c# code to view pdf file : Add page to pdf online Library software component asp.net winforms html mvc PTW_V6.5_Tutorial26-part277

261 
SKM Power*Tools for Windows 
Setting up a Reliability Study 
After defining the reliability data for each of the components in the component editor, the 
next step is to setup a reliability study.  Start the Reliability Analysis module by selecting 
the Reliability Analysis from the Run menu, or by pressing the toolbar icon. 
Once you start the Reliability Analysis module, the following study manager appears with a 
default study named “Study1”.  You can rename it to  a more descriptive name.   
Selecting each different folder/icon on the left hand side will bring up its corresponding 
context on the right hand side.  For example, selecting the root of the tree will show a list 
all major aspects of study results for all studies in this project, selecting the Study folder 
will show major results in the current study only, selecting Reliability Analysis under the 
study will lists all reliability related indices, and selecting Cost Evaluation under the study 
will lists all cost related evaluation results.  Since we haven’t run the study yet, there are no 
results listed under the Load Point Indices Results or IEEE Indices Results folders.  
Add page to pdf online - insert pages into PDF file in C#.net, ASP.NET, MVC, Ajax, WinForms, WPF
Guide C# Users to Insert (Empty) PDF Page or Pages from a Supported File Format
add a page to a pdf in acrobat; add contents page to pdf
Add page to pdf online - VB.NET PDF Page Insert Library: insert pages into PDF file in vb.net, ASP.NET, MVC, Ajax, WinForms, WPF
Easy to Use VB.NET APIs to Add a New Blank Page to PDF Document
add and delete pages in pdf; adding page numbers to pdf in
Reliability Study Setup 
The reliability study setup contains the following study parameters: 
o Disconnect Switches 
Disconnect switches allows restoration of all load points between the supply point 
and the point of isolation before the repair process has been completed.  The 
option assumes that you have a disconnect switch that can isolate each problem 
area and can re-energize the unaffected areas.  Additional control can be achieved 
by setting the repair and switching times appropriately for each branch. 
o Include Load Reliability 
If Include Load Reliability is checked, the reliability analysis will include failure 
rate and restoration time of all loads and motors in the Load Point Indices 
calculations.   
o Replace or Repair Transformers 
Corresponding replace or repair time entered from the component editor will be 
used in the calculations.  This is a global setting for all transformers in the project 
for the current study.  If you would like to set a few transformers to use the replace 
time while all other transformers are using the repair time as set in the global 
setting, you will need to select them in the Custom Setting Components list and 
make changes from there. 
o Fuse Settings 
Fuses allow disconnection of its load point until the failure is repaired.  Thus will 
not affect or cause the disconnection of any other load point.  The Failure 
Probability of fuse is the chance of fuse not being able to operate successfully.  If 
the failure probability is 0.1, the fuses operates successfully 9 out of 10 times 
when required.  The Isolation Time of fuse is the time it takes for all failures to be 
isolated. 
VB.NET PDF insert image library: insert images into PDF in vb.net
Access to freeware download and online VB.NET to provide users the most individualized PDF page image inserting function, allowing developers to add and insert
adding page numbers to a pdf document; add document to pdf pages
C# PDF File & Page Process Library SDK for C#.net, ASP.NET, MVC
C# File: Split PDF; C# Page: Insert PDF pages; C# Page: Delete PDF pages; C# C# Read: PDF Image Extract; C# Write: Insert text into PDF; C# Write: Add Image to
add a page to pdf file; adding page numbers to a pdf file
263 
SKM Power*Tools for Windows 
o Alternative Supply 
In the event of a system failure, the normally open tie-breaker can be closed in 
order to recover loads that have been disconnected. 
o Transfer Load Probability 
It is not always feasible to transfer all loads that are lost in a distribution system 
onto another feeder through a normally open point.  All loads that are lost will be 
transferred if the probability is 1.0.  The Transfer Load Probability is active only 
when the Alternative Supply option is selected. 
o Age Factor 
The Customer Reliability Data library allows you to enter the historical data for 
failure rate and restoration time for each year in the past.  A curve fitting program 
is used to define a mathematical representation for failure rate and restoration time 
as a function relative to the year installed.  If the Include Age Multiplying Factor is 
checked, the Evaluation Year field can be entered  
and the Reliability Analysis program will use the evaluation year and year installed 
to adjust the failure rates and repair times.  See Reliability Data Library for more 
information. 
o Evaluation Year 
Enter a current or future year you want to calculate reliability and related costs.  
