CPU 1511-1 PN  
(6ES7511-1AK00-0AB0) 
___________________ 
___________________ 
___________________ 
___________________ 
___________ 
___________________ 
___________________ 
SIMATIC 
S7-1500 
CPU 1511-1 PN  
(6ES7511-1AK00-0AB0) 
Manual 
12/2014 
A5E31264526-AC 
Preface 
Documentation guide 
Product overview 
Connecting up 
Interrupts, error messages, 
diagnostics and system 
alarms 
Technical specifications 
Dimensional drawing 
C# PDF Page Delete Library: remove PDF pages in C#.net, ASP.NET
class applications to delete any unnecessary page from target existing PDF document file page, a series of pages, and random pages to be Add necessary references
add and delete pages in pdf; add page numbers pdf file
C# PDF insert image Library: insert images into PDF in C#.net, ASP
Add multiple images to multipage PDF document in .NET WinForms. Ability to put image into specified PDF page position and save existing PDF file or output a new
add pages to pdf reader; add pages to an existing pdf
Siemens AG 
Division Digital Factory 
Postfach 48 48 
90026 NÜRNBERG 
GERMANY 
A5E31264526-AC 
Ⓟ 12/2014 Subject to change 
Copyright © Siemens AG 2013 - 2014. 
All rights reserved 
Legal information 
Warning notice system 
This manual contains notices you have to observe in order to ensure your personal safety, as well as to prevent 
damage to property. The notices referring to your personal safety are highlighted in the manual by a safety alert 
symbol, notices referring only to property damage have no safety alert symbol. These notices shown below are 
graded according to the degree of danger. 
DANGER 
indicates that death or severe personal injury will result if proper precautions are not taken. 
WARNING 
indicates that death or severe personal injury may result if proper precautions are not taken. 
CAUTION 
indicates that minor personal injury can result if proper precautions are not taken. 
NOTICE 
indicates that property damage can result if proper precautions are not taken. 
If more than one degree of danger is present, the warning notice representing the highest degree of danger will 
be used. A notice warning of injury to persons with a safety alert symbol may also include a warning relating to 
property damage. 
Qualified Personnel 
The product/system described in this documentation may be operated only by personnel qualified for the specific 
task in accordance with the relevant documentation, in particular its warning notices and safety instructions. 
Qualified personnel are those who, based on their training and experience, are capable of identifying risks and 
avoiding potential hazards when working with these products/systems. 
Proper use of Siemens products 
Note the following: 
WARNING 
Siemens products may only be used for the applications described in the catalog and in the relevant technical 
documentation. If products and components from other manufacturers are used, these must be recommended 
or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and 
maintenance are required to ensure that the products operate safely and without any problems. The permissible 
ambient conditions must be complied with. The information in the relevant documentation must be observed. 
Trademarks 
All names identified by ® are registered trademarks of Siemens AG. The remaining trademarks in this publication 
may be trademarks whose use by third parties for their own purposes could violate the rights of the owner. 
Disclaimer of Liability 
We have reviewed the contents of this publication to ensure consistency with the hardware and software 
described. Since variance cannot be precluded entirely, we cannot guarantee full consistency. However, the 
information in this publication is reviewed regularly and any necessary corrections are included in subsequent 
editions. 
VB.NET PDF insert image library: insert images into PDF in vb.net
Add images to any selected PDF page in VB.NET. Ability to put image into defined location on PDF page. Save changes to existing PDF file or output a new PDF file
adding page numbers to a pdf in preview; add page number to pdf online
VB.NET PDF Page Delete Library: remove PDF pages in vb.net, ASP.
Page: Delete Existing PDF Pages. |. Home ›› XDoc.PDF ›› VB Enable specified pages deleting from PDF in Visual Basic .NET class. Add necessary references:
add a page to a pdf file; add contents page to pdf
CPU 1511-1 PN (6ES7511-1AK00-0AB0) 
4
Manual, 12/2014, A5E31264526-AC 
Preface 
Purpose of the documentation 
This manual supplements the system manual of the S7-1500 automation system and the 
function manuals. All cross-system functions are described in the system manual and in the 
function manuals. 
The information provided in this manual and the system manual allows you to commission 
the CPU 1511-1 PN. 
Conventions 
STEP 7: In this documentation, "STEP 7" is used as a synonym for all versions of the 
configuration and programming software "STEP 7 (TIA Portal)". 
