4.Service
4.8
AlternatorTemperatureSwitch
The alternator temperature switch contacts are normally closed. The switch contacts open at
170°F±5°.
4.9
BrushBlock/SlipRingService
Disconnectthefieldleadsfromthebrushblock(F1, F2),removethetwomountingscrewand
withdraw the brush block from m the generator end bell. . Replace the brush block k assembly y if
eitherbrush isshorterthan7/16 inch(11mm), binds inthebrush block or isdamagedinany
way.
Remove the brush blockand inspect theslip rings forgrooves, pits, or other damage. Use a
ScotchBritepadorcommutatorstonetoremovelightwearorcorrosion.
4.10 StatorService
Removal:
1. Removeroof,servicedoors,fingerguardsandpanelsasnecessary.
NOTICE
Thebackpanelmustberemovedtoremovethestator.
2. Removetheengine-generatorassembly.
3. Removethebrushblock.
CAUTION
Thebrushescanbedamagedifthebrushblockisnotremovedbeforeremovingtheend
bell.
4. Removethenutsandlockwashersonthefourstatorthroughstuds.
5. Removetheendbell.
6. Pullthestatorstraightoutandawayfromtheengine,leavingtherotorandthroughstudsin
place,takingcarenottodamagerotororstatorwindings.
Reassembly: Reassemblyis thereverse of removal.Re-lubricatethe bearingborein the end
bellwith molybdenum disulfide paste orequivalentand make surethe O-ringis placedin the
bearingbore.Torquethenutsonthethroughstudsto31ft-lbs(42N-m).
4.11 RotorService
Removal:
1. Removeroof,servicedoors,fingerguardsandpanelsasnecessary.
NOTICE
Thebackpanelmustberemovedtoremovetherotor.
A030A239(Issue10)
35
Adjust size of pdf file - Compress reduce PDF size in C#.net, ASP.NET, MVC, Ajax, WinForms, WPF
C# Code & .NET API to Compress & Decompress PDF Document
compress pdf; best pdf compressor online
Adjust size of pdf file - VB.NET PDF File Compress Library: Compress reduce PDF size in vb.net, ASP.NET, MVC, Ajax, WinForms, WPF
VB.NET PDF Document Compression and Decompression Control SDK
pdf markup text size; pdf change font size in textbox
4.Service
9-2013
2. Removethestatorandstatorthroughstuds.
3. Removethe e nut and flatwasheronthe rotorthroughstudand remove thethroughstud.
(Usetwonutslockedtogetherattheend of the rotorthroughstudtoloosen andremove
thestudfromthecrankshaft.)
4. Threadinarotorremovalrod(shortened d rotorthroughstud or 7/16-14 UNC-2Athreaded
rod)andturnitwithascrewdriveruntilitbottomsinthecrankshaft.Threadinandtightena
9/16-12UNC-2Bboltagainsttheroduntiltherotorbreaksloosefromthecrankshaft.
Reassembly:Reassemblyisthereverseofremoval.Torquethenutonthethroughstudto49
ft-lbs (67 7 N-m). . If f it is s necessary y to reinstall l the e engine-generator adaptor, , torque e the four
mountingboltsto49ft-lbs(67N-m).
4.12 TestingtheGenerator
RotorWindingContinuity: Test the rotorforgrounded, openandshortedwindings using an
ohmmeter. First test at thebrushblock terminals. If the resistance is high, remove thebrush
block andtestdirectlyontheslip rings.Replacethebrush block ifahighresistance isdueto
thebrushes.
RotorGroundResistance Test: Setthe ohmmeterto the highest resistancescale, or usea
megger.Touchonetestprobetotherotorshaftandtheothertooneofthesliprings.Referto
theRotorandStatorResistanceTeststableforresistancevaluesandanycorrectiveaction.
RotorWindingResistance:Touchtheslipringswiththemetertestprobes.RefertotheRotor
andStatorResistanceTeststableforresistancevaluesandanycorrectiveaction.
MainWindingtoQuadWinding:Testforshortbetweenmainwindingsandquadwindings.
