c# open pdf adobe reader : Delete pages from pdf in preview control Library platform web page .net asp.net web browser TI33K01A12-50E1-part1406

2.  Hardware
2-3
TI 33K01A12-50E
Sep. 1, 2011-00
 Field Control Unit (FCU)
FCU consists of cards and modules executing control computation for FCS.
 FCU Configuration of KFCS and KFCS2
For duplexed FCU, mount two processor cards, power units, battery units, and ESB bus master 
interface cards.
Power unit
ESB bus master interface card
Processor card
Power distribution unit
V net coupler unit
Battery unit
External interface unit
Power input terminal
Air filter
Fan unit
Battery unit
ESB bus coupler unit
F020102E.ai
REVISION
U
H1
H2
M OD EL
A IP5 3 2
S TY LE 1 
 SI
YO
KO
GA
WA
ESB Bus
CN1
RCV
SND-L
SND-R
REVISION
U
H1
H2
MO D EL
A IP5 32
S TY LE 1  
SI
YO
KO
GA
WA
ESB Bus
CN1
RCV
SND-L
SND-R
Figure  Duplexed FCU Configuration (KFCS, KFCS2)
 FCU Configuration of FFCS
For duplexed FCU, mount two processor modules and power modules. You can also mount I/O 
modules. For adding node units, mount a bus interface module in an I/O module slot.
F020103E.ai
Processor module
External interface unit
I/O module
Utility unit
Base unit
Cable tray
CN2
(CPU-L)
CN3
(CPU-R)
CN1
ENBL
DSBL
CN2
(CPU-L)
CN3
(CPU-R)
TM1
READY
FUSE RL1 
CN1
ENBL
DSBL
CN1 (PSU-L)
CN2 (PSU-R)
V net coupler unit
Power module
Figure  Duplexed FCU Configuration (FFCS) 
Delete pages from pdf in preview - remove PDF pages in C#.net, ASP.NET, MVC, Ajax, WinForms, WPF
Provides Users with Mature Document Manipulating Function for Deleting PDF Pages
delete pages from a pdf file; delete pages from pdf acrobat reader
Delete pages from pdf in preview - VB.NET PDF Page Delete Library: remove PDF pages in vb.net, ASP.NET, MVC, Ajax, WinForms, WPF
Visual Basic Sample Codes to Delete PDF Document Page in .NET
add and delete pages in pdf online; delete pages in pdf
2.  Hardware
2-4
TI 33K01A12-50E
Sep. 1, 2011-00
 Node Unit (NU)
Node unit (NU) is a signal processing unit converting and transmitting analog or digital process 
I/O signals received from field devices to the FCU.
Node unit (NU) includes ESB bus node unit (local node) mounted in FCS station and ER 
bus node unit (remote node) mounted in cabinets or panels close to plant-site. Node unit is 
composed of ESB bus slave interface module or ER bus slave interface module, I/O module, and 
power supply module. 
•  ESB Bus Slave Interface Module 
ESB bus slave interface module is a communication module available for dual-redundancy 
enabling the communication between local nodes and FCU. 
•  ER Bus Interface Module 
ER Bus Interface module is a communication module available for dual-redundancy 
enabling the communication between local nodes and remote nodes.  ER Bus Interface 
module includes Interface slave mounted in local nodes or FCU, and Interface Slave 
module mounted in remote nodes. Both modules can be dual-redundant.
•  I/O Module 
I/O Module serves for input, convert, and output of analog or digital field signals.
I/O Module
Cable tray
ESB bus interface module
Power module
F020104E.ai
Figure  Local Node Configuration
How to C#: Preview Document Content Using XDoc.Word
How to C#: Preview Document Content Using XDoc.Word. Get Preview From File. You may get document preview image from an existing Word file in C#.net.
delete page on pdf document; pdf delete page
How to C#: Preview Document Content Using XDoc.PowerPoint
How to C#: Preview Document Content Using XDoc.PowerPoint. Get Preview From File. You may get document preview image from an existing PowerPoint file in C#.net.
delete pages pdf; delete a page from a pdf online
2.  Hardware
2-5
TI 33K01A12-50E
Sep. 1, 2011-00
 ESB Bus and ER Bus
ESB bus (Extended Serial Backboard bus) is a communication bus available for dual-
redundancy connecting ESB bus node units and FCU. ER bus (Enhanced Remote bus) is a 
high-speed communication bus available for dual-redundancy connecting ESB bus node units 
and ER bus node units (*1). Using ER bus, node units can be located away from FCU cabinet as 
well as in the cabinet. This availability for ER bus node units serves for the cases such as locating 
node units close to field devices, limiting power supply capacity for safety, or locating node units 
separately due to space issues. For ER bus, use Ethernet-compatible coaxial cable.  Using 
optical cables or general-purpose optical repeaters, transmission distance can be extended.  
