adobe pdf viewer c# : C# merge pdf files into one application control utility azure html winforms visual studio m07590333_00000000_1en44-part763

Appendix K:  - Compiler Errors and Warnings 
CoDeSys V2.3 
10-141 
4360 
"Time Constant expected after qualifier '<name>'" 
Enter next to the box on the left hand of the action name a time constant behind the qualifier. 
4361 
"'<name>' is not the name of an action" 
Enter next to the box on the right hand of the qualifier the name of an action or the name of a variable 
which is defined in the project. 
4362 
"Nonboolean expression used in action: '<name>'" 
Insert a boolean variable or a valid action name. 
4363 
"IEC-Step name already used for variable: '<Name>'" 
Please rename the step or the variable. 
4364 
"A transition must be a boolean expression" 
The result of the transition expression must be of type BOOL. 
4365 
"Time Constant expected after qualifier '<name>'" 
Open dialog ‚step attributes’ for the step '<Name>' and enter a valid time variable or time constant. 
4366 
"The label of the parallel branch is no valid identifier: '<Name>'" 
Enter a valid identifier next to the triangle which marks the jump label. 
4367 
"The label '<name>' is already used" 
There is already a jump label or a step with this name. Please rename correspondingly. 
4368 
"Action '<name>' is used in multiple step chains, where one is containing the other!" 
The action '<Name>' is used in the POU as well as in one or several actions of the POU. 
4369 
"Exactly one network requried for a transition" 
There are used several FBD resp. LD networks for a transition. Please reduce to 1 network. 
4370 
"Additional lines found after correct IL-transition" 
Remove the not needed lines at the end of the transition. 
4371 
"Invalid characters following valid expression: '<name>" 
Remove the not needed characters at the end of the transition. 
C# merge pdf files into one - Merge, append PDF files in C#.net, ASP.NET, MVC, Ajax, WinForms, WPF
Provide C# Demo Codes for Merging and Appending PDF Document
pdf merge comments; best pdf combiner
C# merge pdf files into one - VB.NET PDF File Merge Library: Merge, append PDF files in vb.net, ASP.NET, MVC, Ajax, WinForms, WPF
VB.NET Guide and Sample Codes to Merge PDF Documents in .NET Project
pdf merger online; add pdf together
Appendix K:  - Compiler Errors and Warnings 
10-142 
CoDeSys V2.3 
4372 
"Step '<name>': Time limit needs type 'TIME'" 
Define the time limits of the step in the step attributes by using a variable of type TIME or by a time 
definition in correct format (e.g. "t#200ms"). 
4373 
"IEC-actions are only allowed with SFC-POUs" 
There is an action assigned to a non-SFC-POU (see in the Object Organizer), which is programmed in 
SFC and which contains IEC actions. Replace this action by one which contains no IEC actions. 
4374 
"Step expected instead of transition '<name>'" 
The SFC POU is corrupt, possibly due to any export-import actions. 
4375 
"Transition expected instead of step '<name>'" 
The SFC POU is corrupt, possibly due to any export-import actions. 
4376 
"Step expected after transition '<name>'" 
The SFC POU is corrupt, possibly due to any export-import actions. 
4377 
"Transition expected after step '<name>'" 
The SFC POU is corrupt, possibly due to any export-import actions. 
4400 
Import / conversion of POU '<name>' contains errors resp. is not complete." 
The POU cannot be converted to IEC 61131-3 completely. 
4401 
"S5 time constant <number> seconds is too big (max. 9990s)." 
There is no valid BCD coded time in the accu. 
4402 
"Direct access only allowed on I/Os." 
Make sure that you only access variables which are defined as input or output. 
4403 
"STEP5/7 instruction invalid or not convertible to IEC 61131-3." 
Some STEP5/7 commands are not convertible to IEC 61131-3, e.g. CPU commands like MAS. 
4404 
"STEP5/7 operand invalid or not convertible to IEC 61131-3." 
Some STEP5/7 operands are not convertible to IEC 61131-3 respectively an operand is missing. 
4405 
"Reset of a STEP5/7 timer cannot be converted into IEC 61131-3." 
The corresponding IEC timer have no reset input. 
Online Merge PDF files. Best free online merge PDF tool.
