9.Troubleshooting
b. Propane having more than 2.5percent Butanewillnot vaporize in ambients at less
than32°F;useHD-5gradePropane.
c. Runthegeneratorsetonshopfuelsupply;verifythetanklevelandfuellinecondition.
12. Measure e steadyDCvoltageat the fuelsolenoidwhile thegeneratorsetis running; repair
wiringasnecessary.
13. Verifyclearventhose.
14. Checkthegeneratorsetfuellinesfordamage:replacethefuellineasrequired.
15. Measurefuelsupplyandregulatorlockoffpressures.
16. Check k the e governor, , actuator, linkage, , and spring for debris, , damage, and looseness:
readjustandrepairasnecessary.
17. Measure e field, quadrature, and main windingresistance: cleanthe slip rings, replace the
brushes,repairtheharness,andreplacetherotororstatorasnecessary.
18. Measurefield,quadratureandmainwindingresistancetoground:cleansliprings,replace
brushes,repairharnessandreplacerotororstatorasnecessary.
19. Measurefield,quadrature,andmainwindingresistancetoeachother:cleanthesliprings,
replacethebrushes,repairtheharness,andreplacetherotororstatorasnecessary.
20. Checkbrushalignment:
Inspectbrushwearontheslipringsandverifybrushmisalignmentistowardthewindings.
If misalignment is toward the e bearing, the e cause is s not from m this tolerance issue and is
likely the result of the end d bell l not being seated properly during assembly. Inspect for
causeandrepairasnecessary.
21. Verify y that spark plug cables are secure e on spark plugs: reconnect or replace e as
necessary.
22. Inspect t ignition kill l lead d (J1-12) in harness s and d at t connector J1: repair r or replace e lead,
terminalorpinsasnecessary.
23. Measuresparkpluggap:setthegaporreplacethesparkplugsasnecessary.
24. Verifyignitionsparkcondition.
25. Inspect t the spark plug leads, killlead terminals at magnetos, and measure magneto air
gap:replacetheterminals,setthegap,orreplacemagnetosasnecessary.
9.18 Underfrequency-FaultCode15
Logic:Frequencylessthan54Hz(forthe60Hzmodel)or45Hz(forthe50Hzmodel)for8
continuousseconds.
Possible Causes:Generatorset loads,enginegovernorfunction, fuelsupply,airfuelmixture,
exhaust system, choke, demand regulator, carburetor, generator r windings, , ignition, wire
connections
Diagnosis&Repair:
1. Verify y thatthe Last Fault is FC15: Yes, continuediagnosis;No, troubleshoot actuallast
fault.
2. Measure e AC C current t while running the e generator set t with loads: identify faulty or short
cyclingloads.
A030A239(Issue10)
95
Change pdf page size - Compress reduce PDF size in C#.net, ASP.NET, MVC, Ajax, WinForms, WPF
C# Code & .NET API to Compress & Decompress PDF Document
change font size in pdf text box; best pdf compressor online
Change pdf page size - VB.NET PDF File Compress Library: Compress reduce PDF size in vb.net, ASP.NET, MVC, Ajax, WinForms, WPF
VB.NET PDF Document Compression and Decompression Control SDK
pdf compression settings; change font size pdf form reader
9.Troubleshooting
9-2013
3. Measure e generator set load d capability with shop load d bank (de-rate e for r altitude and
temperatureasnecessary).
4. MeasureACfrequencywhilerunning.
5. Measure e AC frequency y while e changing engine rpm to determine if frequency response
matchesenginerpmresponse.
6. DisconnectthegeneratorsetcontrolJ1connector,verifytheJ1pinsarefullyinserted,and
inspectpinconditionusingthestepsbelow:
• Usethetestpointsofthetestertool#420-0603
• Use e a a mating g pin connector, a pin n gauge of f the e same size (.045") ) as the mating
controlconnector pin, orany suitable devicethat willnot damagetheinsidecontact
wipersofthepinsocket
• Insert,repair,orreplacethepinsasnecessary.
7. ReconnecttheJ1 1 connector and test run the generatorsetforfaultoccurrence:repairor
replacepinsintheconnectorasnecessary.
