117
IEI Hub Manager Professional v8 
Chapter 6: Database
10.
Now click the Set the Above Security Key button to send the new Security
Key to the selected SEG.
11.
Setup is now complete.
Now that the MAC address is known by Hub Manager™ Professional, if the DHCP
server were to assign a new IP Address to this particular SEG, then the next time you
attempt to communicate with any of the controllers connected to this SEG, Hub
Manager™ Professional will retrieve the new IP Address from the SEG and
automatically save the new IP address into the Site Settings. This saves you the time
needed to reconfigure the IP Address in the Site settings screen.
6.4.5.2
Dynamic IP Address, non-expiring lease
No setup of the SEG via the serial port is required. Just supply the SEG's MAC address
(the 12 digit number located on the label on the SEG; for example 00-20-4A-52-F2-84) to
the IT department and ask them to assign it an IP Address with a non-expiring lease,
which is an IP address that will not change. Once you have the IP address that the IT
department assigned to the SEG, enter that IP address into the Site Settings screen and
save the site.
NOTE: Each SEG is shipped from the factory with an IP Address of 0.0.0.0. When the
SEG is initially powered up (or rebooted) and it has an IP address of all 0's, it will look
for a DHCP server on the network and if one is found the SEG is assigned an IP
Address.
6.4.5.3
Static IP Address
Setting a Static IP Address of a SEG through a serial connection (via
PC com port)
Use this method to configuring the SEG with a static IP address.
The following procedure requires a Terminal Emulation program. The instructions below
describe how to configure the SEG using PuTTY. To download PuTTY (putty.exe) go to
www.putty.org
NOTE: HyperTerminal is no longer supported by Hub Manager™
Professional.
To enter the configuration menu of the SEG, you must perform the following in order:
1.
Connect the DB9-RJ11 adapter labeled Gateway Config (supplied with the
SEG) to your PC COM port.
2.
Plug the 6' phone cord (supplied with the SEG) into the adapter labeled
Gateway Config. 
3.
When using a SEG-1, disconnect the SEG-1 from the LAN and controller and
Pdf change page size - Compress reduce PDF size in C#.net, ASP.NET, MVC, Ajax, WinForms, WPF
C# Code & .NET API to Compress & Decompress PDF Document
adjust size of pdf file; pdf change font size in textbox
Pdf change page size - VB.NET PDF File Compress Library: Compress reduce PDF size in vb.net, ASP.NET, MVC, Ajax, WinForms, WPF
VB.NET PDF Document Compression and Decompression Control SDK
best way to compress pdf files; 300 dpi pdf file size
118
IEI Hub Manager Professional v8 
Chapter 6: Database
bring it back to the PC, along with its power supply. Plug the other end of the 6'
phone cord into the port on the SEG-1 labeled RS232.
4.
When using the SEG-M you must leave it installed on the backplane. In this
case the PC (a laptop is recommended) must be close to the backplane so you
can plug the 6' phone cord into the RJ-11 jack labeled RJ11C on the Max
backplane.
5.
Run putty.exe (double-click on the exe file) to open PuTTY.
6.
When PuTTY opens, the Session options are opened by default. Select the
Serial option on the right, as shown below.
VB.NET Image: How to Create Visual Basic .NET Windows Image Viewer
formats, including png, jpeg, gif, tiff, bmp, PDF, and Word can get a basic idea of the page layout from from that, you are entitled to change the orientation
pdf compression; pdf markup text size
C# PDF insert text Library: insert text into PDF content in C#.net
formatted text and plain text to PDF page using .NET NET PDF edit control allows modify existing scanned PDF text. Ability to change text font, color, size and
change font size in fillable pdf form; acrobat compress pdf
119
IEI Hub Manager Professional v8 
Chapter 6: Database
7.
Next, select the Serial option at the bottom of the Category list, as shown
below. In the Select a serial line section select the COM port you are using. In
the Configure the serial line section use the following settings:
Speed (baud) = 9600
Data bits = 8
Stop Bits = 1
Parity = None
Flow Control = None
C# PDF Convert: How to Convert Word, Excel, PowerPoint, Tiff
Support conversion to PDF from other documents, keeping original document page size. Support rendering image to a PDF document page, no change for image size.
best pdf compressor; change file size of pdf document
C# PDF Annotate Library: Draw, edit PDF annotation, markups in C#.
Able to edit and change PDF annotation properties such as font size or color. Perform Various annotations on PDF Page using C#.NET Demo Codes.
adjust pdf page size; change paper size in pdf
120
IEI Hub Manager Professional v8 
Chapter 6: Database
8.
Now click Open at the bottom of the screen. A black screen should appear.
9.
Disconnect power to the SEG (if it was powered up).
10.
Press and hold down the x key (lowercase) on the PC keyboard while PuTTY
program is running.
11.