Furthermore, node units can be located separately in wide area via wireless network or public 
network.
*1: 
The compact FCS for FIO is able to connect a FCU and a ER bus node unit.
Central instrument room
ER bus
ESB bus
Optical bus repeater
FCU
F020105E.ai
ESB bus node unit
ER bus node unit
ER bus node unit
Figure  Example of Distributed Node Units
VB.NET PDF File Compress Library: Compress reduce PDF size in vb.
a preview component enables compressing and decompressing in preview in ASP images size reducing can help to reduce PDF file size Delete unimportant contents:
delete page pdf; delete page in pdf online
C# WinForms Viewer: Load, View, Convert, Annotate and Edit PDF
Erase PDF images. • Erase PDF pages. Miscellaneous. • Select PDF text on viewer. • Search PDF text in preview. • View PDF outlines. Related Resources.
delete page from pdf file online; delete a page from a pdf in preview
2.  Hardware
2-6
TI 33K01A12-50E
 Optical ESB Bus
An optical ESB bus enables to transmit the conventional ESB bus signal for a long distance 
by using an optical fiber cable and an optical ESB bus repeater module. Connection types are 
selectable from chain and star topologies to extend the ESB bus transmittal distance up to 50 
Km. An optical ESB bus is only applicable to use with FFCS-V.
 Example of Chain Type Connection
F020106E.ai
: Fiber-optic cable
Max. length of
Fiber-optic cable 5 km
ANT401: option code “/CU1T”
ANT512: option code “/HU1B”
ANT411: option code “/CU1T”
ANT502: option code “/HU1A”
Max. length of
Fiber-optic cable 50 km
Total Max. length of
Fiber-optic cable 50 km
ANB11
ANB11
AFV30/AFV40 
I
O
M
I
O
M
I
O
M
I
O
M
I
O
M
I
O
M
I
O
M
I
O
M
P
S
U
P
S
U
I
O
M
I
O
M
I
O
M
I
O
M
I
O
M
I
O
M
P
S
U
P
S
U
I
O
M
I
O
M
I
O
M
I
O
M
A
N
T
4
0
1
A
N
T
4
1
1
A
N
T
4
1
1
A
N
T
5
0
2
A
N
T
5
0
2
A
N
T
5
1
2
A
N
T
5
1
2
A
N
T
4
0
1
E
C
4
0
1
E
C
4
0
1
P
S
U
P
S
U
C
P
4
6
1
C
P
4
6
1
HKU
HKU
HKU
UTILITY UNIT
Figure  Example of Chain Connection Using HK Function
Sep. 1, 2011-00
C# PDF Page Insert Library: insert pages into PDF file in C#.net
document files by C# code, how to rotate PDF document page, how to delete PDF page using C# .NET, how to reorganize PDF document pages and how
delete pages from pdf reader; delete page on pdf reader
How to C#: Preview Document Content Using XDoc.excel
How to C#: Preview Document Content Using XDoc.Excel. Get Preview From File. You may get document preview image from an existing Excel file in C#.net.