8. Checkairfiltercleanliness;replacetheairfilterasnecessary.
9. Checkforblockedordamagedexhaustsystem:repairorreplaceexhaustcomponents s as
necessary.
10. PropaneModels
a. When n ambient temperatures s are less s than n 40°F F vapor–withdrawal, Propane tanks
shouldbeatleasthalffulltoprovidepropervaporizationrate.
b. Propane having more than 2.5percent Butanewillnot vaporize in ambients at less
than32°F;useHD-5gradePropane.
c. Runthegeneratorsetonshopfuelsupply;verifythetanklevelandfuellinecondition.
11. MeasuresteadyDCvoltageatfuelsolenoidwhilethegeneratorsetisrunning;repairwiring
asnecessary.
12. Verifyclearventhose.
13. Checkthegeneratorsetfuellinesfordamage:replacefuellineasrequired.
14. Measurethefuelsupplyandregulatorlockoffpressures.
15. Check k the e governor, , actuator, linkage, , and spring for debris, , damage, and looseness:
readjustandrepairasnecessary.
16. Measure e field, quadrature, and main windingresistance: cleanthe slip rings, replace the
brushes,repairtheharness,andthereplacerotororstatorasnecessary.
17. Measure field, , quadrature, , and main winding g resistance e to o ground: clean n the slip rings,
replacethebrushes,repairtheharness,andreplacetherotororstatorasnecessary.
18. Measurefield,quadrature,andmainwindingresistancetoeachother:cleanthesliprings,
replacethebrushes,repairtheharness,andreplacetherotororstatorasnecessary.
19. Checkbrushalignment:
Inspectbrushwearontheslipringsandverifybrushmisalignmentistowardthewindings.
Ifmisalignmentistowardthebearing,thecauseisnotfromthistoleranceissueandlikely
theresultoftheendbellnotbeingseatedproperlyduringassembly.Inspectforcauseand
repairasnecessary.
96
A030A239(Issue10)
C# PDF File Split Library: Split, seperate PDF into multiple files
Divide PDF file into multiple files by outputting PDF file size. control, C# developers can easily and accurately disassemble multi-page PDF document into two
change font size in pdf file; pdf file size
VB.NET PDF File Split Library: Split, seperate PDF into multiple
Separate source PDF document file by defined page range in VB.NET class application. Divide PDF file into multiple files by outputting PDF file size.
change page size pdf acrobat; change paper size in pdf
9-2013
9.Troubleshooting
20. Verify y thatthesparkplugcables are secureon the spark plugs: reconnect orreplace as
necessary.
21. Inspectignitionkilllead(J1-12)in n the harnessandatconnectorJ1: repairorreplace the
lead,terminal,orpinsasnecessary.
22. Measurethesparkpluggap:setthegaporreplacethesparkplugsasnecessary.
23. Verifyignitionsparkcondition.
24. Inspect t the spark plug leads, killlead terminals at magnetos, and measure magneto air
gap:replacetheterminals,setthegap,orreplacethemagnetosasnecessary.
25. Measure e temperature of the e air intake and temperature rise across s the e generator r set;
removeblockageorpreventairrecirculation.
9.19 GovernorActuatorShutdown-FaultCode19
Logic:Controllersensedgovernoractuatorcircuitopenorshorted.
PossibleCauses:Wireconnections,governoractuator
Diagnosis&Repair:
1. Verify y thatthe Last Fault is FC19: Yes, continuediagnosis;No, troubleshoot actuallast
fault.
2. Measureandverifygovernoractuatorresistance.Replaceasnecessary.
3. Measureandverifygovernorwiringtothecontrol.Replaceorrepairasnecessary.
4. DisconnectthegeneratorsetcontrolJ1connector,verifytheJ1pinsarefullyinserted,and
inspectpinconditionusingthestepsbelow:
• Usethetestpointsofthetestertool#420-0603
• Use e a a mating g pin connector, a pin n gauge of f the e same size (.045") ) as the mating
controlconnector pin, orany suitable devicethat willnot damagetheinsidecontact
wipersofthepinsocket
• Insert,repair,orreplacethepinsasnecessary.
