c# pdf viewer free : How to reverse pages in pdf SDK application API .net azure asp.net sharepoint WinCCInformationSystemScripting_en-US54-part1409

4. Step:
Dim startId
startId = CLng(4)
vServerDataX(3) = startId
vServerDataY(3) = startId
5. Step:
fx_trend.ServerDataX = ServerDataX
fx_trend.ServerDataY = ServerDataY
End Sub
ServerDataY
ServerDataY
Accesses the configured data connection for the Y axis with WinCC FunctionTrendControl.
The attribute can be assigned dynamic properties by means of the name ServerDataY. The 
data type is LONG.
Example: Editing the start ID
You may use the ServerDataY  attribute to edit the start ID of the Y axis. 
Prerequisite is that you have an existing trend and trend view, configured X and Y axes, as 
well as a data connection to the user archive.
In the following example you employ the GetTrend method to set a reference to the object and 
then to the trend used. Determine the data connection settings in the third step. Set the start 
ID to 4 in step 4. The number (3) represents the listing type "user archive" for data transfer. 
Change the modified data connection settings in step five:
Sub OnCklick(ByVal Item)
1. Step:
Dim fx_ctrlSet fx_ctrl  ScreenItems.Item("Control1")
2. Step:
Dim fx_trendSet fx_trend = fx_ctrl.Getrend("myTrend1")
3. Step:
Dim vServerDataX, vServerDataYvServerDataX = 
fx_trend.ServerDataXvServerDataY = fx_trend.ServerDataY
4. Step:
Dim startIdstartId = CLng(4)vServerDataX(3) = 
startIdvServerDataY(3) = startId
5. Step:
fx_trend.ServerDataX = ServerDataXfx_trend.ServerDataY = 
ServerDataY
End Sub
VBS for Creating Procedures and Actions
1.14 VBS Reference
WinCC: Scripting (VBS, ANSI-C, VBA)
System Manual, 02/2013, A5E32315920-AA
541
How to reverse pages in pdf - re-order PDF pages in C#.net, ASP.NET, MVC, Ajax, WinForms, WPF
Support Customizing Page Order of PDF Document in C# Project
how to reorder pages in pdf file; how to change page order in pdf document
How to reverse pages in pdf - VB.NET PDF Page Move Library: re-order PDF pages in vb.net, ASP.NET, MVC, Ajax, WinForms, WPF
Sort PDF Document Pages Using VB.NET Demo Code
reorder pages in pdf reader; reverse page order pdf
ServerNames property
Server selection - ServerNames
Defines from which servers within a distributed system the message window obtains the 
display data. 
The attribute can be assigned dynamic properties by means of the name ServerNames. The 
data type is STRING.
ServerNames property (before WinCC V7)
Description
Defines the server in a distributed system to which the data in the message window should 
relate. Servers are specified as follows: NameServer1;NameServer2;NameServer3. Write/
Read access.
See also
WinCC Alarm Control (before WinCC V7) (Page 279)
ScreenItem Object (Page 130)
ServerPrefix Property
Description
Defines the server containing the picture to be displayed in the picture window in Runtime or 
returns the server name. 
Enter the server name followed by two colons: "<Servername>::". No check is made as to 
whether the server actually exists.
See also
Picture Window (Page 185)
ScreenItem Object (Page 130)
VBS for Creating Procedures and Actions
1.14 VBS Reference
WinCC: Scripting (VBS, ANSI-C, VBA)
542
System Manual, 02/2013, A5E32315920-AA
C# Word: How to Use C# Code to Print Word Document for .NET
document pages in original or reverse order within demonstrates how to print defined pages of Word powerful & profession imaging controls, PDF document, image
reorder pages pdf; rearrange pages in pdf
Sh - Sk
ShareSpaceWithSourceControl property
ShareSpaceWithSourceControl
Defines whether the size of the source control in the picture window is adapted so that the 
WinCC RulerControl is also displayed in a small picture window.
Value
Explanation
TRUE
The source control in the picture window is adapted.
FALSE
The source control in the picture window is not adapted.
The attribute can be assigned dynamic properties by means of the name 
ShareSpaceWithSourceControl. The data type is BOOLEAN.
ShowBar Property
Description
TRUE, when the bar should be displayed. BOOLEAN write-read access.
See also
WinCC Slider Control (Page 272)
ScreenItem Object (Page 130)
ShowDanger Property
Description
Controls the display of the "danger zone" on the instrument scale. BOOLEAN write-read 
access.