Power up the SEG.
12.
In a few seconds you should get a response from the SEG asking you to
press enter to go into Setup Mode, as shown below. You must press Enter
within in 5 seconds.
NOTE: If you do not press Enter within 5 seconds, you will not be allowed to
enter setup mode, and you will see ?!? displayed on the screen beneath
Press Enter for Setup Mode. If this happens you must close PuTTY and
repeat the  procedure starting at step 5.
13.
Release the x key.
C# PDF Thumbnail Create SDK: Draw thumbnail images for PDF in C#.
public override Bitmap ConvertToImage(Size targetSize). Description: Convert the PDF page to bitmap with specified size. Parameters:
adjusting page size in pdf; change paper size pdf
C# PDF File Split Library: Split, seperate PDF into multiple files
Divide PDF file into multiple files by outputting PDF file size. control, C# developers can easily and accurately disassemble multi-page PDF document into two
best pdf compressor online; pdf change font size
121
IEI Hub Manager Professional v8 
Chapter 6: Database
14.
After pressing Enter setup mode opens, which contains the settings and
menu system shown below.
VB.NET PDF File Split Library: Split, seperate PDF into multiple
Separate source PDF document file by defined page range in VB.NET class application. Divide PDF file into multiple files by outputting PDF file size.
change font size in pdf; pdf page size dimensions
Create Thumbnail Winforms | Online Tutorials
editor: Click "Add" to add new items in thumbnail; Click "Swap" to change two items Multi-page Tiff Processing; RasterEdge OCR Engine; PDF Reading; Encode &
can pdf files be compressed; pdf page size limit
122
IEI Hub Manager Professional v8 
Chapter 6: Database
15.
To change the IP Address select option 0 Server configuration by pressing 0
followed by the Enter key. A three-digit number, which is the first octet of the
current IP address, is displayed in brackets (this value is 000 by default). Enter
the first three digits of the IP Address then press Enter. You must enter the
value of all four octets of the IP Address. If any of the numbers are already set
correct, you can just press Enter to leave the value unchanged.
16.
Once you've finished entering the IP Address, press Enter through the
remaining options until the menu scrolls by automatically.
17.
From the main menu, select 9 save and exit by pressing 9 followed by the
Enter key.
18.
When you receive the Parameters stored ... message you can exit this utility
by clicking the red X in the upper right corner. Click Yes if you are prompted to
close the program.
NOTE: Do not change the default values in any other menu option. To leave
the default value, simply press the Enter key when that setting is displayed.
123
IEI Hub Manager Professional v8 
Chapter 6: Database
SEG Menu System
Below is a table showing the configurable options of the SEG's Setup Menu. 
Out-of-box Value: This column lists the out-of-box default values of each option. 
Can be modified by a Network Administrator: This column specifies which values can be
modified by a Network Administrator, as required by the network or to restrict the
configuration methods of the SEG thereby improving security. 
The SEG device is factory set to leave all the the configuration methods enabled in the
Security menu. After the SEG is initially setup and is communicating with  Hub
Manager™ Professional properly, it is recommended that your Network Administrator
disables the configuration methods in the security menu which they do not want to leave
open. 
Out-of-box Values in bold italics should always be set to the specified values for this
SEG to properly work with Hub Manager™ Professional. All other out-of-box values can be
changed as required by the Network Administrator. 
Menu Option
Option Name
Out-of-box
Values
Can be
modified by a
Network
Administrator
SEG
v1.32 (or
earlier)
SEG
v1.40
0 - Server
Configuration
IP address
0.0.0.0
0.0.0.0 for
DHCP  or    X.
X.X.X for static
*
Set Gateway
Address
N
Y (as required)
Netmask
0
X.X.X.X (as
required)
Change Telnet
config password
N
Y (for greater
security)
Change DHCP
Device Name
N
Y (as required)
*
1 - Channel 1
Configuration
Baud Rate
1200
*
*
I/F Mode
4C
*
*
Flow
00
*
*
Use UDP/TCP
TCP
*
124
IEI Hub Manager Professional v8 
Chapter 6: Database
Menu Option
Option Name
Out-of-box
Values
Can be
modified by a
Network
Administrator
SEG
v1.32 (or
earlier)
SEG
v1.40
Source Port
9997
XXXX (as
required)
*
*
Destination Port
0000
XXXX (as
required)
*
*
Destination IP
0.0.0.0
X.X.X.X (as
required)
*
*
2 - Channel 2
Configuration
Baud Rate
19200
*
*
I/F Mode
4C
*
*
Flow
00
*
*
6 - Security
Disable SMNP
N
Y (for greater
security)
*
SNMP Community
Name
public
Y (as required)
*
Disable Telnet
Setup
Y (for greater
security)
*
*
Disable TFTP
Firmware Update
N
Y (for greater
security)
*
*
Disable Port 77FEh
N
Y (for greater
security)
*
*
Disable Web Server
N
Y (for greater
security)
*
Disable Web Setup
N
Y (for greater
security)
*
*
Enable Encryption
Y
*
*
Change Key
N
Y (set to all 0's
to reset)
*
*
Disable ECHO
Ports
N
Y (as required)
*
Enable Enhanced
Password
N
Y (for greater
security)
*
·  Server Configuration
125
IEI Hub Manager Professional v8 
Chapter 6: Database
· IP Address : Allows you to set the IP address of the SEG directly. You can
set it to 0.0.0.0 to instruct the SEG to be served a dynamic IP address from
a DHCP server, or  you can set  it to a static address of X.X.X.X that the
Network Administrator has assigned to this specific network device. The IP
address should only be set to 0.0.0.0 if the DHCP server is assigning the
same IP address to this specific SEG device every time. There are several
ways to enforce that the same IP address is assigned to a specific network
device, and it is based upon the capabilities of the DHCP server on your
network.