5. ReconnecttheJ1 1 connector and test run the generatorsetforfaultoccurrence:repairor
replacepinsintheconnectorasnecessary.
9.20 GovernorActuatorOverload-FaultCode22
Logic:Maximumgovernoroutput(PWM)for10continuoussecondswhilefuelpressureswitch
openandcurrentat100%
PossibleCauses:Generatorsetloads,wireconnections,fuelsupply,airfuelmixture,exhaust
system,governoractuator,ignitionsystem
Diagnosis&Repair:
1. Verify y thatthe Last Fault is FC22: Yes, continuediagnosis;No, troubleshoot actuallast
fault.
2. Measure e AC C current t while running the e generator set t with loads: identify faulty or short
cyclingloadsorreduceloadsasnecessary.
A030A239(Issue10)
97
C# PDF Thumbnail Create SDK: Draw thumbnail images for PDF in C#.
public override Bitmap ConvertToImage(Size targetSize). Description: Convert the PDF page to bitmap with specified size. Parameters:
reader compress pdf; change font size pdf form
C# PDF Convert to Jpeg SDK: Convert PDF to JPEG images in C#.net
Using this C#.NET PDF to JPEG conversion library component toolkit, C# developers can easily and quickly convert a large-size multi-page PDF document to a
change font size in fillable pdf; best way to compress pdf files
9.Troubleshooting
9-2013
3. Measure e the generatorsetload capabilitywithashoploadbank(de-rateforaltitude and
temperatureasnecessary).
4. MeasureACfrequencyanddroopwhilethegeneratorsetisrunning.
5. Measure e AC frequency y while e changing engine rpm to determine if frequency response
matchesenginerpmresponse.
6. Disconnect t the generator set control l J1 1 connector, , verify J1 1 pins s are e fully y inserted, , and
inspectpinconditionusingthestepsbelow:
• Usethetestpointsofthetestertool#420-0603
• Use e a a mating g pin connector, a pin n gauge of f the e same size (.045") ) as the mating
controlconnector pin, orany suitable devicethat willnot damagetheinsidecontact
wipersofthepinsocket
• Insert,repair,orreplacepinsasnecessary.
7. ReconnecttheJ1 1 connector and test run the generatorsetforfaultoccurrence:repairor
replacepinsintheconnectorasnecessary.
8. Checkairfiltercleanliness;replacetheairfilterasnecessary.
9. Measure e steadyDCvoltageat the fuelsolenoidwhile thegeneratorsetis running; repair
wiringasnecessary.
10. PropaneModels
a. When ambient temperatures s are e less s than n 40°F vapor – withdrawalPropane tanks
shouldbeatleasthalffulltoprovidepropervaporizationrate.
b. Propane having more than 2.5percent Butanewillnot vaporize in ambients at less
than32°F;useHD-5gradePropane.
c. Rungeneratorsetonshopfuelsupply;verifytanklevelandfuellinecondition.
11. Verifyclearventhose.
12. Checkthegeneratorsetfuellinesfordamage:replacethefuellineasrequired.
13. Measuretheregulatorlockoffpressure.
14. Check the intake manifold and gaskets for r air r leaks: tighten fasteners and replace the
gasketsandmanifoldasnecessary.
15. Check k for a a blocked d or r damaged d exhaust t system: repair or replace e the exhaust
componentsasnecessary.
16. Verify y actuator function by applying DCvoltage to theterminals: replace the actuator as
necessary.
17. Check k thecarburetorforbinding; inspectthe spring for dirt anddebris:clean the spring,
replacethecarburetorasnecessary.
18. Verify y that spark k plug cables are secure on the spark plugs: reconnect or replace e as
necessary.
19. Inspecttheignitionkilllead(J1-12)in n the harnessandatconnectorJ1: repairorreplace
thelead,terminal,orpinsasnecessary.