TRUE : The area is identified by the color defined in "DangerColor".
FALSE : The color identification of the area is switched off.
See also
WinCC Gauge Control (Page 255)
ScreenItem Object (Page 130)
VBS for Creating Procedures and Actions
1.14 VBS Reference
WinCC: Scripting (VBS, ANSI-C, VBA)
System Manual, 02/2013, A5E32315920-AA
543
ShowDecimalPoint Property
Description
TRUE, when the labeling of the scale section should be with decimal numbers (decimal point 
and one decimal place).
FALSE, when the labeling of the scale section should be with whole numbers.
BOOLEAN write-read access.
See also
WinCC Gauge Control (Page 255)
ScreenItem Object (Page 130)
ShowNormal Property
Description
Controls the display of the "normal zone" on the instrument scale. BOOLEAN write-read 
access.
TRUE : The area is identified by the color defined for normal color.
FALSE : The color identification of the area is switched off.
See also
WinCC Gauge Control (Page 255)
ScreenItem Object (Page 130)
ShowPeak Property
Description
Defines the display of a slave pointer to display the maximum value. BOOLEAN write-read 
access.
TRUE : The slave pointer is displayed.
FALSE : The slave pointer is hidden.
See also
WinCC Gauge Control (Page 255)
ScreenItem Object (Page 130)
VBS for Creating Procedures and Actions
1.14 VBS Reference
WinCC: Scripting (VBS, ANSI-C, VBA)
544
System Manual, 02/2013, A5E32315920-AA
ShowPosition Property
Description
TRUE, when the slider position is to be displayed. BOOLEAN write-read access.
See also
WinCC Slider Control (Page 272)
ScreenItem Object (Page 130)
ShowRuler property
Show ruler - ShowRuler
Enables the display of a ruler for scanning the coordinate points on picture calls.
Value
Explanation
TRUE
Enables the display of a ruler for scanning the coordinate points.
FALSE
Disables the display of a ruler for scanning the coordinate points.
The attribute can be assigned dynamic properties by means of the name ShowRuler. The data 
type is BOOLEAN.
ShowRulerImmediately Property
Description
TRUE, when the ruler for determining the coordinate values should be displayed when opening 
a picture. BOOLEAN write-read access.
See also
WinCC Online Trend Control (before WinCC V7) (Page 285)
WinCC Function Trend Control (before WinCC V7) (Page 281)
ScreenItem Object (Page 130)
VBS for Creating Procedures and Actions
1.14 VBS Reference
WinCC: Scripting (VBS, ANSI-C, VBA)
System Manual, 02/2013, A5E32315920-AA
545
ShowRulerInAxis property
ShowRulerInAxis
Enables the display of rulers in the time axis.
Value
Explanation
TRUE
Enables the display of rulers in the time axes.
FALSE
Disables the display of rulers in the time axes.
The attribute can be assigned dynamic properties by means of the name ShowRulerInAxis. 
The data type is BOOLEAN.
ShowScrollbars property
Scroll bars - ShowScrollbars
Enables the display of scroll bars.
The following settings are available:
Value
Description
Explanation
0
No
The display of scroll bars is disabled.
1
as required
Scroll bars are displayed if space requirements of the control are greater than the actual 
display area. 
2
always
The scroll bars are always displayed.
The attribute can be assigned dynamic properties by means of the name ShowScrollbars. The 
data type is LONG.
ShowSlider property
ShowSlider
Specifies if a time slider is displayed in the control. 
The attribute can be assigned dynamic properties by means of the name ShowSlider. The data 
type is BOOLEAN.
VBS for Creating Procedures and Actions
1.14 VBS Reference
WinCC: Scripting (VBS, ANSI-C, VBA)
546
System Manual, 02/2013, A5E32315920-AA
ShowSortButton property
Use sorting button - ShowSortButton
Enables the display of a sorting button above the vertical scroll bar. Click this sorting button 
to sort the selected column based on the configured sorting criteria. The sorting button is not 
displayed if the table does not contain a vertical scroll bar.
Value
Explanation
TRUE
Enables sorting of a selected column by means of sorting button.
FALSE
The sorting button is not displayed.
The attribute can be assigned dynamic properties by means of the name ShowSortButton . 
The data type is BOOLEAN.
ShowSortIcon property
Show sorting icon - ShowSortIcon
Enables the display of the sorting icon.
Value
Explanation
TRUE
Enables the display of the sorting icon.
FALSE
Disables the display of the sorting icon.