We try to make it as easy as possible to merge your PDF files. RasterEdge C#.NET PDF document merging toolkit (XDoc.PDF) is designed to help .NET
add pdf files together reader; add two pdf files together
C# Word - Merge Word Documents in C#.NET
Combine and Merge Multiple Word Files into One Using C#. This part illustrates how to combine three Word files into a new file in C# application.
break pdf into multiple files; all jpg to one pdf converter
Appendix K:  - Compiler Errors and Warnings 
CoDeSys V2.3 
10-143 
4406 
"STEP5/7 Counter constant out of range (max. 999)." 
There is no valid BCD coded counter constant in the accu. 
4407 
"STEP5 instruction not convertible to IEC 61131-3." 
Some STEP5/7 instructions cannot be converted to IEC 61131-3, e.g. DUF. 
4408 
"Bit access of timer or counter words not convertible into IEC 61131-3." 
Special timer/counter commands are not convertible into IEC 61131-3. 
4409 
"Contents of ACCU1 or ACCU2 undefined, not convertible into IEC 61131-3." 
A command, which connects the both accus, cannot be converted, because the accu values are not 
defined. 
4410 
"Called POU not in project." 
Import the called POU. 
4411 
"Error in global variable list." 
Please check the SEQ file. 
4412 
"Internal error no.11" 
Please contact the PLC manufacturer. 
4413 
"Error in format of line in data block" 
In the code which should be imported there is an erroneous date. 
4414 
"FB/FX name missing." 
In the original S5D file the symbolic name of an (extended) POU is missing. 
4415 
"Instruction after block end not allowed." 
A protected POU cannot get imported. 
4416 
"Invalid command" 
The S5/S7 command cannot be disassembled. 
4417 
"Comment not closed" 
Close the comment with "*)". 
C# PowerPoint - Merge PowerPoint Documents in C#.NET
Combine and Merge Multiple PowerPoint Files into One Using C#. This part illustrates how to combine three PowerPoint files into a new file in C# application.
merge pdf files; c# merge pdf pages
C# Create PDF from images Library to convert Jpeg, png images to
Example: Convert More than Two Type Images to PDF in C#.NET Application. This example shows how to build a PDF document with three image files (BMP, JPEG
attach pdf to mail merge; batch pdf merger online
Appendix K:  - Compiler Errors and Warnings 
10-144 
CoDeSys V2.3 
4418 
"FB/FX-Name too long (max. 8 characters)" 
The symbolic name of an (extended) POU is too long. 
4419 
"Expected format of line "(* Name: <FB/FX-Name> *)" " 
Correct the line correspondingly. 
4420 
"Name of FB/FX parameter missing" 
Check the POUs. 
4421 
"Type of FB/FX parameter invalid" 
Check the POUs. 
4422 
"Type of FB/FX parameter missing" 
Check the POUs. 
4423 
"Invalid FB/FX call parameter" 
Check the interface of the POU. 
4424 
"Warning: FB/FX for call either missing or parameters invalid or has '0' parameters" 
The called POU is not imported yet or is not correct or has no parameters (in the last case you can 
ignore the error message). 
4425 
"Definition of label missing" 
The aim (label) of the jump is not defined. 
4426 
"POU does not have a valid STEP 5 block name, e.g. PB10" 
Modify the POU name. 
4427 
"Timer type not declared" 
Add a declaration of the timer in the global variables list. 
4428 
"Maximum number of open STEP5 brackets exceeded" 
You may not use more than seven open brackets. 
4429 
"Error in name of formal parameter" 
The parameter name may not exceed four characters. 
C# PDF: C# Code to Process PDF Document Page Using C#.NET PDF
C# PDF Page Processing: Merge PDF Files - C#.NET PDF document merger APIs for combining two different PDF documents into one large PDF file.
combine pdf; add multiple pdf files into one online
C# Create PDF from CSV to convert csv files to PDF in C#.net, ASP.
document, it's unnecessary to convert CSV files to .xls This C# sample code illustrates how to convert CSV to Description: Convert to PDF/TIFF and save it into
combine pdfs online; add pdf files together
Appendix K:  - Compiler Errors and Warnings 
CoDeSys V2.3 
10-145 
4430 
"Type of formal parameter not IEC-convertible" 
In IEC 61131-3 Timer, counter and POUs cannot be converted as formal parameters. 