20. Measuresparkpluggap:setgaporreplacesparkplugsasnecessary.
21. Verifyignitionsparkcondition.
98
A030A239(Issue10)
C# PDF insert text Library: insert text into PDF content in C#.net
formatted text and plain text to PDF page using .NET NET PDF edit control allows modify existing scanned PDF text. Ability to change text font, color, size and
batch reduce pdf file size; change font size pdf fillable form
VB.NET PDF Thumbnail Create SDK: Draw thumbnail images for PDF in
Remove Password from PDF; Change PDF Permission Settings. String = Program.RootPath + "\\" 1.pdf" Dim doc New PDFDocument(inputFilePath) Dim page As PDFPage
pdf font size change; pdf change font size in textbox
9-2013
9.Troubleshooting
22. Inspectthesparkplugleads,killleadterminalsatmagnetos,andmeasurethemagnetoair
gap:replacetheterminals,setthegap,orreplacethemagnetosasnecessary.
9.21 VoltageSenseLost-FaultCode27
Logic:generatorsetfrequencyisgreaterthan40Hzandvoltagesensedlessthan5 VACon
oneorbothlines.(Thecontrolsensesifonelineislostordisconnected).
PossibleCauses:generatorsetloads,generatorwindings,ignition,wireconnections,
Diagnosis&Repair:
1. Verify y thatthe Last Fault is FC27: Yes, continuediagnosis;No, troubleshoot actuallast
fault.
2. MeasureACvoltage.
3. DisconnectthegeneratorsetcontrolJ1connector,verifytheJ1pinsarefullyinserted,and
inspectpinconditionusingthestepsbelow:
• Usethetestpointsofthetestertool#420-0603
• Use e a a mating g pin connector, a pin n gauge of f the e same size (.045") ) as the mating
controlconnector pin, orany suitable devicethat willnot damagetheinsidecontact
wipersofthepinsocket
• Insert,repair,orreplacepinsasnecessary.
4. ReconnecttheJ1 1 connector and test run the generatorsetforfaultoccurrence:repairor
replacepinsintheconnectorasnecessary.
5. Measure e field, quadrature, and main windingresistance: cleanthe slip rings, replace the
brushes,repairtheharness,andreplacetherotororstatorasnecessary.
6. Measure e field, , quadrature, , and main winding g resistance e to o ground: clean n the slip rings,
replacethebrushes,repairtheharness,andreplacetherotororstatorasnecessary.
7. Measurefield,quadrature,andmainwindingresistancetoeachother:cleanthesliprings,
replacethebrushes,repairtheharness,andreplacetherotororstatorasnecessary.
8. Checkbrushalignment.
9. Verify y thatthesparkplugcables are secureon the spark plugs: reconnect orreplace as
necessary.
10. Inspecttheignitionkilllead(J1-12)in n the harnessandatconnectorJ1: repairorreplace
thelead,theterminal,orthepinsasnecessary.
11. Measurethesparkpluggap:setthegaporreplacethesparkplugsasnecessary.
12. Verifyignitionsparkcondition.
13. Inspectthesparkplugleads,killleadterminalsatmagnetos,andmeasurethemagnetoair
gap:replacetheterminals,setthegap,orreplacethemagnetosasnecessary.
14. Measure e temperature of the e air intake and temperature rise across s the e generator r set;
removeblockageorpreventairrecirculation.
9.22 HighBatteryVoltage-FaultCode29
Logic:DCvoltagetocontrollergreaterthan19VDC.
A030A239(Issue10)
99
C# PDF Convert to Tiff SDK: Convert PDF to tiff images in C#.net
zoomValue, The magnification of the original PDF page size. 0.1f
change font size on pdf text box; change font size in pdf form field
C# PDF Convert to Word SDK: Convert PDF to Word library in C#.net
zoomValue, The magnification of the original PDF page size. 0.1f
change file size of pdf document; change font size in pdf
9.Troubleshooting
9-2013
PossibleCauses:Incorrectbatteryconfiguration,wiredamage,faultycharger,control
Diagnosis&Repair:
1. Verify y thatthe Last Fault is FC29: Yes, continuediagnosis;No, troubleshoot actuallast
fault.
