REQUIREMENTS FOR PARALLEL OPERATION FOR CUSTOMERS WITH 
GENERATION NOT EXCEEDING 50 kW 
FOREWARD 
“Requirements for Parallel Operations for Customers with Generation Not Exceeding 50 
kW” is intended to be used as a guide for customers with small generators who wish to 
interconnect to PECO electric distribution system.  This document condenses 
requirements in the 
Exelon Energy Delivery Interconnection Guidelines for Generators 2 MVA 
or less
For additional information about PECO services and future updates of this document 
please contact the PECO New Business office. 
A. CUSTOMER ELIGIBILITY 
Applicant must be a PECO customer with at least a 60 Amp, 120/240 Volt secondary 
service. The generator operated in parallel with PECO may not exceed 50 kW, 240 volts, 
without special permission. 
B. EQUIPMENT REQUIREMENTS 
Figures 1 through 4 show suggested arrangements of equipment, although they are not 
intended as design documents. Customers with Utility Interactive Inverter power system 
interfaces which meet current standards set forth in UL Publication 1741 and IEEE 1547 
are eligible for an expedited review.  The customer shall furnish, install and maintain the 
following equipment: 
1. COMPATIBLE EQUIPMENT: Energy conversion facilities, generator and 
necessary interface equipment to match PECO service. 
2. NEC CONFORMANCE  The service shall be modified per the National 
Electrical Code
® 
(NEC), to accommodate an interconnected electric power 
production source ( See Articles 690, 692, and 705) 
3. DISCONNECT SWITCH A readily accessible disconnect switch which is pad 
lockable and provides a visible break shall be installed between the AC output of 
the interconnected power source and its connection to the premise wiring system.  
For residential services, this switch shall be located outdoors, as close as practical 
to the utility meters.  If this disconnect switch is not visible from the utility 
meters, a plaque shall be located at the utility meters indicating the presence and 
location of this disconnect switch.  For commercial, industrial, or multi-tenant 
facilities larger than 5 units, this switch may be located indoors, by special 
permission, where conditions of maintenance and supervision ensure that the 
customer can provide qualified persons, available 24/7, to service and operate the 
system as required by PECO. 
Interconnected Generation 50 kW or less 
Page 1 of 6  Rev date  September 30, 2009 
Deleting pages from pdf - copy, paste, cut PDF pages in C#.net, ASP.NET, MVC, Ajax, WinForms, WPF
Easy to Use C# Code to Extract PDF Pages, Copy Pages from One PDF File and Paste into Others
extract one page from pdf reader; extract pages from pdf file online
Deleting pages from pdf - VB.NET PDF Page Extract Library: copy, paste, cut PDF pages in vb.net, ASP.NET, MVC, Ajax, WinForms, WPF
Detailed VB.NET Guide for Extracting Pages from Microsoft PDF Doc
deleting pages from pdf in preview; copy pdf page to clipboard
4. METERING OPTIONS: All services shall be metered for registered  kWH and 
KW usage as dictated by the PAPUC tariff.   PECO will provide the IN and OUT 
meters for customers electing a Net Metering option.  Customers must provide 
and install the required meter sockets or metering transformer enclosures to 
contain the PECO metering equipment.  For the residential, two meter option, 
both sockets must be outdoors, with space for mounting a copy of the source 
directory required per NEC, Article 705.10, showing location of all electrical 
sources to the premises.  The various metering options available are indicated in 
the table below 
METERING OPTIONS 
Option
Description
Meter 
Configuration
Notes
Net Metering 
• 
2 Meters 
• 
1 – IN 
• 
1 - OUT 
Two meters - Customer billed monthly for 
net usage. 
Single Meter, 
Detented 
• 
1 Meter IN only 
Generation output should not exceed 
premise load.  Customer does not expect to 
export power or Net Meter. 
Sale of Energy 
to Third Party 
• 
Separate Service to 
System 
• 
2 Meters 
• 
PECO IN 
• 
Third Party OUT 
PECO meter reads IN only.  Customer is 
billed for all registered usage.  Third 
party agreement through PJM to 
purchase energy.  OUT meter and 
communications to meet requirements 
of PJM. 
Virtural Net 
Metering 
• 
Multiple IN meters 
• 
Multiple OUT 
meters 
Combined registration of multiple usage 
and source meters within 2 mile radius 
under the same ownership and PECO 
account name. 