4431 
"Too many 'VAR_OUTPUT' parameters for a call in STEP5 STL" 
A POU may not contain more than 16 formal parameters as outputs. 
4432 
"Labels within an expression are not allowed" 
In IEC 61131-3 jump labels may not be inserted at any desired position. 
4434 
"Too many labels" 
A POU may not contain more than 100 labels. 
4435 
"After jump / call, a new expression must start" 
After jump or call a Load command LD must follow. 
4436 
"Bit result undefined, not convertible to IEC 61131-3." 
The command which is used by VKE cannot get converted, because the value of the VKE is not 
known. 
4437 
"Type of instruction and operand are not compatible" 
A bit command is used for a word operand or the other way round. 
4438 
"No data block opened (insert instruction C DB before)" 
Insert a "A DB". 
4500 
"Unrecognized variable or address" 
The watch variable is not declared within the project. By pressing <F2> you get the input assistant 
which lists the declared variables. 
4501 
"Extra characters following valid watch expression" 
Remove the surplus signs. 
4520 
"Error in Pragma: Flag expected before '<Name>'!" 
The pragma is not correct. Check whether ‘<Name>' is a valid flag. 
4521 
"Error in Pragma: Unexpected element '<Name>'!" 
Check whether pragma is composed correctly. 
C# PDF: C#.NET PDF Document Merging & Splitting Control SDK
C#. VB.NET. Home > .NET Imaging SDK > C# > Merge and Split C# PDF Merging & Splitting Application. This C#.NET PDF to one PDF file and split source PDF file into
pdf combine pages; c# merge pdf files into one
VB.NET TWAIN: Scanning Multiple Pages into PDF & TIFF File Using
most cases, those scanned individual image files need to New PDFDocument(imgSouce) doc1.Save("outputPDF.pdf") End Sub Written in managed C# code, this VB.NET
pdf mail merge; acrobat merge pdf
Appendix K:  - Compiler Errors and Warnings 
10-146 
CoDeSys V2.3 
4522 
"flag off' pragma expected!" 
Pragma has not been terminated, insert a 'flag off' instruction. 
4523 
"Pragma {<Pragmaname>} not allowed in interface of type '<Name>'" 
Das Pragma cannot be used at this location. Please see the CoDeSys Online Help resp. Users Guide, 
keyword 'pragma' for the correct use of pragmas. 
4550 
"Index out of defined range : Variable OD "number>, Line <line number>." 
Ensure that the index is within the area which is defined in the target settings/networkfunctionality. 
4551 
"Subindex out of defined range : Variable OD "number>, Line <line number>." 
Ensure that the subindex is within the area which is defined in the target settings/networkfunctionality. 
4552 
"Index out of defined range : Parameter OD "number>, Line <line number>." 
Ensure that the index is within the area which is defined in the target settings/networkfunctionality. 
4553 
"Subindex out of defined range : Parameter OD "number>, Line <line number>." 
Ensure that the subindex is within the area which is defined in the target settings/networkfunctionality. 
4554 
"Variablename invalid: Variable OD <number>, Line <line number>." 
Enter a valid project variable in the filed ‚variable’. Use the syntax <POU name>.<variable name> 
resp. for global variables .<variable name>  
4555 
"Empty table-entry, input not optional: Parameter OD <number>, Line <line number>  
You must make an entry in this field. 
4556 
"Empty table-entry, input not optional: Variable OD <number>, Line <number>" 
You must make an entry in this field. 
4557 
"The required parameter memory is too large" 
The maximum size of data which can be loaded via parameter lists of type Parameters to the 
controller has been exceeded. This size is defined by the target system. Information on the data size 
is displayed in the message window at compilation. Reduce the parameter lists size. 
4558 
"The required variable memory is too large" 
The maximum size of data which can be loaded via parameter lists of type Variables to the controller 
has been exceeded. This size is defined by the target system. Information on the data size is 
displayed in the message window at compilation. Reduce the parameter lists size. 