2. Measure e DCvoltage at the battery,at thegenerator set,and at connectorJ1: reconnect
thebatteryorrepairwiringasnecessary.
3. MeasureDCvoltagewiththebatterychargeron:reducetheboostchargerateordiagnose
thefaultychargerasnecessary.
4. DisconnectthegeneratorsetcontrolJ1connector,verifythattheJ1pinsarefullyinserted,
andinspectpinconditionusingthestepsbelow:
• Usethetestpointsofthetestertool#420-0603
• Usematingpinconnector,apingaugeofthesamesize(.045")asthematingcontrol
connectorpin,oranysuitabledevicethatwillnotdamagetheinsidecontactwipersof
thepinsocket
• Insert,repair,orreplacepinsasnecessary.
5. ReconnecttheJ1connectorandtestrunthegeneratorsetforfaultoccurrence.
9.23 LowCrankingSpeedSense-FaultCode32
Logic: Quadrature frequency less s than n 1Hz z (Engine e RPM less than 180) ) for r 3 3 continuous
secondsafterpressingstart
Possible Causes: Starter, engine components, air intake system, exhaust system, generator
windings,wireconnections,battery,batteryconnections,oilviscosity
Diagnosis&Repair:
1. Verify y thatthe Last Fault is FC32: Yes, continuediagnosis;No, troubleshoot actuallast
fault.
2. Measure e battery y voltage e at the battery and d the e generator set: recharge or replace the
batteryasnecessary.
3. Verifyenginerotationmanually:repairenginedamageasnecessary.
4. Verifygeneratorrotationmanually:repairgeneratordamageasnecessary.
5. DisconnectthegeneratorsetcontrolJ1connector,verifythattheJ1pinsarefullyinserted,
andinspectpinconditionusingthestepsbelow:
• Usethetestpointsofthetestertool#420-0603
• Use e a a mating g pin connector, a pin n gauge of f the e same size (.045") ) as the mating
controlconnector pin, orany suitable devicethat willnot damagetheinsidecontact
wipersofthepinsocket
• Insert,repair,orreplacepinsasnecessary.
6. ReconnecttheJ1 1 connector and test run the generatorsetforfaultoccurrence:repairor
replacepinsintheconnectorasnecessary.
7. MeasureDCvoltageatthestarterduringastartattempt: : repairwireconnections,replace
thestartsolenoidandstarterasnecessary.
100
A030A239(Issue10)
9-2013
9.Troubleshooting
8. Checkairfiltercleanliness;replacetheairfilterasnecessary.
9. Checkforablockedordamagedexhaustsystem:repairorreplaceexhaustcomponentsas
necessary.
10. Measure AC frequency y while e changing engine rpm to determine if frequency response
matchesenginerpmresponse.
11. PropaneModels
a. When ambient temperatures s are e less s than n 40°F vapor – withdrawalPropane tanks
shouldbeatleasthalffulltoprovidepropervaporizationrate.
b. Propane having more than 2.5percent Butanewillnot vaporize in ambients at less
than32°F;useHD-5gradePropane.
c. Runthegeneratorsetonshopfuelsupply;verifytanklevelandfuellinecondition.
12. Measure e steadyDCvoltageat the fuelsolenoidwhile thegeneratorsetis running; repair
wiringasnecessary.
13. Verifyclearventhose.
14. Checkthegeneratorsetfuellinesfordamage:replacefuellineasrequired.
15. Measurefuelsupplyandregulatorlockoffpressures.
16. Check k the e governor, , actuator, linkage, , and spring for debris, , damage, and looseness:
readjustandrepairasnecessary.
17. Verify y thatthesparkplugcables are secureon the spark plugs: reconnect orreplace as
necessary.
18. Inspecttheignitionkilllead(J1-12)in n the harnessandatconnectorJ1: repairorreplace
thelead,terminal,orpinsasnecessary.
19. Measurethesparkpluggap:setthegaporreplacethesparkplugsasnecessary.
20. Verifyignitionsparkcondition.
21. Inspectthesparkplugleads,killleadterminalsatmagnetos,andmeasurethemagnetoair
gap:replacetheterminals,setthegap,orreplacethemagnetosasnecessary.