5. ELECTRICAL INTERFACE PROTECTION All interconnected power 
systems are required to monitor current, voltage and frequency and to disconnect 
the power source from the utility service, per IEEE 1547 protection levels and 
time delays,  if the PECO supply is interrupted.  Over/Under Voltage, and 
Over/Under Frequency protection shall meet the requirements of  IEEE 1547.  
Manufacturer specifications for frequency and voltage protection schemes must 
be submitted to PECO for review.    If this protection is not an integral part of a 
listed, manufactured power source interconnection system, PECO shall have the 
right to require testing of the protection device systems at the customer’s expense.  
Minimum protection requirements are dependent on the type of generation source 
as listed below. Additional protection may be installed such as reverse power, 
reverse current, or out of step relaying, at the manufacturer’s discretion. 
Note: 
Interconnected Generation 50 kW or less 
Page 2 of 6  Rev date  September 30, 2009 
C# PDF Page Delete Library: remove PDF pages in C#.net, ASP.NET
C#.NET PDF Library - Delete PDF Document Page in C#.NET. Provide C# Users with Mature .NET PDF Document Manipulating Library for Deleting PDF Pages in C#.
copy pdf page into word doc; cut paste pdf pages
VB.NET PDF Page Delete Library: remove PDF pages in vb.net, ASP.
Document Page in VB.NET Class. Free PDF edit control and component for deleting PDF pages in Visual Basic .NET framework application.
delete pages of pdf; delete page from pdf reader
Utility Interactive Inverters meeting the requirements of UL Publication 1741, and  IEEE  
1547  satisfy these interface  protection requirements
.
a. Overcurrent Protection - All Generation Types 
Circuit breakers or fuse elements sized in accordance with the NEC must be present in 
the circuit interconnecting the generation source to the premise electrical system.. 
b Utility Interactive Inverters 
Utility Interactive Inverters shall meet UL publication 1741, which requires monitoring 
the service voltage and frequency to detect utility service interruption and shuts down the 
inverter operation upon loss of utility supply. 
c Induction Generators  
A protective device meeting IEEE 1547 shall monitor the service voltage and frequency 
to detect utility service interruption, and disconnect the induction generator from the 
service. 
d. Synchronous Generators 
Synchronous generators produce power without the need of a utility source for excitation, 
and have the capability to supply loads independent of the utility electric supply.  PECO 
shall review these installations for their expected contribution to fault currents.  The 
installer shall calculate the fault contribution of the synchronous generator at the service 
voltage, and submit “X
d
,  X
’d
, and X
”d”
impedance values for the generator being 
installed.    A protective device meeting IEEE 1547 shall monitor the service voltage and 
frequency to detect utility service interruption and disconnect the generator from the 
electrical service.   Frequency protection shall be set to trip the generator if less than 59.5 
Hertz or greater than 60.5 Hertz. In addition, these sources must be interconnected to 
supply the phase to neutral loads on the service. 
e.  Self Commutating Inverters 
Self commutating inverters produce power without the need of a utility source for 
commutation, and have the capability to supply loads independent of the utility electric 
supply.  PECO shall review these installations  for their expected contribution to fault 
currents.  The installer shall calculate the steady state fault current contributions of a self 
commutating inverter to a  single phase fault on the service, and or a three phase fault 
where appropriate..  A protective device meeting IEEE 1547 shall monitor the service 
voltage and frequency to detect utility service interruption and shut down the inverter.   
Frequency protection shall be set to shut down the inverter if less than 59.5 Hertz or 
greater than 60.5 Hertz. In addition, these sources must be interconnected to supply the 
phase to neutral loads on the service 
Interconnected Generation 50 kW or less 
Page 3 of 6  Rev date  September 30, 2009 
C# PDF File & Page Process Library SDK for C#.net, ASP.NET, MVC
Deleting Pages. You may feel free to define some continuous PDF pages and delete. Certainly, random pages can be deleted from PDF file as well. Sorting Pages.
extract pages from pdf reader; extract pages from pdf without acrobat
C# Word - Delete Word Document Page in C#.NET
C# Word - Delete Word Document Page in C#.NET. Provides Users with Mature Document Manipulating Function for Deleting Word Pages. Overview.