Appendix K:  - Compiler Errors and Warnings 
CoDeSys V2.3 
10-147 
4560 
"Invalid value: Dictionary '<Name>', column '<Name>', line '<line number>'" 
Check this entry. It depends on the currently used column (attribute) definition which entries are valid 
for this field. This definition is given by the target-specific XML description file of the Parameter 
Manager resp. by the standard settings which will be used if there is no description file. 
4561 
"Column not defined: '<Name>'" 
Entries in a column of the parameter list refer to another column, which is not defined however. The 
column definitions are given by the description file (XML) of the Parameter Manager for the current 
target. If a description file is not available, standard settings are used. 
4562 
"Index/subindex used already: Dictionary '<Name>', line '<Line Number>'" 
The Index/Subindex-combination must be unique throughout all parameter lists, because it can be 
used for the parameter access. Correct the indices correspondingly. 
4563 
"Identifier '<Name>' used already: Dictionary '<Name>', line '<Line Number>'" 
The name must be unique throughout all parameter lists, because it can be used for parameter 
access. 
4564 
"Index '<Name>'  is out of range: Dictionary '<Name>', line '<Line Number>' " 
Enter an index which is within the range defined in the target settings, category network functionality 
in field 'Index range...' for the respective list types (Variables, Parameters, Mappings). 
4565 
"Subindex '<Name>' is out of range: Dictionary '<Name>', line '<Line Number>' " 
Enter an subindex which is within the range defined in the target settings, category network 
functionality in field 'SubIndex range'. 
4566 
"An error occurred during import of the parameter manager" 
You have imported an export file which contains erroneous information on the Parameter Manager. 
Check the *.exp-file. 
4600 
"Networkvariables: '<name>' expression is not from type bool!" 
Make sure that the variable defined in the properties dialog of the network variables list at option 
'Transmit on event', is of type BOOL. 
4601 
"Network variables '<name>': No cyclic or freewheeling task for network variable exchange 
found" 
There is no cyclic or free-wheeling task resp. PLC_PRG in the project where the network variables of 
type CAN or UDP of the given list are used (only declaration is not sufficient!). You must take care that 
the variables are used in an appropriate task or in PLC_PRG. If you want to use them in several 
tasks, regard, that at data exchange the task with the highest priority will be regarded. 
Appendix K:  - Compiler Errors and Warnings 
10-148 
CoDeSys V2.3 
4602 
"'<name of network variables list>': The object uses UDP port '<port number>' instead of '<port 
number>'" 
In the Settings of the named network variables list a port number is used which is not the same as that 
which is used in the first network variables list found in the global variables folder. Take care that all 
network variables lists are using the same port! 
4604 
"Network variables '<name>': Base identifier has been used more than once." 
The same COB-ID is used in the configuration settings (‘Object’ ‘Properties’) of multiple Network 
Variables lists. Assign unique IDs. 
4605 
"Network variables '<name>': Duplicate CAN COB id." 
In the configuration of a Network Variables list (‘Object’ ‘Properties’) a COB-ID is used, which is also 
specified in the CAN PLC Configuration. Assign unique IDs. 
4620 
Unused variables have been found in the project. See See Chapter 4.3 for the description for 
command 'Project' 'Check' Unused Variables. 
4621 
There are overlaps at the assignment of variables to memory areas via the  „AT"-declaration. See 
Chapter 4.3 for the description of command 'Project' 'Check'  'Overlapping memory areas'. 
4622 
IEC addresses assigned to the same memory area are referenced in more than one task. See 
Chapter 4.3 for the description of command 'Project' 'Check' 'Concurrent Access'. 
4623 
The project gains write access to the same memory area at more than one place. See Chapter 4.3 for 
the description of command 'Project' 'Check' 'Multiple writes to output'. 
4650 
"AxisGroup '<Name>': Task '<Name>' does not exist." 
In the PLC Configuration in the definition of the axis group (dialog 'Module parameters', column 
'Value') there is a name defined for the task which is controlling the data transfer of this axis group, 
which is not known in the Task Configuration. Correct Task Configuration resp. PLC Configuration 
correspondingly. 
4651 
"AxisGroup '<Name>': Cycletime (dwCycle) not set." 
In dialog 'Module parameters' of the axis group enter a value for the cycle time (dwCycle). 
4656 
"Drive '<name>': Scaling factor must not be 0. 
Open the PLC Configuration and check the Scale entries in the configuration dialog of the drive. All 
fields must have entries not equal "0". 