Also read the notes labeled as follows: 
Note 
A note contains important information on the product described in the documentation, on the 
handling of the product or on the section of the documentation to which particular attention 
should be paid. 
Security information 
Siemens provides products and solutions with industrial security functions that support the 
secure operation of plants, solutions, machines, equipment and/or networks. They are 
important components in a holistic industrial security concept. With this in mind, Siemens’ 
products and solutions undergo continuous development. Siemens recommends strongly 
that you regularly check for product updates.  
For the secure operation of Siemens products and solutions, it is necessary to take suitable 
preventive action (e.g. cell protection concept) and integrate each component into a holistic, 
state-of-the-art industrial security concept. Third-party products that may be in use should 
also be considered. You can find more information about industrial security on the Internet 
(http://www.siemens.com/industrialsecurity). 
To stay informed about product updates as they occur, sign up for a product-specific 
newsletter. You can find more information on the Internet 
(http://support.automation.siemens.com). 
C# PDF File & Page Process Library SDK for C#.net, ASP.NET, MVC
Create Thumbnails. Page: Insert PDF Pages. Page: Delete Existing PDF Pages. Redact Text Content. Redact Images. Redact Pages. Annotation & Drawing. Add Sticky Note
add page pdf reader; add remove pages from pdf
VB.NET PDF Password Library: add, remove, edit PDF file password
VB: Add Password to PDF with Permission Settings Applied. This VB.NET example shows how to add PDF file password with access permission setting.
add page number to pdf preview; adding page numbers to a pdf file
CPU 1511-1 PN (6ES7511-1AK00-0AB0) 
Manual, 12/2014, A5E31264526-AC 
5
Table of contents 
Preface ................................................................................................................................................... 4 
Documentation guide .............................................................................................................................. 6 
Product overview .................................................................................................................................... 8 
2.1 
Application ................................ 8 
2.2 
How it works  
10 
2.3 
Properties ................................ 
11 
2.4 
Operating and display elements  
14 
2.4.1 
Front view of the module with closed front panel ................................................................... 14 
2.4.2 
Front view of the module without front panel  
16 
2.4.3 
Rear view of the module  
17 
2.5 
Mode selector switch  
17 
2.6 
Functions ................................ 
18 
2.6.1 
PROFINET IO  
18 
2.6.2 
PROFIenergy  
19 
2.6.3 
Memory reset  
19 
2.6.4 
Restoring the factory settings of the CPU 
21 
Connecting up ....................................................................................................................................... 24 
Interrupts, error messages, diagnostics and system alarms ................................................................... 28 
4.1 
Status and error display of the CPU  
28 
Technical specifications ........................................................................................................................ 31 
Dimensional drawing ............................................................................................................................. 40 
C# PDF Password Library: add, remove, edit PDF file password in C#
C# Sample Code: Add Password to PDF with Permission Settings Applied in C#.NET. This example shows how to add PDF file password with access permission setting.
add page numbers to a pdf document; add page numbers pdf files
C# PDF Page Rotate Library: rotate PDF page permanently in C#.net
page, it is also featured with the functions to merge PDF files using C# .NET, add new PDF page, delete certain PDF page, reorder existing PDF pages and split
add a page to a pdf in acrobat; adding page numbers to pdf document
CPU 1511-1 PN (6ES7511-1AK00-0AB0) 
6
Manual, 12/2014, A5E31264526-AC 
Documentation guide 
The documentation for the SIMATIC S7-1500 automation system and the SIMATIC 
ET 200MP distributed I/O system is arranged into three areas. 
This arrangement enables you to access the specific content you require. 
Basic information 
System Manual and Getting Started describe in detail the configuration, installation, wiring 
and commissioning of the SIMATIC S7-1500 and ET 200MP systems. The STEP 7 online 
help supports you in the configuration and programming. 
Device information 
Product manuals contain a compact description of the module-specific information, such as 
properties, terminal diagrams, characteristics and technical specifications. 
General information 
The function manuals contain detailed descriptions on general topics regarding the SIMATIC 
S7-1500 and ET 200MP systems, e.g. diagnostics, communication, Motion Control, Web 
server. 
You can download the documentation free of charge from the Internet 
(http://www.automation.siemens.com/mcms/industrial-automation-systems-
simatic/en/manual-overview/tech-doc-controllers/Pages/Default.aspx). 
Changes and supplements to the manuals are documented in a Product Information. 