delete pages from pdf in reader; delete pages of pdf preview
C. Requirements for Connection 
1.  The applicant  shall submit the following to the appropriate PECO regional New 
Business office: 
a.  A Level 1, 2, 3, or 4 “INTERCONNECTION APPLICATION / 
AGREEMENT” application form 
b.  A PECO Service and Meter Application 
c.  Appropriate application fee 
.The forms and fees are available on the following PECO Net Metering and 
Interconnection webpage. 
http://www.peco.com/pecores/energy_rates/Net+Metering+and+Interconnections.htm
APPLICATION LEVEL GUIDE LINE 
Level 
Size of 
Interconnected 
Power Source 
Applicability 
10 kW or Less 
• 
Power interface is inverter based. 
• 
Power interface with utility is pre-certified by a Listed 
testing agency to meet UL-1741 and IEEE 1547. 
• 
Exported power will be Net-Metered with PECO IN 
and OUT  service meters. 
>10 kW  
<= 50 kW 
• 
Power interface is inverter based. 
• 
Power interface with utility is pre-certified by a Listed 
testing agency to meet UL-1741 and IEEE 1547. 
• 
Exported power will be Net-Metered with PECO IN 
and OUT  service meters. 
<= 50 kW 
• 
Systems submitted as Level 1, 2, or 4 which were not 
approved 
• 
Systems which do not meet Level 1 or 2 criteria 
• 
Installation may require PECO system modifications 
to interconnect. 
• 
Non-Inverter based interface 
• 
Interface protection is not certified by a Listed testing 
agency to meet UL-1741 and IEEE 1547 
• 
Exported power will be Net-Metered with PECO IN 
and OUT  service meters. 
<= 50 kW 
• 
Systems submitted as Level 1 or 2 which were not 
approved 
• 
Export of power is not expected 
• 
Reverse power relays or other protection functions that 
prevent power flow onto the utility grid. 
• 
PECO service meter to be detented to register IN only 
Interconnected Generation 50 kW or less 
Page 4 of 6  Rev date  September 30, 2009 
VB.NET PDF File & Page Process Library SDK for vb.net, ASP.NET
You may feel free to define some continuous PDF pages through deleting pages in VB.NET demo code. Certainly, random pages can be deleted from PDF file as well.
extract page from pdf file; export pages from pdf reader
C# PowerPoint - Delete PowerPoint Document Page in C#.NET
C# PowerPoint - Delete PowerPoint Document Page in C#.NET. Provides Users with Mature Document Manipulating Function for Deleting PowerPoint Pages. Overview.
extract page from pdf document; extract page from pdf acrobat
2.  A diagram, similar to Figures 1 thru 4, shall be submitted by the contractor indicating: 
• 
Where the electrical interconnection will be made with the premise wiring 
• 
List equipment ratings, conductor sizes, and fuse and breaker ratings 
Note: Transformer rated metering installations will require special review for 
modification to the meter board. This type of installation is not included in the 
Figures. 
3.  Submit all available manufacturers’ information concerning the system’s electrical 
components. 
Note: not required for systems meeting IEEE Standard  1547, and UL Publication 1741
4.  The installation must meet all local municipality building codes, the National 
Electrical Code, and the National Electrical Safety Code, and shall be inspected by an 
electrical underwriter listed in PECO’s Electric Service Requirements handbook. 
5.  PECO will review the application per PAPUC PA Code Chapter 75 criteria.  The 
results of this review will be forwarded to the submitter with instructions to modify  
PECO’s metering installation.  If PECO distribution facilities must be modified to 
meet the Chapter 75 criteria, the submitter shall be notified per section  
D. Rearrangement Of PECO Distribution Facilities,  below. 
6.  Upon the completion of the interconnected power system’s installation and any 
required PECO system and or metering upgrades, the applicant shall sign and submit 
PECO’s Certification of Completion form and an electrical underwriter’s inspection 
of the interconnected power system wiring,  The Certification of Completion. is 
available on the PECO Net Metering and Interconnection webpage.  PECO reserves 
the right to require a “witness test” of the system’s protection scheme.  Testing will 
be required for systems meeting the following criteria: 
a.  Any system which is not pre- certified by an independent testing laboratory (UL 
1741). 
b.  Systems with field adjustable relays will require calibration by an independent 
testing service.  A trip test shall be witnessed by a PECO representative.  In 
addition, a test report of the relay calibrations shall be submitted to PECO for 
review. 