4670 
"CNC program '<Name>': Global variable '<Name>' not found." 
Appendix K:  - Compiler Errors and Warnings 
CoDeSys V2.3 
10-149 
In the CNC program a global variable is used (e.g. $glob_var$), which is not defined in the project. 
Add the appropriate declaration resp. correct the assignment to the variable in the CNC program. 
4671 
"CNC program '<Name>': Variable '<Name>' has an incompatible type." 
There is a variable assigned in a instruction of the CNC program , which is declared of a data type 
which is not valid in this place. Use another variable resp. correct the type specification. 
4685 
"CAM '<Name>': CAM table type unknown." 
Check the data type which is specified in the CAM Editor dialog ''Compile options.." for the equidistant 
resp. element optimized point table.  
4686 
"CAM '<Name>': CAM point exceeds datatype range." 
In this CAM points are used, which are out of the data range specified for the point table. For the 
current range definition see dialog 'Compile options..' in the CAM-Editor.  
4700 
"'<Number>' ('<Name>'): Watch expression '<Name>' is not a numeric variable."  
In the configuration of the visualization a variable is used which is not a number, as required in this 
place (e.g. at the configuration of XOffset or Angle values etc.).  
4701 
"'<Name>' ('<Number>'): Watch expression '<name>' is not of type BOOL."  
In the configuration of the visualization a variable is used which is not of type BOOL, as required in 
this place. 
4702 
"'<Name>' ('<Number>'): Watch expression '<name>' is not of type STRING." 
The visualization contains a variable which is not of type STRING although this is required in this 
place (e.g. at the tooltip configuration). 
4703 
"'<Name>'  ('<Number>' ): Invalid watch expression '<Name>'" 
The visualization contains an invalid variable. 
4704 
"'<Name>'('<Number>'): Invalid initial value in watch list '<Name>'." 
In this watch list, used in a visualization (INTERN command in category Input), there is a erroneous 
initial value. Check the used list. 
4705 
"'<Name>' ('<Number>'): No valid alarm group assigned to alarm table." 
Enter a valid alarm group In the configuration dialog of the alarm table (category Alarm table). 
4706 
"'<Name>' ('<Number>'): Use of alarm tables requires the target setting 'Alarmhandling in 
controller' to be activated.." 
Open the target settings in tab 'Resources' and in dialog 'Visualization' activate option 'Alarmhandling 
in the PLC'. Otherwise the alarm table element will not work in the Target-Visualization which is 
currently activated also in the target settings. 
Appendix K:  - Compiler Errors and Warnings 
10-150 
CoDeSys V2.3 
4707 
"'<Name>' ('<Number>'):  Alarm tables are not supported by the current target. Please remove 
these elements from the target visualization.“ 
The target system does not support the processing of alarms (target setting 'Alarmhandling in the 
PLC' cannot be activated). Thus for running a Target-Visualization (currently activated in the target 
settings in tab 'Visualization') the alarm table elements must be removed from the visualization. 
4708 
"'<Name>' ('<Number>'):  Use of trends requires the target setting 'Trend recording in the PLC’ 
to be activated. 
Open the target settings in tab 'Resources' and in dialog 'Visualization' activate option 'Store trend 
data in the PLC'. Otherwise the trend element will not work in the Target-Visualization which is 
currently activated also in the target settings. 
4709 
"'<Name>' ('<Number>'):  Trends are not supported by the current target. Please remove these 
elements from the target visualization." 
The target system does not support the processing of trend data (target setting 'Store trend data in the 
PLC' cannot be activated). Thus for running a Target-Visualization (currently activated in the target 
settings in tab 'Visualization') the trend elements must be removed from the visualization. 
4712 
"'<Name>'('<number>'):  The selected target does not support the output of passwords"" 
The text output in the visualization element is configured to work via dynamic texts or unicode texts. 
Additionally the option "Hidden" is activated in the "Input" category. This is not supported by the 
Target-Visualization. 
4900 
"Invalid type for conversion" 
You are using a type conversion which is not supported by the currently chosen codegenerator. 
4901 
"Internal error: Overflow in array access!" 
The array bounds are to large for a 32-bit-variable. Reduce the array index range. 
Documents you may be interested