1756-6.5.3 - December 1999
Adding an I/O Chassis to an Existing ControlNet Network
11-9
11.Click on Finish to accept the configuration.
The I/O Configuration tree should now look similar to the one shown 
below.
Edit the Controller Tags
1. Double-click on the Controller Tags folder in the project window.
2. Note that new tags have been added for the remote CNB module and the 
remote analog I/O module.
Tags for new remote 
1756-CNB and remote 
analog I/O created by the 
system.
Delete pages from pdf reader - SDK control service:C# PDF Page Extract Library: copy, paste, cut PDF pages in C#.net, ASP.NET, MVC, Ajax, WinForms, WPF
Easy to Use C# Code to Extract PDF Pages, Copy Pages from One PDF File and Paste into Others
www.rasteredge.com
Delete pages from pdf reader - SDK control service:VB.NET PDF Page Extract Library: copy, paste, cut PDF pages in vb.net, ASP.NET, MVC, Ajax, WinForms, WPF
Detailed VB.NET Guide for Extracting Pages from Microsoft PDF Doc
www.rasteredge.com
1756-6.5.3 - December 1999
11-10
Adding an I/O Chassis to an Existing ControlNet Network
3. Select the Edit Tags tab at the bottom of the Controller Tags window.
4. Create the following tag:
Modify the Ladder Program
1. Double-click on Main Routine under the Main Program folder, and 
add rungs 3 and 4 to the ladder program:
2. Save the program.
Download the Program
(1)
1. Click on the Communications menu and select Who Active.
2. The Who Active window will appear (Your window may look different 
depending upon the drivers and other devices you have installed).
Tag Name
Type
Analog_Output
Timer
(1)
This example uses RSLogix5000 version 2.25. See Appendix D if you are using version 2.10 or earlier.
SDK control service:VB.NET PDF Page Delete Library: remove PDF pages in vb.net, ASP.
doc.Save(outPutFilePath). How to VB.NET: Delete Consecutive Pages from PDF. doc.Save(outPutFilePath). How to VB.NET: Delete Specified Pages from PDF.
www.rasteredge.com
SDK control service:C# PDF Page Delete Library: remove PDF pages in C#.net, ASP.NET
doc.Save(outPutFilePath); Demo Code: How to Delete Consecutive Pages from PDF in C#.NET. Demo Code: How to Delete Specified Pages from PDF in C#.NET.
www.rasteredge.com
1756-6.5.3 - December 1999
Adding an I/O Chassis to an Existing ControlNet Network
11-11
3. Drill down the tree through the ControlNet driver and the 1756-CNB 
module at node 1 to the controller in slot 0.
4. Highlight the controller and click on the Download button.
5. Minimize RSLogix5000.
Schedule the Network Using 
RSNetWorx for ControlNet
Whenever you add or remove a remote I/O module you must run 
RSNetWorx for ControlNet to transfer the new configuration data to 
networked modules and establish a Network Update Time (NUT) for 
ControlNet that is compliant with the desired communication options 
specified for each module during configuration.
Perform the following steps to schedule and optimize the network:
1. Start the RSNetWorx for ControlNet software.
The RSNetWorx for ControlNet main window will appear.
2. From the Network menu, select New.
3. Check the Edits Enabled box and go Online
SDK control service:C# PDF File & Page Process Library SDK for C#.net, ASP.NET, MVC
VB.NET Page: Insert PDF pages; VB.NET Page: Delete PDF pages; VB.NET Annotate: PDF Markup & Drawing. XDoc.Word for XImage.OCR for C#; XImage.Barcode Reader for C#
www.rasteredge.com
SDK control service:C# PDF Page Insert Library: insert pages into PDF file in C#.net
how to merge PDF document files by C# code, how to rotate PDF document page, how to delete PDF page using C# .NET, how to reorganize PDF document pages and how
www.rasteredge.com
1756-6.5.3 - December 1999
11-12
Adding an I/O Chassis to an Existing ControlNet Network
The Browse for Network window will appear with a list of available 
drivers. (Your list may appear different from that shown below, but you 
should have the AB_KTC-1 driver configured as described in 
chapter 2.).
4. Select the AB_KTC-1 driver and click on OK.
5. If you receive a message that there is an Online/Offline mismatch, select 
the Use online data (upload) option and click on OK.
The Save As window will appear:
6. Enter an appropriate name for the network (e.g., “Sched_IO_2”) and 
click on Save.
SDK control service:VB.NET PDF Page Insert Library: insert pages into PDF file in vb.
Page: Insert PDF Pages. |. Home ›› XDoc.PDF ›› VB.NET PDF: Insert PDF Page. Add and Insert Multiple PDF Pages to PDF Document Using VB.
www.rasteredge.com
SDK control service:VB.NET PDF delete text library: delete, remove text from PDF file
Visual Studio .NET application. Delete text from PDF file in preview without adobe PDF reader component installed. Able to pull text
www.rasteredge.com
1756-6.5.3 - December 1999
Adding an I/O Chassis to an Existing ControlNet Network
11-13
RSNetWorx for ControlNet will browse the network for the attached 
devices. When it is done browsing, your ControlNet network should 
appear similar to that shown below:
7. Verify that the devices shown and their network node addresses are 
correct.