· Set Gateway IP Address: This can be changed by the Network
administrator as required. The term 'Gateway' here refers to a network
router on the LAN that separates LAN segments, not the Secure Ethernet
Gateway (SEG) device you are configuring here. Do not enter the static
address assigned to this SEG in this field. 
· Netmask: This can be changed by the Network administrator as required.
· Change telnet config password: This can be changed by the Network
administrator as required to restrict access to the Telnet setup menu of this
SEG. 
· 1 Channel 1 Configuration (RS232 Port Settings)
· Baud Rate: Communications speed between the SEG and access control
equipment. This should always be set to 1200. 
· I/F mode: Communications protocol setting between the SEG and access
control equipment. This should always be set to 4C.
· Flow: Communications protocol setting between the SEG and access
control equipment. This should always be set to 0.
· Use TCP: Communications protocol setting between the PC and SEG. This
should always be set to TCP. 
· Source Port: This can be changed by the Network administrator as
required. If there is a need to change this, then make sure to change the
Port number on the sending side to match. 
· Destination Port: This can be changed by the Network administrator as
required.
· Destination IP: This can be changed by the Network administrator as
required.
· 2 Channel 2 Configuration (RS485 Port Settings)
· Baud Rate: Communications speed between the SEG and access control
equipment. This should always be set to 19200. 
· I/F mode: Communications speed between the SEG and access control
equipment. This should always be set to 4C. 
· Flow: Communications speed between the SEG and access control
equipment. This should always be set to 0.
126
IEI Hub Manager Professional v8 
Chapter 6: Database
· 6 Security : Here you can change the Encryption key to match the encryption
key Hub Manager™ Professional is using. This is normally not necessary
because Hub Manager™ Professional normally performs this function. After going
through this menu item completely, the encryption settings are automatically
saved and the session is closed.
· Disable Telnet setup : This setting defaults to the N (No) option. The Y
(Yes) option disables access to this Configuration Menu by Telnet (port
9999). It only allows access via the Web pages and the serial port of the
unit. 
· Disable TFTP firmware upgrade: This can be changed by the Network
administrator as required for greater security. 
· Disable port 77FE?: This can be changed by the Network administrator as
required for greater security.
· Disable Web Server?: This can be changed by the Network administrator as
required for greater security.The Y (Yes) option disables the use of the Web
page configuration tool that is built into this unit.
· Disable web setup?: This can be changed by the Network administrator as
required for greater security.
· Enable encryption?: Encryption must always be enabled, because all data
sent to the SEG is encrypted. Do not disable this option or
communications between Hub Manager™ Professional, the SEG, and the
access control hardware will fail.
· XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX Change key?  (N) This 128 bit
security key is changed via the Hub Manager™ Professional software. If
this security key does not match the key stored in the site settings in Hub
Manager™ Professional, then any communication attempts to your
controller hardware will fail.
· Disable ECHO Ports: This can be changed by the Network administrator as
required.
· Enable Enhanced Password: This setting defaults to the N (option), which
allows you to set a 4-character password that protects the Configuration
Menu via Telnet and Web pages. The Y (Yes) option allows you to set a 16
character password for protecting Telnet access.
· 7 Factory Defaults: WARNING: This option should be used with caution. This
option will reset all Server Configuration, Channel 1, Channel 2, and Security
options back to Lantronix factory defaults (and not IEI factory defaults). After
performing this function, you will not be able to communicate with the SEG from
Hub Manager™ Professional until you have visited each of the menus: Server
Configuration, Channel 1, Channel 2, and Security and set the values for each
option as specified in the SEG Menu Option table. The Factory Defaults option
also resets the Security Key in the SEG to all 0's, so be sure you change the
security key into the SEG, via the Site Settings screen in Hub Manager™
Professional before you attempt to send any data to the door controllers. This