VB.NET PDF Password Library: add, remove, edit PDF file password
On this page, we will illustrate how to protect PDF document via password by using simple VB.NET demo code. Open password protected PDF. Add password to PDF.
add page numbers to pdf in reader; adding page numbers to a pdf in preview
C# PDF insert image Library: insert images into PDF in C#.net, ASP
download and online C#.NET class source code. How to insert and add image, picture, digital photo, scanned signature or logo into PDF document page in C#.NET
adding a page to a pdf document; add multi page pdf to word document
Custom Setting Components 
The Study setup parameters apply to all components in the project for the particular study.  
If you have parameters that need to be specified at the component level, you can use the 
“Select Components” menu to add these components to  the “Custom Setting Components” 
list, and change the settings individually.  For example, repair times are used by default for 
all loads and motors.  But you can select LOAD-0001 and change it to use the replace time 
instead.  
VB.NET PDF Page Delete Library: remove PDF pages in vb.net, ASP.
Please follow the sections below to learn more. DLLs for Deleting Page from PDF Document in VB.NET Class. Add necessary references:
add page to pdf online; add page number to pdf preview
VB.NET PDF- View PDF Online with VB.NET HTML5 PDF Viewer
C# File: Split PDF; C# Page: Insert PDF pages; C# Page: Delete PDF pages; C# C# Read: PDF Image Extract; C# Write: Insert text into PDF; C# Write: Add Image to
adding page numbers pdf; adding page numbers to pdf in reader
265 
SKM Power*Tools for Windows 
Running a Reliability Study 
Once the study setup parameters are set and the custom setting components are selected and 
settings are set, you are ready to select the “Run” ”  button to run the study. 
To run a study, select any folder under the study name you would like to analyze and 
simply press the “Run” button on the bottom left co o rner of the reliability study tree.  
Alternatively, you can select “Run Study” under the  Reliability menu or the right mouse 
menu.   
The load point indices and IEEE indices will be calculated and the study progress/log 
report will be listed under the study setup output window.  Any input data errors and 
warnings will be reported in this window for your review.  It is highly recommended that 
you resolve all errors and understand all warnings before proceeding to the indice results. 
Running All Studies 
If you made changes on the study setup parameters or custom component settings within 
each study, it may be useful to setup a few different studies for comparison and run them in 
one action.  To run all studies in the project, select the root of the reliability study manager 
tree and simply press the “Run” button on the botto o m left corner, or select the “Run Study” 
menu option.   
If you make change on the system topology from the one-line or change data from the 
component editor from one study to another, then you are using different studies just to 
keep track of output results.  In this case, you should run each study right after the changes 
are made and do not run all studies in one action. 
C# HTML5 PDF Viewer SDK to view PDF document online in C#.NET
C# File: Split PDF; C# Page: Insert PDF pages; C# Page: Delete PDF pages; C# C# Read: PDF Image Extract; C# Write: Insert text into PDF; C# Write: Add Image to
adding pages to a pdf document in preview; add page to pdf in preview
C# PDF Password Library: add, remove, edit PDF file password in C#
your PDF document in C# project, XDoc.PDF provides some PDF security settings. On this page, we will talk about how to achieve this via Add necessary references
adding a page to a pdf in preview; add page numbers to pdf in preview
Load Point Reliability Indices 
The Load Point Reliability includes the following indices for each load and motor in the 
system.  Definitions for the indices follow.   Most of them come from the IEEE Standard 
493-1997 Gold Book - “Design of Reliable Industrial and Commercial Power Systems”: 
o MTBF  
The mean exposure time between consecutive failures of a 
component.  It can be estimated by dividing the exposure time by the number of 
failures in that period, provided that a sufficient number of failures have occurred 
in that period.  MTBF = MTTF + MTTR 
o Failure Rate 
The mean number of failures of a component per unit exposure 
time.  Usually exposure time is expressed in years and failure rate is given in 
failures per year. 