The attribute can be assigned dynamic properties by means of the name ShowSortIcon. The 
data type is BOOLEAN.
ShowSortIndex property
Show sorting index - ShowSortIndex
Enables the display of a sorting icon. 
Value
Explanation
TRUE
Enables the display of a sorting index.
FALSE
Disables the display of a sorting index.
The attribute can be assigned dynamic properties by means of the name ShowSortIndex. The 
data type is BOOLEAN.
VBS for Creating Procedures and Actions
1.14 VBS Reference
WinCC: Scripting (VBS, ANSI-C, VBA)
System Manual, 02/2013, A5E32315920-AA
547
ShowSpanNames Property
Description
TRUE, if a section name is also to be displayed in the Value column of Trend Control apart 
from the measured value and the status display "i" and "u". BOOLEAN write-read access.
ShowStatisticRuler property
ShowStatisticRuler
Enables the display of rulers in the statistics field on picture calls.
Value
Explanation
TRUE
Enables the display of rulers in the statistics field.
FALSE
Disables the display of rulers in the statistics field.
The attribute can be assigned dynamic properties by means of the name ShowStatisticRuler. 
The data type is BOOLEAN.
ShowThumb Property
Description
TRUE, when the slider is to be displayed. BOOLEAN write-read access.
See also
WinCC Slider Control (Page 272)
ScreenItem Object (Page 130)
ShowTitle property
Window title - ShowTitle
Defines representation the Control window header. 
Value
Designation
Explanation
0
No
No window title.
1
Normal
The window title consists of a WinCC icon and text. The text is entered in the "Text" field. 
2
Narrow
The window title consists only of text. The text is entered in the "Text" field.
The attribute can be assigned dynamic properties by means of the name ShowTitle. The data 
type is LONG.
VBS for Creating Procedures and Actions
1.14 VBS Reference
WinCC: Scripting (VBS, ANSI-C, VBA)
548
System Manual, 02/2013, A5E32315920-AA
ShowToolbar property
ShowToolbar
Specifies if a toolbar is displayed in the control. 
The attribute can be assigned dynamic properties by means of the name ShowToolbar. The 
data type is BOOLEAN.
ShowTrendIcon property
ShowTrendIcon
Enables the display of an icon below the value axes. The icon indicates the trend currently 
displayed in the foreground.
The attribute can be assigned dynamic properties by means of the name ShowTrendIcon. The 
data type is BOOLEAN.
ShowValuesExponentialX Property
Description
TRUE, when the X-coordinate of a measured value determined via the "Display value at this 
position" function is displayed in exponential notation by a trend referenced via "Index". 
Whether the information is evaluated is dependent on the value of the "TimeAxisX" property. 
BOOLEAN write-read access.
See also
WinCC Function Trend Control (before WinCC V7) (Page 281)
ScreenItem Object (Page 130)
ShowValuesExponentialY Property
Description
TRUE, when the Y-coordinate of a measured value determined via the "Display value at this 
position" function is displayed in exponential notation by a trend referenced via "Index". 
BOOLEAN write-read access.
See also
WinCC Function Trend Control (before WinCC V7) (Page 281)
ScreenItem Object (Page 130)
VBS for Creating Procedures and Actions
1.14 VBS Reference
WinCC: Scripting (VBS, ANSI-C, VBA)
System Manual, 02/2013, A5E32315920-AA
549
ShowWarning Property
Description
Controls the display of the "warning zone" on the instrument scale. BOOLEAN write-read 
access.
TRUE : The area is identified by the color defined by the warning color attribute.
FALSE : The color identification of the area is switched off.
See also
WinCC Gauge Control (Page 255)
ScreenItem Object (Page 130)
SignificantMask Property
Description
Is required in Runtime to display the active message class with the highest priority. 
The value of the SignificantMask property represents an internal system output value does not 
require any specific configuration by the user. Updating is initiated in Runtime by clicking on 
the object.
See also
Group Display (Page 200)
ScreenItem Object (Page 130)
Sizeable property
Sizeable
Enables resizing of the control during runtime.
Value
Explanation
TRUE
The control can be resized during runtime.
FALSE
The control cannot be resized during runtime.
The attribute can be assigned dynamic properties by means of the name Sizeable. The data 
type is BOOLEAN.
VBS for Creating Procedures and Actions
1.14 VBS Reference
WinCC: Scripting (VBS, ANSI-C, VBA)
550
System Manual, 02/2013, A5E32315920-AA
Documents you may be interested
Documents you may be interested