StatorGroundResistanceTest:Set theohmmeter to thehighest resistancescale,orusea
megger.Settheohmmetertothehighestresistancescaleandthentouchonetestprobetothe
stackand,inturn,theothertoeachstatorlead.RefertotheRotorandStatorResistanceTests
tableformeasurementvalues.
Stator Winding Resistance: Use a meter r (Wheatstone Bridge) having a a precision down to
0.001 ohms to o measure e stator winding resistance values as shown n in n the Rotor and Stator
ResistanceTeststable.
Stator Winding for Grounds: With an ohmmeter, , measure e each winding to the stator
laminationstocheckforbadinsulation.RefertotheRotorandStatorResistanceTeststablefor
measurementvalues.
TABLE12. ROTORANDSTATORRESISTANCETESTS
Tests
MeasurementValues
RotorGroundResistance
Reading>1megohm(onemillionohms)onmegger,or
infinityonanohmmeter
RotorWindingResistanceF1toF2(at75°F-room
27.59ohms±10%.
temperature)
MainWindingtoQuadWinding
Open(infinity)foranywinding
StatorGroundResistance
Reading>1megohm(onemillionohms)onmegger,or
infinityonanohmmeter.
StatorWindingResistance(at75°F-roomtemperature):
L1toN
0.094ohms±10%
36
A030A239(Issue10)
VB.NET Image: How to Draw Annotation on Doc Images with Image SDK
like multi-page TIFF, Microsoft Office Word and PDF file). that, you are also able to adjust various image the annotation shapes, the outline size (width and
change font size in pdf comment box; can a pdf file be compressed
C# Image: Zoom Image and Document Page in C#.NET Web Viewer
jpeg), gif, bmp (bitmap), tiff / multi-page tiff, PDF, etc. APIs for Visual C# .NET developers to adjust the image & document page viewing size with this
pdf page size; pdf files optimized
9-2013
4.Service
Tests
MeasurementValues
L2toN
0.094ohms±10%
L1toL2
(EqualtosumofL1toNandL2toN)±1%
Q1toQ2
1.11ohms±10%
L1andNtoQ1andQ2
Infinity
L2andNtoQ1andQ2
Infinity
L1toGnd
Infinity
L2toGnd
Infinity
L1andNtolaminations
Infinity
L2andNtolaminations
Infinity
Q1-Q2tolaminations
Infinity
*Ifastatororrotorfailstheinitialtest,repeatthetesttocheckthevalidityoftheinitialmeasurementbeforereplacing
thestatorortherotor.
Thisgeneratorisratedinaccordancewith UL2200(StationaryEngineGeneratorAssemblies)
orCSA C22.2 No. . 100-04 (Motors andGenerators). The maximumcontinuous currentvalues
thatarelistedonthegeneratorsetnameplateandspecificationtablesoccuratthelowerlimitof
acceptablevoltage.Maximumcurrentoccursat108and216volts.Thevoltagesetpointofthis
generatorsetcanbeadjustedfromtheoperatorpanelifdesired.
Theoperatorpanelallowstheservicevoltagetobechangedto7.5%belowthenominal240volt
setpoint.Theentire10%voltageadjustmentisnotallowedbytheenduserinordertoensure
thattheutilizationvoltageisnottoolowattheenddevices.Additionalvoltagedropacrossthe
supplyconductorsmaycauserick ofdamageorimproperfunctionofthedevices ifthevoltage
atthegensetissettoolow.
DeratingGuidelines:Maximumwattageormaximumcurrentaresubjecttoandlimitedbysuch
factorsasfuelBtucontent,ambienttemperature,altitude,enginepowerandcondition,etc.Full
ratedpowerisavailableat60°F(15.5°C)atsealevel.Derate3.5%foreach1000ft(304.8m)
abovesealeveland3%foreach10°F(5.5°C)increaseinambienttemperatureabove60°F
(15.5°C).
ExampleDerateCalculation:
Customerlocationisat2000ft(xm)elevationandtheambientairtemperatureis90°F(x°C).