Documentation guide 
CPU 1511-1 PN (6ES7511-1AK00-0AB0) 
Manual, 12/2014, A5E31264526-AC 
7
Manual Collection S7-1500/ET 200MP 
The Manual Collection contains the complete documentation on the SIMATIC S7-1500 
automation system and the ET 200MP distributed I/O system gathered together in one file. 
You can find the Manual Collection on the Internet 
(http://support.automation.siemens.com/WW/view/en/86140384). 
My Documentation Manager 
The My Documentation Manager is used to combine entire manuals or only parts of these to 
your own manual. 
You can export the manual as PDF file or in a format that can be edited later. 
You can find the My Documentation Manager on the Internet 
(http://support.automation.siemens.com/WW/view/en/38715968). 
Applications & Tools 
Applications & Tools supports you with various tools and examples for solving your 
automation tasks. Solutions are shown in interplay with multiple components in the system - 
separated from the focus in individual products. 
You can find Applications & Tools on the Internet 
(http://support.automation.siemens.com/WW/view/en/20208582). 
CAx Download Manager 
The CAx Download Manager is used to access the current product data for your CAx or CAe 
systems. 
You configure your own download package with a few clicks. 
In doing so you can select: 
● Product images, 2D dimension drawings, 3D models, internal circuit diagrams, EPLAN 
macro files 
● Manuals, characteristics, operating manuals, certificates 
● Product master data 
You can find the CAx Download Manager on the Internet 
(http://support.automation.siemens.com/WW/view/en/42455541). 
TIA Selection Tool 
With the TIA Selection Tool, you can select, configure and order devices for Totally 
Integrated Automation (TIA). 
This tool is the successor of the SIMATIC Selection Tool and combines the known 
configurators for automation technology into one tool. 
With the TIA Selection Tool, you can generate a complete order list from your product 
selection or product configuration. 
You can find the TIA Selection Tool on the Internet 
(http://w3.siemens.com/mcms/topics/en/simatic/tia-selection-tool). 
CPU 1511-1 PN (6ES7511-1AK00-0AB0) 
8
Manual, 12/2014, A5E31264526-AC 
Product overview 
2.1 
Application 
The CPUs of the SIMATIC S7-1500 controller family offer best possible performance 
combined with excellent usability. With their integrated PROFINET/PROFIBUS interfaces, 
the Web server and integrated functionalities, such as Motion Control, PID controller and 
temperature controller, trace support, the CPUs are predestined for numerous applications in 
automation engineering. 
Performance segments 
The CPUs can be used for smaller and mid-range applications, as well as for the high-end 
area of machine and plant automation.  
CPU 
Performance segment 
PROFIBUS  
interfaces 
PROFINET  
interfaces 
Work 
memory 
Processing 
time for bit 
operations 
CPU 1511-1 PN 
Standard CPU for smaller to mid-range  
applications 
-- 
1.15 MB 
60 ns 
CPU 1511F-1 PN 
Fail-safe CPU for smaller to mid-range 
applications 
-- 
1.23 MB 
60 ns 
CPU 1513-1 PN 
Standard CPU for mid-range applications 
-- 
1.8 MB 
40 ns 
CPU 1513F-1 PN 
Fail-safe CPU for mid-range applications 
-- 
1.95 MB 
40 ns 
CPU 1515-2 PN 
Standard CPU for mid-range to large 
applications 
-- 
3.5 MB 
30 ns 
CPU 1515F-2 PN 
Fail-safe CPU for mid-range to large 
applications 
-- 
3.75 MB 
30 ns 
CPU 1516-3 PN/DP 
Standard CPU for high-end applications 
and communication tasks 
6 MB 
10 ns 
CPU 1516F-3 PN/DP Fail-safe CPU for high-end applications 
and communication tasks 
6.5 MB 
10 ns 
CPU 1517-3 PN/DP 
Standard CPU for demanding  
applications and communication tasks 
10 MB 
2 ns 
CPU 1517F-3 PN/DP Fail-safe CPU for demanding  
applications and communication tasks 
11 MB 
2 ns 
CPU 1518-4 PN/DP 
Standard CPU for high-performance 
applications, demanding communication 
tasks and very short reaction times 
24 MB 
1 ns 
CPU 1518F-4 PN/DP Fail-safe CPU for high-performance  
applications, demanding communication 
tasks and very short reaction times 
26 MB 
1 ns 
Product overview 
2.1 Application 
CPU 1511-1 PN (6ES7511-1AK00-0AB0) 
Manual, 12/2014, A5E31264526-AC 
9
Integrated technology functions 
The CPUs of the SIMATIC S7-1500 family support Motion Control functions. STEP 7 offers 
PLCopen standardized blocks for configuring and connecting a drive to the CPU. Motion 
Control supports speed, positioning and synchronous axes, as well as external encoders. 
