_POS deliver two triangular functions, SAWTOOTH_RISE an ascending, 
Appendix D:  - The CoDeSys Libaries 
10-58 
CoDeSys V2.3 
SAWTOOTH_FALL a descending sawtooth, RECTANGLE a rectangular signal and SINE and 
COSINE the sine and cosine: 
TRIANGLE: 
TRIANGLE_POS: 
SAWTOOTH_RISE: 
SAWTOOTH_FALL: 
RECTANGLE: 
SINUS: 
COSINUS: 
BASE defines whether the cycle period is really related to a defined time (BASE=TRUE) or whether it 
is related to a particular number of cycles, which means the number of calls of function block 
(BASE=FALSE). 
PERIOD or CYCLES defines the corresponding cycle period. 
AMPLITUDE defines, in a trivial way, the amplitude of the function to be generated. 
The function generator is again set to 0 as soon as RESET=TRUE. 
Example in FBD:  
Appendix D:  - The CoDeSys Libaries 
CoDeSys V2.3 
10-59 
10.18.6 
Function Manipulators... 
CHARCURVE 
This function block serves to represent values, piece by piece, on a linear function: 
IN of the type INT is fed with the value to be manipulated. The BYTE N designates the number of 
points which defines the presentation function. This characteristic line is then generated in an ARRAY 
P[0..10] with P of the type POINT which is a structure based on two INT values (X and Y). 
The output consists of OUT of the type INT, the manipulated value and BYTE ERR, which will indicate 
an error if necessary. 
The points P[0]..P[N-1] in the ARRAY must be sorted according to their X values, otherwise ERR 
receives the value 1. If the input IN is not between P[0].X and P[N-1].X, ERR=2 and OUT contains the 
corresponding limiting value P[0]. Y or P[N-1].Y. 
If N lies outside of the allowed values which are between 2 and 11, then ERR=4. 
Example in ST: 
First of all ARRAY P must be defined in the header: 
VAR 
... 
CHARACTERISTIC_LINE:CHARCURVE; 
KL:ARRAY[0..10] OF POINT:=(X:=0,Y:=0),(X:=250,Y:=50), 
(X:=500,Y:=150),(X:=750,Y:=400),7((X:=1000,Y:=1000)); 
COUNTER:INT; 
...  
END_VAR 
Then we supply CHARCURVE with for example a constantly increasing value: 
COUNTER:=COUNTER+10; 
CHARACTERISTIC_LINE(IN:=COUNTER,N:=5,P:=KL); 
The subsequent tracing illustrates the effect: 
RAMP_INT 
RAMP_INT serves to limit the ascendance or descendance of the function being fed: 
The input consists on the one hand out of three INT values: IN, the function input, and ASCEND and 
DESCEND, the maximum increase or decrease for a given time interval, which is defined by 
TIMEBASE of the type TIME. Setting RESET to TRUE causes RAMP_INT to be initialised anew. 
The output OUT of the type INT contains the ascend and descend limited function value. 
When TIMEBASE is set to t#0s, ASCEND and DESCEND are not related to the time interval, but 
remain the same. 
Appendix D:  - The CoDeSys Libaries 
10-60 
CoDeSys V2.3 
Example in CFC: 
RAMP_REAL 
RAMP_REAL functions in the same way as RAMP_INT, with the simple difference that the inputs IN, 
ASCEND, DESCEND and the output OUT are of the type REAL. 
10.18.7 
Analog Value Processing... 
HYSTERESIS 
The input to this function block consists of three INT values IN, HIGH and LOW. The output OUT is of 
the type BOOL. 
If IN goes below the limiting value LOW, OUT becomes TRUE. If IN goes over the upper limit HIGH, 
FALSE is delivered. 
An illustrative example:  
Documents you may be interested
Documents you may be interested