De-rateforElevation:
2000÷1000=2
2x3.5%=7%de-rateforelevation
De-rateforTemperature:
90°-60°=30°
30°÷10°=3
3x3%=9%de-ratefortemperature
TotalDe-rate:
9%+7%=16%totalde-rate%
Ampx(totalde-rate÷100)=de-rateinamps
73.2x(16÷100)=11.7amps
A030A239(Issue10)
37
VB.NET Image: VB.NET Code to Create Watermark on Images in .NET
font type "Times New Roman", size "16", and style "Bold"), and then adjust brush color provide powerful & profession imaging controls, PDF document, tiff
best way to compress pdf files; adjust size of pdf
C# PDF Convert: How to Convert Word, Excel, PowerPoint, Tiff
for image size. Able to adjust and customize image resolution to meet various C# PDF conversion requirements. Conversion from other files to PDF file can be
change page size pdf acrobat; reduce pdf file size
4.Service
9-2013
Expectedoutputwillbe73.2amp-11.7amp=61.5amp
Toverifygeneratorsetperformance:
1. Followde-rateguidelinesaboveanddetermine%reductioningeneratorsetoutputdueto
temperatureandelevation.Seeexamplecalculation.
2. While e the generator r set t is running, determine e the e output voltage at the customer
connectionblockTB2.
3. Usethetablebelowtofindtheexpectedcurrentvalueforthemeasuredvoltageandapply
thede-ratecalculatedinstep1.
4. MeasurecurrentatthecustomerconnectionwiresatTB2.
5. Turnonhouseholddevicesorincreasetheloadsettingoftheloadbankuntilthecurrentis
equaltothede-ratedcurrentcalculatedinstep3.Approximateloadbank settingrequired
to achieve the expected amperage output t can n be estimated by multiplying the expected
amperageoutputbythevoltagemeasuredinstep2.
TABLE13. EXPECTEDCURRENTVALUEFORMEASUREDVOLTAGE
GeneratorVoltageat
MinimumAmps
MinimumAmps
GeneratorVoltageat
MinimumAmps
TB2
AvailableBefore
AvailableBefore
TB2
AvailableBefore
DerateLP
DerateNG
DerateNG
252
69.7
61.5
241.5
55.9
249.6
70.4
62.1
239.2
56.4
247.2
71
62.7
236.9
57
244.8
71.7
63.4
234.6
57.5
242.4
72.4
64
232.3
58.1
240
73.2
64.6
230
58.7
237.6
73.9
65.3
227.7
59.3
235.2
74.7
65.9
225.4
59.9
232.8
75.4
66.6
223.1
60.5
230.4
76.2
67.3
220.8
61.1
228
77
68
218.5
61.8
225.6
77.8
68.7
216.2
62.4
223.2
78.7
69.5
213.9
63.1
*220.8
79.5
70.2
*211.6
63.8
*218.4
80.4
71
*209.3
64.5
*216
81.3
71.8
*207
65.2
*Thesevoltagesettingsarenotallowedbythegeneratorcontrol.
38
A030A239(Issue10)
C# PDF: Use C# APIs to Control Fully on PDF Rendering Process
0, 0, originalWidth, originalHeight), size); // adjust with a 0, originalWidth / 2, originalHeight), new Size(originalWidth / 2 tool to convert PDF document to
best online pdf compressor; change font size pdf
C# PowerPoint: How to Set PowerPoint Rendering Parameters in C#
this SDK to render PowerPoint (2007 or above) slide into PDF document or Generally, you are allowed to set image resolution, image size, batch conversion and
can a pdf be compressed; change font size pdf form
5
Operation
5.1
In-HomeOperatorPanel
Theoperatorpanelmustbehard-wiredtothegeneratorsetinorderforthegeneratorsystemto
operate.
NOTICE
Thein-homeoperatorpanelandInternet/Emailinterfacecanbeusedsimultaneously
The operatorpanelconsists of two UTILITYstatus s lamps, , three GENERATORstatus lamps,
threeactionbuttonsandanLCDdisplayscreenwithfournavigationbuttons.
No. Description
1
BackButton-WhennavigatingthroughtheLCDmenus,pressthisbuttontoreturntothemainoperating
screen.