delete pages pdf online; delete a page from a pdf acrobat
2.  Hardware
2-7
TI 33K01A12-50E
Sep. 1, 2011-00
 Example of Star Type Connection
F020107E.ai
: Fiber-optic cable
ESB bus cable
Max. length: 10 m
ESB bus cable
Max. length: 10 m
ANT401(B1, 2)  : option code “/CU1T”
ANT411(IO7, 8) : option code “/CU1N”
ANT401(IO5, 6) : option code “/CU1N” 
ANT512: option code “/HU1B”
ANT502: option code “/HU1A”
SB401: option code “/CU2T”
AFV30/AFV40
Max. length of
Fiber-optic cable 5 km
Max. length of
Fiber-optic cable 50 km
I
O
M
I
O
M
I
O
M
I
O
M
I
O
M
I
O
M
P
S
U
P
S
U
E
C
4
0
1
E
C
4
0
1
C
P
4
6
1
C
P
4
6
1
ANT10U
P
S
U
P
S
U
A
N
T
4
1
1
A
N
T
4
1
1
A
N
T
4
0
1
A
N
T
4
0
1
ANB11
I
O
M
I
O
M
I
O
M
I
O
M
I
O
M
I
O
M
I
O
M
I
O
M
P
S
U
P
S
U
A
N
T
5
1
2
A
N
T
5
1
2
ANB11
I
O
M
I
O
M
I
O
M
I
O
M
I
O
M
I
O
M
I
O
M
I
O
M
P
S
U
P
S
U
A
N
T
5
0
2
A
N
T
5
0
2
ANB10
I
O
M
I
O
M
I
O
M
I
O
M
I
O
M
I
O
M
I
O
M
I
O
M
P
S
U
P
S
U
S
B
4
0
1
S
B
4
0
1
A
N
T
4
0
1
A
N
T
4
0
1
UTILITY UNIT
HKU
HKU
HKU
Figure  Example of Star Connection Using HK Function
VB.NET PDF delete text library: delete, remove text from PDF file
Visual Studio .NET application. Delete text from PDF file in preview without adobe PDF reader component installed. Able to pull text
delete pages from pdf document; copy pages from pdf to another pdf
C# Word - Delete Word Document Page in C#.NET
doc.Save(outPutFilePath); Delete Consecutive Pages from Word in C#. int[] detelePageindexes = new int[] { 1, 3, 5, 7, 9 }; // Delete pages.
delete pdf pages in preview; delete page from pdf document
2.  Hardware
2-8
TI 33K01A12-50E
 House Keeping Unit (HKU)
CENTUM VP FCS is equipped with a house keeping function that is to monitor the environment 
in the cabinet where FCS is mounted or the status of FCS itself. The FCS’s reliability is improved 
by this house keeping function. Taking an example of FFCS-V, details of the house keeping unit 
(HKU) are described here.
HKU hardware is composed of HKU, DPU, fan power supply unit, node fan unit, vertical type 
power distribution unit, and utility unit. All of these are set inside the FCS cabinet. The table below 
shows an overview of each function unit.
Table  Overview of the HKU Function Units
Unit Name
Description
HKU (House Keeping Unit)
Alarm information such as cabinet temperature and performance 
status of cooling fans are controlled and monitored.
PDU (Power Distribution Unit)
Composed of a circuit breaker and a noise filter, PUD supplies power 
to the cabinet and protect it from malfunctions such as inrush current.
Fan Power Supply Unit
Supplies power to door fan, node fun, HKU, and contact output relays.
Node Fan Unit
FCU and nodes are cooled.
Power Supply Bus Unit, Vertical Type
Powers to the cabinet is distributed.
Utility Unit
Power supplies to FCU are supplied, and provide interfaces between 
FCU and HKU.
The HKU and its related units for AFV40D (with cabinet) is shown here.
Utility Unit
Node Fan Unit
Node Fan Unit
Power Supply Bus Unit, Vertical Type
PDU
HKU
Fan Power Supply Unit
Door Fan Unit
Door Fan Unit
F020108E.ai
Front
Rear
Power Supply Bus Unit, Vertical Type
Figure  HKU and its related units  
Sep. 1, 2011-00
C# PDF delete text Library: delete, remove text from PDF file in
Delete text from PDF file in preview without adobe PDF reader component installed in ASP.NET. C#.NET PDF: Delete Text from Consecutive PDF Pages.
cut pages from pdf reader; copy page from pdf
C# PowerPoint - Delete PowerPoint Document Page in C#.NET
doc.Save(outPutFilePath); Delete Consecutive Pages from PowerPoint in C#. int[] detelePageindexes = new int[] { 1, 3, 5, 7, 9 }; // Delete pages.
copy pages from pdf to new pdf; delete pdf pages reader
2.  Hardware
2-9
TI 33K01A12-50E
HKU main unit displays the information given from each functional unit by the LED on the front. 
The table below shows the elements of the HKU for FFCS-V.
Table  HKU display elements
Name
Color
Description
RDY
Green
The initial HKU information is being collected when it is blinking.
When blinking stops, HKU is in routine operation.
(Both represent normal operation status.)
LNK
Green
HK-BUS CARRIER DETECT
D-FAN
Red
The DFAN UNIT (door fan/roof fan) failed.