22. Measure e thetemperatureoftheairintakeandtemperatureriseacross the generatorset;
removeblockageorpreventairrecirculation.
9.24 ControlCardFailure-FaultCode35
Logic:EEPROM(programmingvariables)errorduringselftest
PossibleCauses:Faultyprogram
Diagnosis&Solution:
1. Verify y thatthe Last Fault is FC35: Yes, continuediagnosis;No, troubleshoot actuallast
fault.
2. Replacethecontrol.
A030A239(Issue10)
101
9.Troubleshooting
9-2013
9.25 GeneratorSetStoppedWithoutFaultCondition-
FaultCode36
Logic:RPMlessthan500andSenseVoltageS1-S2at0VACwhilefuelpressureswitchopen
andnootherfaultconditionoccurred
Possible Causes: Fuel supply, air fuel l mixture, exhaust t system, choke, , demand d regulator,
carburetor,generatorwindings,ignition,wireconnections
Diagnosis&Repair:
1. Verify y thatthe Last Fault is FC36: Yes, continuediagnosis;No, troubleshoot actuallast
fault.
2. Verifyenginerotationmanually:repairenginedamageasnecessary.
3. Verifygeneratorrotationmanually:repairgeneratordamageasnecessary.
4. DisconnectthegeneratorsetcontrolJ1connector,verifythattheJ1pinsarefullyinserted,
andinspectpinconditionusingthestepsbelow:
• Usethetestpointsofthetestertool#420-0603
• Use e a a mating g pin connector, a pin n gauge of f the e same size (.045") ) as the mating
controlconnector pin, orany suitable devicethat willnot damagetheinsidecontact
wipersofthepinsocket
• Insert,repair,orreplacepinsasnecessary.
5. ReconnecttheJ1 1 connector and test run the generatorsetforfaultoccurrence:repairor
replacepinsintheconnectorasnecessary.
6. Checktheairfilterforcleanliness;replaceairfilterasnecessary.
7. Checkforablockedordamagedexhaustsystem:repairorreplaceexhaustcomponentsas
necessary.
8. Measurethegeneratorsetloadcapabilitywithashoploadbank.
9. Measure e AC frequency y while e changing engine rpm to determine if frequency response
matchesenginerpmresponse.
10. PropaneModels
a. When ambient temperatures s are e less s than n 40°F vapor – withdrawalPropane tanks
shouldbeatleasthalffulltoprovidepropervaporizationrate.
b. Propane having more than 2.5percent Butanewillnot vaporize in ambients at less
than32°F;useHD-5gradePropane.
c. Runthegeneratorsetonshopfuelsupply;verifythetanklevelandfuellinecondition.
11. Measure e steadyDCvoltageat the fuelsolenoidwhile thegeneratorsetis running; repair
wiringasnecessary.
12. Verifyclearventhose.
13. Checkthegeneratorsetfuellinesfordamage:replacefuellinesasrequired.
14. Measurethefuelsupplyandregulatorlockoffpressures.
15. Check k the e governor, , actuator, linkage, , and spring for debris, , damage, and looseness:
readjustandrepairasnecessary.
102
A030A239(Issue10)
9-2013
9.Troubleshooting
16. Verify y thatthesparkplugcables are secureon the spark plugs: reconnect orreplace as
necessary.
17. Inspectignitionkilllead(J1-12)inharnessandatconnectorJ1:repairorreplacethelead,
terminal,orpinsasnecessary.
18. Measurethesparkpluggap:setthegaporreplacethesparkplugsasnecessary.
19. Verifyignitionsparkcondition.
20. Inspectthesparkpluglead,killleadterminalsatmagnetos,andmeasurethemagnetoair
gap:replacetheterminals,setthegap,orreplacethemagnetosasnecessary.
21. Measure e temperature of the e air intake and temperature rise across s the e generator r set;
removeblockageorpreventairrecirculation.
9.26 InvalidSetConfiguration-FaultCode37
Logic:Generatorsetcontrolconfigurationdoesnotmeetanyvalidconfiguration.