2
StandbyOn/OffButton-SeetheToEnable/DisableStandbysectionofthismanual.
3
StartStopButton-SeetheToManuallyStart/StopGeneratorSetsectionofthismanual.
4
NavigationButtons-Thefunctionofthesebuttonschangeasdifferentscreensappear.
FIGURE11. IN-HOMEOPERATORPANEL
5.1.1 BACKButton
When navigating through the LCD menus, press the BACK button n to o return to the main
operatingscreen.
5.1.2 StandbyON/OFFButton
SeeToEnable/DisableStandby.
A030A239(Issue10)
39
View Images & Documents in Web Image Viewer | Online Tutorials
page document or image file, like Word, PDF or TIFF three different APIs for adjusting image viewing size. btnFitWidth API allows developers to adjust the width
change file size of pdf document; change file size of pdf
VB.NET Image: Image Resizer Control SDK to Resize Picture & Photo
VB.NET Code for Adjusting Image Size. In order to resizer control add-on, can I adjust the sizes of powerful & profession imaging controls, PDF document, image
change page size of pdf document; adjust pdf size preview
5.Operation
9-2013
5.1.3 STARTSTOPButton
SeeToManuallyStart/StopGeneratorSet.
5.2
TypicalOperation
NOTICE
ThefollowingdiagramsarebasedonanAPPROXIMATEtimeduration.Yourgensetmay
varyslightlyfromthetimingdiagramsinthismanual.
FIGURE12. TYPICALPOWEROUTAGECYCLETIMINGDIAGRAM
40
A030A239(Issue10)
C# Word: How to Draw Text, Line & Image in C#.NET Word Project
copy the sample codes below to adjust text properties such as image color, picture size, location of powerful & profession imaging controls, PDF document, image
acrobat compress pdf; best compression pdf
VB.NET Excel: VB Methods to Set and Customize Excel Rendering
on the fixed image size ration that the size is limited by Adjust Image Scaling Factor. supports converting Excel to other document files, like PDF with online
pdf font size change; change font size in pdf
9-2013
5.Operation
FIGURE13. EXERCISETIMINGDIAGRAM
A030A239(Issue10)
41
5.Operation
9-2013
FIGURE14. MANUALSTART/STOPTIMINGDIAGRAM
42
A030A239(Issue10)
9-2013
5.Operation
FIGURE15. LOADMANAGEMENTTIMINGDIAGRAM
5.2.1 NormalOperation:UtilityPowerAvailableandConnected
As long as utility y power r is available and connected, both of the green UTILITY Y lamps
(PRESENTandCONNECTED)willstayonandtheLCDscreenwillindicate“GensetStopped".
If the e red GENERATOR STANDBY Y OFF light is on, , the e generator set will not start up
automaticallyifutilitypowerisinterrupted.SeetheToEnable/DisableStandbysectionofthis
manualto enableSTANDBYsothatthegenerator set willautomaticallysupplypowerif utility
powerisinterrupted.
A030A239(Issue10)
43
5.Operation
9-2013
FIGURE16. UTILITYPRESENTANDCONNECTED—STANDBYOFFLAMPON
5.2.2 EmergencyOperation:UtilityPowerInterrupted
Ifutilitypowerisinterrupted,
1. ThegreenUTILITYPRESENTlampwillgoout
2. ThegeneratorsetwillstartautomaticallyandthegreenGENERATORRUNNINGlampwill
turnon.
3. TheUTILITYCONNECTEDlightwillgooutwhenthegeneratorsetisconnectedtosupply
power.
TheLCDscreenwillprovideavisualindicationof“GensetLoad"(bargraphs).Thebargraphs
indicatehowmuchoftheavailablepowerisbeingusedineachsupplyline(L1andL2).
If the e red d ACTION REQUIRED D light comes s on, either the generator shut down or periodic
maintenance has comedue.TheLCDscreen willindicatewhat maintenance is due orwhich
faultoccurred.
FIGURE17. GENERATORSETRUNNING—ACTIONREQUIREDLAMPON
44
A030A239(Issue10)