o MTTF  
Mean time to failure (1/ λ), or years per failure 
o Annual Outage Time: Total hours per year when a component or system is not 
available to properly perform its intended function due to some event directly 
associated with that component or system. 
o MTTR  
The mean-time to repair or replace a failed component.  It can 
be estimated by dividing the summation of repair times by the number of repairs, 
and, therefore, it is practically the average repair time. 
o Availability 
The long-term average fraction of time that a component or 
system is in service and satisfactorily performing its intended function. 
o Annual Availability% 
(1 - Annual Outage Time / 8760) * 100, 8760 I the total 
hours per year. 
o EENS  
Expected energy (kWh) not supplied per year. 
o ECOST  
Total damage cost in thousands of dollars (k$) per year due to 
failures.  
c(r): cost which depending on the outage time ($/kW), this can be obtained from 
Customer damage function (CDF) of each load. 
267 
SKM Power*Tools for Windows 
IEEE Reliability Indices 
The IEEE Reliability Indices include the following indices for each protective device in the 
system.   
System Average Interruption Frequency Index, SAIFI (interruptions/customer-yr.) 
where l
i
is the failure rate and N
is the number of customers of load point i. 
o System Average Interruption Duration Index, SAIDI (hours/customer-yr.) 
where U
i
is the annual outage time and N
is the number of customers of load point 
i. 
o Customer Average Interruption Frequency Index, CAIDI (hours/customer-
interruption) 
o Average Service Availability Index, ASAI 
o Average Service Unavailability Index, ASUI 
o Expected Energy Not Supplied Index, ENS (kWh/yr.) 
where L
a (i)
is the average load connected to load point i. 
o Average Energy not Supplied, AENS (kWh/customer-yr.) 
where L
a(i)
is the average load connected to load point i. 
c(r): cost which depending on the outage time ($/kW), this can be obtained from 
Customer damage function(CDF) of each load. 
269 
SKM Power*Tools for Windows 
Utility System Evaluation 
The economic analysis for cost-reliability evaluation cannot be considered in a general 
sense.  Most of the reasons and justifications are managerial decisions that can only be 
made based on your business goals.  However, the reliability analysis conducted in Part 3 
and Part 4 should provide you with one of the most important input parameters in your 
decision making process.  The basis for the method used in the program for utility and 
distribution system evaluation comes from IEEE paper No. PCIC 2000-02 “Improvements 
in Modeling and Evaluation of Electrical Power System Reliability” by John E. Propst and 
Daniel R. Doan.  Combining the reliability indices with these system evaluation methods 
bring reliability and cost considerations together in an easy to manage, scenario-based tool 
to help you make decisions effectively. 
Utility System Configurations 
Selecting the “Utility System Installed Cost” under  the “Cost Evaluation” folder will bring 
up the following dialog for you to select a utility system configuration.  There are 7 choices 
ranging from the simplest (least expensive, and least reliable) Single Source, Single 
Transformer, to the most complex (most expensive, and most reliable) Dual Source, Dual 
Transformer with Ring Bus configuration.  As you select a different configuration, a sample 
one-line next to the selection will show its basic design. 
Refer to John E. Propst and Daniel R. Doan’s paper for more detail on the cost-reliability 
trade-off for these configurations. 
Utility System Installed Cost - Single Source, Single Transformer 
Select single source, single transformer, and the program will fill in the equipment required 
for this configuration, the cost for each piece of equipment, and the total cost for the utility 
portion of the system. 
Customize the a Default Configuration 
You can customize what’s in each default configuration by entering new equipment with the 
cost and number of each.  Once you choose “Save As Template”, the list will be saved as 
the new default.   The next time you choose the same configuration, you will see your 
customized equipment list and pricing for the utility portion of the system.
Documents you may be interested
Documents you may be interested