N-FAN1
Red
Either node FAN Unit 1 or SC FAN Unit on the front failed.
N-FAN2
Red
Node FAN Unit 2 failed.
N-FAN3
Red
Either node FAN Unit 3 or SC FAN Unit on the rear failed.
N-FAN4
Red
Node FAN Unit 4 failed.
PSU HK /AUX HK
Red
Either the fan power unit or the contact I/O failed.
PSU TB
Red
PS4 power unit failed, when it is installed.
ID1
Red
Displays the failure 1. (See the table “Combination of the failed units.”)
ID2
Red
Displays the failure 2. (See the table “Combination of the failed units.”)
ID3
Red
Displays the failure 3. (See the table “Combination of the failed units.”)
ID4
Red
Displays the failure 4. (See the table “Combination of the failed units.”)
Table  Combination of the failed units
ID
D-FAN
N-FANx
PSU HK / AUX HK
PSU TB
Temperature 
anomaly
ID1
Door Fan 1
1st from the left
Fan Power Supply 1
Front, Left
AIR OUT
ID2
Door Fan 2
2nd from the left
Fan Power Supply 2
Front, Right
AIR IN
ID3
Door Fan 3
3rd from the left
Rear, Left
ID4
Door Fan 4
4th from the left
Contact Input
Rear, Right
When the cabinet is installed in a remote location, the HK information is transmitted to FCU via 
an optical ESB bus. All these HK information can be monitored on an HIS through FCS status 
display view.
Sep. 1, 2011-00
2.  Hardware
2-10
TI 33K01A12-50E
2.2 
FCS Configuration
FCS is composed of FCU, node units, ESB bus, etc.. You can select the configuration of these 
components according to the requirement for your operation.
Table  FCS Configuration
Component
Type
FFCS-V
FFCS-L
FFCS
KFCS, 
KFCS2
LFCS, 
LFCS2
PFC 
-H/-S/-E
CPU configuration
Single
Yes
Yes
Yes
Yes
Yes
Yes
Duplexed
Yes
Yes
Yes
Yes
Yes
Yes
ESB bus
Single
Yes
Yes
Yes
Yes
Yes
Yes
Duplexed
Yes
Yes
Yes
Yes
Yes
Yes
ER bus
Single
No
Yes
Yes
Yes
No
No
Duplexed
No
Yes
Yes
Yes
No
No
Optical ESB bus
Single
Yes
No
No
No
No
No
Duplexed
Yes
No
No
No
No
No
Mounting
Rack mountable
Yes
Yes
Yes
Yes
Yes
Yes
Cabinet type
Yes
No
No
Yes
Yes
No
V net
Single
No
No
Yes
No
No
Caution 
(*1)
Duplexed
No
No
Yes
Yes
Yes
Vnet/IP
Duplexed(*2)
Yes
Yes
No
No
No
No
Yes:  Available
No:  Not available
*1: 
For PFCS-S/-E single CPU, use single V net. For PFCD-S/-E duplexed CPU, use duplexed V net. However, for PFC□-H use 
duplexed V net always.
*2: 
Vnet/IP supports only duplexed network.
Sep. 1, 2011-00
2.  Hardware
2-11
TI 33K01A12-50E
2.3 
I/O Module
I/O modules include input modules converting process signals to digital data format used in FCS 
and output modules converting digital data to analog or contact signals.
CENTUM VP I/O modules provide various choices for isolated types or connector types to 
respond flexibly to any requirements.