Note: PECO net- meter billing will not become active until the “witness test” has been waived, 
or satisfied, the Certificate of Completion has been completed and  signed by the applicant, and 
an electrical under writer inspection has been submitted. 
Interconnected Generation 50 kW or less 
Page 5 of 6  Rev date  September 30, 2009 
VB.NET TIFF: Modify TIFF File by Adding, Deleting & Sort TIFF
Please check following TIFF page deleting methods and &ltsummary> ''' Sort TIFF document pages in designed & profession imaging controls, PDF document, image
extract one page from pdf acrobat; extract pages from pdf
VB.NET TIFF: An Easy VB.NET Solution to Delete or Remove TIFF File
also empowers users to insert blank pages into TIFF I have tried the function of deleting page from powerful & profession imaging controls, PDF document, image
delete blank page from pdf; delete pages from pdf reader
D. Rearrangement Of PECO Distribution Facilities 
Where the review of a Level 1, 2, or 4 application determines that PECO facilities must 
be modified to accommodate the connection of the applicant’s system, the application 
will be returned to the applicant to be re-submitted as a Level 3 with appropriate Level 3 
application fee.  An explanation of the reason for the return will be indicated.  The new 
Level 3 application will keep the queue position of the original application.  A Level 3 
review response may require the applicant to pay for an Interconnection Feasibility Study 
and or an Interconnection Impact Study, to determine the modifications to PECO’s 
system required to accommodate the interconnection of the proposed power system.  
When the extent of PECO’s system modifications have been determined, PECO will 
prepare an Interconnection  Facilities Study to communicate the nature of the PECO 
system modifications, costs for engineering, procurement, construction, and overheads, as 
well as an estimated time to complete the construction associated with the modifications.  
The applicant must agree to pay for the modifications, in advance, before work begins. 
Interconnected Generation 50 kW or less 
Page 6 of 6  Rev date  September 30, 2009 
C#: How to Delete Cached Files from Your Web Viewer
PDF pages extract, copy, paste, C#.NET rotate PDF pages, C#.NET VB.NET How-to, VB.NET PDF, VB.NET Word Visual C#.NET Developers the Ways of Deleting Cache Files.
crop all pages of pdf; deleting pages from pdf document
C# PDF remove image library: remove, delete images from PDF in C#.
VB.NET comment annotate PDF, VB.NET delete PDF pages, VB.NET C# PDF - Remove Image from PDF Page. Provide C# Demo Code for Deleting and Removing Image from PDF
cut pages out of pdf; extract pdf pages acrobat
FIGURE 1
RESIDENTIAL NON-UTILITY GENERATION
TYPICAL SERVICE & EQUIPMENT ARRANGEMENT
PHOTOVOLTAIC / UTILITY INTERACTIVE INVERTER
WHM
WHM
PECO RESIDENTIAL 
SERVICE
120/240 VOLTS
1 PHASE 3 WIRE
FORM 2S
All equipment shown, except for watt-hour meters (WHM), 
are owned, operated and maintained by the customer.  
Both breakers and switch/fuse equipment may be 
interchanged.  Symbols were selected for convenience 
only.
Separate*, self-contained meter sockets of the same size 
shall be installed outdoors, with space provision for NEC 
Source directory.  Meters register flow in direction shown.  
Meters are detented to prevent reverse registration.
* MULTIPLE METER SOCKET BOARDS WITH COMMON 
BUS ARE NOT PERMITTED.
100 AMP, 2 POLE
VOLTAGE & 
FREQUENCY 
PROTECTION
KW
VOLTS
AMPS
MAKE
INVERTER TRIP
HOUSE LOADS
MODEL
IN
METER
OUT
METER
INCOMING
SERVICE
TO SERVICE
DISCONNECTS
METER DETAIL
Interconnection may be made on 
the supply side of the main 
service disconnect per Figure 2.
Interconnection on the load side 
of the service disconnect requires 
special NEC considerations.