For effective commissioning, diagnostics and fast optimization of drives and controls, the 
SIMATIC S7-1500 controller family offers extensive trace functions for all CPU tags. 
In addition to drive integration, the SIMATIC S7-1500 has extensive control functionalities, 
such as easy-to-configure blocks for automatic optimization of the controller parameters for 
optimized control quality. 
Technology modules also implement functions such as high-speed counting, position 
detection and measuring functions for 24 V signals up to 200 kHz.  
Due to the integrated technology function, the CPUs are suitable, for example, for pumps, 
fans, mixers, conveyor belts, lifting platforms, gate control systems, building management 
systems, synchronized axes, cross cutters, etc. 
Security Integrated 
The CPUs are aimed at users that require the maximum possible plant security. 
In combination with STEP 7, each CPU offers password-based know-how protection against 
unauthorized reading or modifying of the program blocks. 
The copy protection provides high-performance protection against unauthorized reproduction 
of program blocks. The copy protection can be used to link individual blocks on the SIMATIC 
memory card with their serial numbers. The block can only be executed if the configured 
memory card is inserted in the CPU. 
In addition, four different authorization levels in the CPUs can be used to assign different 
access right to various user groups. 
Improved manipulation protection allows the CPUs to detect changed or unauthorized 
transfers of the engineering data. 
Safety Integrated 
The fail-safe CPUs are aimed at users that want to implement demanding standard and  
fail-safe applications in both a centralized and a distributed manner. 
These fail-safe CPUs allow the processing of standard and safety programs on a single 
CPU. This allows fail-safe data to be evaluated in the standard user program. This 
integration thus provides the system advantages and the extensive functionality of SIMATIC 
also for fail-safe applications. 
The fail-safe CPUs are certified for use in safety mode up to: 
● Safety class (Safety Integrity Level) SIL 3 according to IEC 61508:2010 
● Performance Level (PL) e and Category 4 according to ISO 13849-1:2006 or according to 
EN ISO 13849-1:2008 
Additional password protection for F-configuration and F-program is set up for IT security.  
Product overview 
2.2 How it works 
CPU 1511-1 PN (6ES7511-1AK00-0AB0) 
10
Manual, 12/2014, A5E31264526-AC 
Design and handling 
The design and handling of the CPUs is very straightforward and offers the greatest possible 
user friendliness. All CPUs have a display. The display provides information on order 
numbers, firmware version and serial numbers of all connected modules. The IP address of 
the CPU and other network settings can be set directly on site, without a programming 
device. The display shows occurring errors messages directly as plain text multi-lingual 
messages and helps you to reduce downtimes.  
System diagnostics 
Integrated system diagnostics is activated by default for the CPUs. The different diagnostic 
types are configured instead of programmed. System diagnostics information is shown 
uniformly and in plain text on the display of the CPU, in STEP 7, on the HMI and on the Web 
server, even for alarms related to drives. This information is available in RUN mode, but also 
in STOP mode of the CPU. An automatic update of the diagnostics information is performed 
when you configure new hardware components. 
2.2 
How it works 
The CPU contains the operating system and executes the user program. The user program 
is located on the SIMATIC memory card and is processed in the work memory of the CPU. 
The PROFINET interfaces on the CPU allow simultaneous communication with PROFINET 
devices, PROFINET controllers, HMI devices, programming devices, other controllers and 
other systems. CPU 1511-1 PN supports operation as an IO controller and I-device. 
IO controller 
As an IO controller, CPU 1511-1 PN sends and receives data and signals from the 
connected IO devices within a PROFINET IO system. You can operate the CPU with a 
maximum of 128 IO devices, of which a maximum of 64 may be IRT (Isochronous Realtime) 
devices. 
I-device 
In the "I-device" (intelligent IO device) function, CPU 1511-1 PN not only controls its own 
central modules, but also acts as an I-device, exchanging data with a higher-level IO 
controller. CPU 1511-1 PN thus fulfills the role of an intelligent pre-processing unit for sub-
processes. 
Documents you may be interested