 I/O Modules for FIO
Table  I/O Modules for FIO (1/2)
Models
Name
Analog I/O Modules
AAI141
Analog Input Module (4 to 20 mA, 16-Channel, Non-Isolated)
AAV141
Analog Input Module (1 to 5 V, 16-Channel, Non-Isolated)
AAV142
Analog Input Module (-10 V to +10 V, 16-Channel, Non-Isolated)
AAI841
Analog I/O Module 
(4 to 20 mA Input, 4 to 20 mA Output, 8-Channel Input/8-Channel Output, Non-Isolated)
AAB841
Analog I/O Module 
(1 to 5 V Input, 4 to 20 mA Output, 8-Channel Input/8-Channel Output, Non-Isolated)
AAV542
Analog Output Module (-10 V to +10 V, 16-Channel, Non-Isolated)
AAI143
Analog Input Module (4 to 20 mA, 16-Channel, Isolated)
AAV144
Analog Input Module (-10 V to +10 V, 16-Channel, Isolated)
AAV544
Analog Output Module (-10 V to +10 V, 16-Channel, Isolated)
AAI543
Analog Output Module (4 to 20 mA, 16-Channel, Isolated)
AAT141
TC/mV Input Module (16-Channel, Isolated)
AAR181
RTD Input Module (12-Channel, Isolated)
AAI135
Analog Input Module (4 to 20 mA, 8-Channel, Isolated Channels)
AAI835
Analog I/O Module (4 to 20 mA, 4-Channel Input/4-Channel Output, Isolated Channels)
AAT145
TC/mV Input Module (16-Channel, Isolated Channels)
AAR145
RTD/POT Input Module (16-Channel, Isolated Channels)
AAP135
Pulse Input Module (8-Channel, Pulse Count, 0 to 10 kHz, Isolated Channels)
AAP149
Pulse Input Module for Compatible PM1 (16-Channel, Pulse Count, 0 to 6 kHz, Non-Isolated)
AAP849
Pulse Input Module/Analog Output Module (8-Channel Input/8-Channel Output, Non-Isolated)
Analog I/O Modules with HART Communication Function
AAI141-H
Analog Input Module (4 to 20 mA, 16-Channel, Non-Isolated)
AAI841-H
Analog I/O Module 
(4 to 20 mA Input, 4 to 20 mA Output, 8-Channel Input/8-Channel Output, Non-Isolated)
AAI143-H
Analog Input Module (4 to 20 mA, 16-Channel, Isolated)
AAI543-H
Analog Output Module (4 to 20 mA, 16-Channel, Isolated)
AAI135-H
Analog Input Module (4 to 20 mA, 8-Channel, Isolated Channels)
AAI835-H
Analog I/O Module (4 to 20 mA, 4-Channel Input/4-Channel Output, Isolated Channels)
Sep. 1, 2011-00
2.  Hardware
2-12
TI 33K01A12-50E
Table  I/O Modules for FIO (2/2)
Sep. 1, 2011-00
Models
Name
Digital I/O Modules
ADV151
Digital Input Module (32-Channel, 24 V DC, Isolated)
ADV141
Digital Input Module (16-Channel, 100 V to 120 V AC, Isolated)
ADV142
Digital Input Module (16-Channel, 200 V to 240 V AC, Isolated)
ADV551
Digital Output Module (32-Channel, 24 V DC, Isolated)
ADV157
Digital Input Module (32-Channel, 24 V DC, Pressure Clamp Terminal Support Only, Isolated)
ADV161
Digital Input Module (64-Channel, 24 V DC, Isolated)
ADV557
Digital Output Module (32-Channel, 24 V DC, Pressure Clamp Terminal Support Only, Isolated)
ADV561
Digital Output Module (64-Channel, 24 V DC, Isolated)
ADR541
Relay Output Module (16-Channel, 24 to 110 V DC/100 to 240 V AC, Isolated)
ADV859
Digital I/O Module for Compatible ST2 
(16-Channel Input/16-Channel Output, Isolated Channels)
ADV159
Digital Input Module for Compatible ST3 (32-Channel Input, Isolated Channels)
ADV559
Digital Output Module for Compatible ST4 (32-Channel Output, Isolated Channels)
ADV869
Digital I/O Module for Compatible ST5 
(32-Channel Input/32-Channel Output, Isolated, Common Minus Side Every 16-Channel)
ADV169
Digital Input Module for Compatible ST6 
(64-Channel Input, Isolated, Common Minus Side Every 16-Channel)
ADV569
Digital Output Module for Compatible ST7 
(64-Channel Output, Isolated, Common Minus Side Every 16-Channel)
ADV851
Digital I/O Module (16-Channel input, 16-Channel output, 24 V DC)
Communication Modules
ALR111
RS-232C Communication Module (2-Port)
ALR121
RS-422/RS-485 Communication Module (2-Port)
ALE111
Ethernet Communication Module
ALF111
FOUNDATION fieldbus (FF-H1) Communication Module (4-Port)
ALP111
PROFIBUS-DPV1 Communication Module
Turbomachinery I/O Modules
AGS813
Servo Module(Isolated)
AGP813
High Speed Protection Module(Isolated)
Documents you may be interested
Documents you may be interested