FIGURE 2
RESIDENTIAL NON-UTILITY GENERATION
TYPICAL SERVICE & EQUIPMENT ARRANGEMENT
SYNCHRONOUS OR INDUCTION GENERATOR
AND PHOTOVOLTAIC / UTILITY INTERACTIVE INVERTER
WHM
WHM
All equipment shown, except for watt-hour meters (WHM), are owned, 
operated and maintained by the customer.  Both breakers and switch/
fuse equipment may be interchanged.  Symbols were selected for 
convenience only.
Separate*,self-contained meter sockets of the same size shall be 
installed outdoors, with space provision for NEC Source directory.  
Meters register flow in direction shown.  Meters are detented to prevent 
reverse registration.
Interconnection on the load side of the service disconnect requires 
special NEC considerations.
* MULTIPLE METER SOCKET BOARDS WITH COMMON BUS ARE 
NOT PERMITTED.
100 AMP, 2 POLE
VOLTAGE & 
FREQUENCY 
PROTECTION
MAGNETICALLY HELD
CONTACTOR
NEMA SIZE
O.L. SET
ROTATING
GENERATOR
KW
VOLTS
AMPS
RPM
 ] SYNC    [  ] INDUCTION
GENERATOR TRIP
HOUSE LOADS
PECO RESIDENTIAL 
SERVICE
120/240 VOLTS
1 PHASE 3 WIRE
FORM 2S
IN
METER
OUT
METER
INCOMING
SERVICE
TO SERVICE
DISCONNECTS
METER DETAIL
FIGURE 3
THREE-PHASE GENERAL SERVICE METER SOCKET
NON-UTILITY GENERATION
TYPICAL SERVICE & EQUIPMENT ARRANGEMENT
PHOTOVOLTAIC / UTILITY INTERACTIVE INVERTER
WHM
WHM
PECO THREE-PHASE 
GENERAL SERVICE
3 PHASE 4 WIRE
FORM 15 / 16S
All equipment shown, except for watt-hour meters (WHM), 
are owned, operated and maintained by the customer.  
Both breakers and switch/fuse equipment may be 
interchanged.  Symbols were selected for convenience 
only.
Separate*, self-contained meter sockets of the same size 
shall be installed outdoors, with space provision for NEC 
Source directory.  Meters register flow in direction shown.  
Meters are detented to prevent reverse registration.
* MULTIPLE METER SOCKET BOARDS WITH COMMON 
BUS ARE NOT PERMITTED.
VOLTAGE & 
FREQUENCY 
PROTECTION
KW
VOLTS
AMPS
MAKE
INVERTER TRIP
HOUSE LOADS
MODEL
Pole
Amps
IN
METER
OUT
METER
INCOMING
SERVICE
TO SERVICE
DISCONNECTS
METER DETAIL
Interconnection may be made on 
the supply side of the main 
service disconnect per Figure 4.
Interconnection on the load side 
of the service disconnect requires 
special NEC considerations.
FIGURE 4
THREE-PHASE GENERAL SERVICE METER SOCKET
NON-UTILITY GENERATION
TYPICAL SERVICE & EQUIPMENT ARRANGEMENT
SYNCHRONOUS OR INDUCTION GENERATOR
AND PHOTOVOLTAIC / UTILITY INTERACTIVE INVERTER
WHM
WHM
PECO
THREE-PHASE
GENERAL SERVICE
3 PHASE 4 WIRE
FORM 15 / 16S
1 -
VOLTAGE & 
FREQUENCY 
PROTECTION
MAGNETICALLY HELD
CONTACTOR
NEMA SIZE
O.L. SET
ROTATING
GENERATOR
KW
VOLTS
AMPS
RPM
 ] SYNC    [  ] INDUCTION
GENERATOR TRIP
HOUSE LOADS
Pole
Amps
IN
METER
OUT
METER
INCOMING
SERVICE
TO SERVICE
DISCONNECTS
METER DETAIL
All equipment shown, except for watt-hour meters (WHM), are owned, 
operated and maintained by the customer.  Both breakers and switch/
fuse equipment may be interchanged.  Symbols were selected for 
convenience only.
Separate*,self-contained meter sockets of the same size shall be 
installed outdoors, with space provision for NEC Source directory.  
Meters register flow in direction shown.  Meters are detented to prevent 
reverse registration.
Interconnection on the load side of the service disconnect requires 
special NEC considerations.
* MULTIPLE METER SOCKET BOARDS WITH COMMON BUS ARE 
NOT PERMITTED.