Verify the Network Properties
Make sure that the network update time (NUT), Max Scheduled Address, 
and Max Unscheduled Address are set correctly.
1. Select Network from the main menu bar and Properties from the 
pull-down menu.
The following window will appear:
SDK control service:C# PDF Page Rotate Library: rotate PDF page permanently in C#.net
batch changing PDF page orientation without other PDF reader control. NET, add new PDF page, delete certain PDF page, reorder existing PDF pages and split
www.rasteredge.com
SDK control service:C# PDF delete text Library: delete, remove text from PDF file in
Delete text from PDF file in preview without adobe PDF reader component installed in ASP.NET. C#.NET PDF: Delete Text from Consecutive PDF Pages.
www.rasteredge.com
1756-6.5.3 - December 1999
11-14
Adding an I/O Chassis to an Existing ControlNet Network
2. Make sure that these parameters to are set to the following values:
3. Click on OK.
Survey the Network for Connected Devices
Next, have RSNetWorx for ControlNet survey the network for all connected 
devices.
1. Check the Edits Enabled box.
2. From Selection pull-down menu, select Survey Network.
In this field
Select
Network_Update_Time (ms)
5 ms
(1)
(1)
Remember that the requested packet interval (RPI) for any of the devices on the network 
cannot be faster than the NUT.
Max Scheduled Address
10
(2)
(2)
This should be set to a value 3 or 4 above the highest scheduled node on the network, in this 
case the 1756-CNB module at node 6.
Max Unscheduled Address
17
(3)
(3)
At a minimum, this should be set to the highest node address on the network, in this case 
the 1784-KTXC15 card at node 17.
1756-6.5.3 - December 1999
Adding an I/O Chassis to an Existing ControlNet Network
11-15
When RSNetWorx for ControlNet is finished surveying, the network 
window should appear similar to that shown below.
Schedule the Network and Save the Configuration
1. From the File menu, select Save.
The following pop-up window will appear:
2. Select “Optimize and re-write schedule for all connections” and click 
onOK.
The network is now configured and scheduled, and the local controller is 
able to communicate with the remote ControlNet devices.
1756-6.5.3 - December 1999
11-16
Adding an I/O Chassis to an Existing ControlNet Network
Test the Example Application
Use the following procedure to test the operation of the remote analog 
output:
1. Connect a voltmeter across the channel 0 outputs of the 1756-OF6VI 
analog output module as shown in the following figure:
2. Restore the RSLogix5000 software and place the controller in Run 
mode.
3. Measure the output voltage of channel 0. You should see it slowly rising 
to approximately 10V, reset to zero, and start rising again, etc.
4. Verify that the digital I/O modules in the other remote chassis are still 
working. See page 10-18.
OUT-0
RTN-0
1
5
1756-OF6VI
V
+
Refer to the ControlLogix Analog I/O Modules User Manual, publication 
1756-6.5.9, and the ControlLogix Digital I/O Modules User Manual, 
publication 1756-6.5.8, for assistance in wiring and debugging the I/O 
modules, if needed.
1756-6.5.3 - December 1999
Adding an I/O Chassis to an Existing ControlNet Network
11-17
Adding 1756-CNB Modules to 
Expand the Network
The ControlNet network in the example application can support a maximum 
of 64 remote bidirectional connections. To expand the network you can add 
additional 1756-CNB interface modules to the local chassis and connect 
them to remote 1756-CNB modules on the same or another ControlNet 
network. Each 1756-CNB module added to the local chassis can 
communicate with a maximum of 64 connections. For example, the system 
shown in the following figure can use one controller to support a theoretical 
maximum of 128 remote connections.
Important:The number of connections that can actually be supported on a 
network is dependent upon many factors, including the network 
parameter settings. For example, at an RPI of 5ms, not more 
than 10 to 12 connections can be supported, at an RPI of 2ms 
only 4 connections can be supported. 
Logix5550
1756-CNB
(Node 1)
1756-CNB
(Node 12)
Local Chassis
Remote Chassis #3
PC with
1784-KTCX15
Interface 
Controller
Remote Chassis #4
1756-CNB
(Node 31)
1756-CNB
(Node 6)
Remote Chassis #1
1756-CNB
(Node 3)
1756-CNB
(Node 2)
To Other
Devices
Remote Chassis #2
1756-6.5.3 - December 1999
11-18
Adding an I/O Chassis to an Existing ControlNet Network
The RSLogix5000 I/O configuration for the expanded network is shown in 
the following figure. To add remote I/O modules to the configuration, add 
them to the remote 1756-CNB modules as you did in the example 
application.
This completes the expanded remote I/O example.
Refer to Appendix A for information on allocating communication 
connections in a ControlNet network.