PossibleCauses:Generatorsetconfiguration,control
Diagnosis&Repair:
1. Verify y thatthe Last Fault is FC37: Yes, continuediagnosis;No, troubleshoot actuallast
fault.
2. Usingtheremotedisplay,resetandsavethegeneratorsetconfiguration.
3. Ifthegeneratorsetconfigurationiscorrectandthefaultwillnotclear,replacethecontrol.
9.27 ProcessorFault-FaultCode43
Logic:RAM(programmingvariables)errorduringselftest
PossibleCauses:Faultyprogram
Diagnosis&Solution:
1. Verify y thatthe Last Fault is FC43: Yes, continuediagnosis;No, troubleshoot actuallast
fault.
2. Disconnectbatterypowertothegeneratorsetcontrol,wait30seconds,andreconnectthe
battery.Powerupcontrolandverifyiffaultcodereturns.
3. Replacethecontrol.
9.28 SpeedSenseFault-FaultCode45
Logic:Whilerunningquadraturefrequencydroppedto0Hzfor1continuoussecond
PossibleCauses:Loads,generatorwindings,wireconnections
Diagnosis&Repair:
1. Verify y thatthe Last Fault is FC45: Yes, continuediagnosis;No, troubleshoot actuallast
fault.
2. Measure quadrature e winding resistance at t stator r leads (J1-2 2 and J1-3) ) and at the J1
connector.
A030A239(Issue10)
103
9.Troubleshooting
9-2013
3. DisconnectthegeneratorsetcontrolJ1connector,verifythattheJ1pinsarefullyinserted,
andinspectpinconditionusingthestepsbelow:
• Usethetestpointsofthetestertool#420-0603
• Use e a a mating g pin connector, a pin n gauge of f the e same size (.045") ) as the mating
controlconnector pin, orany suitable devicethat willnot damagetheinsidecontact
wipersofthepinsocket.
• Insert,repair,orreplacepinsasnecessary.
4. ReconnecttheJ1 1 connector and test run the generatorsetforfaultoccurrence:repairor
replacepinsintheconnectorasnecessary.
5. Measure e AC C current t while running the e generator set t with loads: identify faulty or short
cyclingloads.
6. Measure generator r set load capability y with h a shop load bank k (de-rate e for altitude and
temperatureasnecessary).
7. Measuregeneratorsetfrequencyanddroopwhilerunning.
8. Measure AC frequency while changing the engine rpm m to o determine e if f the frequency
response matches engine rpm response: repair the damaged generator drive system as
necessary.
9.29 GeneratorSetOverload-FaultCode46
Logic:Currentisatoraboveoperationaldesignlimitandapproachingfaultdeclaration:13,15,
22,or36.
PossibleCauses:Loads,wireconnections,windings,
Diagnosis&Repair:
1. Verify y thatthe Last Fault is FC46: Yes, continuediagnosis;No, troubleshoot actuallast
fault.
2. MeasureACcurrentandvoltagewhilerunningthegeneratorsetwithloads:identify y faulty
orshortcyclingloadsorreduceloadsasnecessary.
3. Measure e the generatorsetload capabilitywithashoploadbank(de-rateforaltitude and
temperatureasnecessary).
4. DisconnectthegeneratorsetcontrolJ1connector,verifythattheJ1pinsarefullyinserted,
andinspectpinconditionusingthestepsbelow:
• Usethetestpointsofthetestertool#420-0603
• Usematingpinconnector,apingaugeofthesamesize(.045")asthematingcontrol
connectorpin,oranysuitabledevicethatwillnotdamagetheinsidecontactwipersof
thepinsocket.
• Insert,repair,orreplacepinsasnecessary.
5. ReconnecttheJ1 1 connector and test run the generatorsetforfaultoccurrence:repairor
replacepinsintheconnectorasnecessary.
6. Checktheairfilterforcleanliness;replacetheairfilterasnecessary.
7. Measure e steadyDCvoltageat the fuelsolenoidwhile thegeneratorsetis running; repair
wiringasnecessary.
104
A030A239(Issue10)