1756-6.5.3 - December 1999
Chapter 12
Troubleshooting
The 1756-CNB and 1756-CNBR modules are provided with the LED 
diagnostic indicators shown below. The diagnostics provided by these 
indicators is described in the following sections.
Module Status Indicator and Display
LED
Display
Cause
Action
Off
None
Module not communicating 
due to a power supply fault or 
internal fault.
1. Check the power supply.
2. Check the cable connectors.
3. Make sure the module is firmly 
seated in the chassis.
4. If the indicator remains off, 
replace the module.
Red
INIT
Module is initializing
None required.
POST
Module is running Power-On 
Self Test (POST)
X
Module failed POST because 
the RAM test failed.
Replace the module.
1756-CNB
1756-CNBR
20958-M
ControlNet status indicator(s)
module status display and 
network addressdescribed 
on page 14 
module status indicator
(red or 
green)described on 
page 11 
module status display and network 
address 
module status indicator (red or 
green)
See pages 12-1 to 12-3. 
See pages 12-3 to 12-4.
OK
Delete page from pdf document - application control utility:C# PDF Page Extract Library: copy, paste, cut PDF pages in C#.net, ASP.NET, MVC, Ajax, WinForms, WPF
Easy to Use C# Code to Extract PDF Pages, Copy Pages from One PDF File and Paste into Others
www.rasteredge.com
Delete page from pdf document - application control utility:VB.NET PDF Page Extract Library: copy, paste, cut PDF pages in vb.net, ASP.NET, MVC, Ajax, WinForms, WPF
Detailed VB.NET Guide for Extracting Pages from Microsoft PDF Doc
www.rasteredge.com
1756-6.5.3 - December 1999
12-2
Troubleshooting
Red
ADDR 
ERR
Module’s network address is 
set to 00, an invalid ControlNet 
address.
1.Remove the module from the 
chassis.
2.Set the network address 
switches to a unique address 
(01-99).
3.Install the module in the chassis.
4.If off, turn chassis power supply 
on.
RACK 
ERR
Module is unable to read the 
size data stored in the 
EEPROM because the EEPROM 
is uninitialized or invalid.
Replace the chassis.
CNP2 
ERR
The module has detected that 
it is unable to be the keeper 
for this network due to a 
firmware incompatibility.
Change this node’s address to a 
value of 2 or greater. Contact 
Allen-Bradley for a compatible 
firmware update.
BPIC
ERR
There is a hardware fault 
within the module.
Replace the module.
The module has detected 
improper backplane operation. 
This could be due to a noisy or 
defective backplane 
connection or bad hardware 
within the module.
1.Make sure your system is 
grounded properly.
2.Cycle power on the power supply 
or reset the counters using the 
ControlLogix Gateway 
configuration software.
3.Remove the module and make 
sure its backplane connectors 
aren’t damaged.
4.If these steps fail to correct the 
problem, replace the module.
CNIC
ERR
There is a hardware fault 
within the module.
Replace the module.
None
Flashing 
Red
ROM
UPDT
Flash update is in progress.
None required
DUPL
NODE
Module’s network address is 
the same as another module’s 
on the link.
1.Remove the module from the 
chassis.
2.Set the network address 
switches to a unique address 
(01-99).
3.Install the module in the chassis.
4.If off, turn chassis power supply 
on.
BOOT
Module has invalid firmware. Update module firmware with 
ControlFlash Update Utility.
Green
OK
Normal operation
None required
Green or 
Flashing 
Green
BPA#
ERR
Module detected a different 
slot address than that latched 
in at power-up. Excessive 
noise on the backplane causes 
this error.
1.Make sure your system is 
grounded properly.
2.Cycle power on the power supply 
or reset the counters using the 
ControlLogix Gateway 
configuration software.
3.Remove the module and make 
sure its backplane connectors 
aren’t damaged.
LED
Display
Cause
Action
OK
application control utility:VB.NET PDF Page Delete Library: remove PDF pages in vb.net, ASP.
VB.NET PDF - How to Delete PDF Document Page in VB.NET. This page is aimed to help you learn how to delete page from your PDF document in VB.NET application.
www.rasteredge.com
application control utility:C# PDF Page Delete Library: remove PDF pages in C#.net, ASP.NET
C#.NET PDF Library - Delete PDF Document Page in C#.NET. Provide C# Users in C#.NET. How to delete a single page from a PDF document.
www.rasteredge.com
1756-6.5.3 - December 1999
Troubleshooting
12-3
ControlNet Network Status Indicators
• steady - indicator is on continuously in the defined state.
• alternating - the two indicators alternate between the two defined states 
at the same time (applies to both indicators viewed together). The two 
indicators are always in opposite states, out of phase.
• flashing - the indicator alternates between the two defined states (applies 
to each indicator viewed independent of the other). If both indicators are 
flashing, they must flash together, in phase.
Green or 
Flashing 
Green
BPRX
ERR
Too many CRC errors being 
generated by the multicast 
backplane receiver, so the 
backplane multicast receivers 
have been shut off.
Cycle power on the module or send 
a reset to the module. If condition 
persists, replace the module. 
(This error is caused by a module 
hardware fault or noisy backplane.) 
KPR
ERR
The configured keeper object 
within the module is unable to 
operate on the attached 
network.
1. Verify that this module is 
attached to the correct network.
2. Rerun RSNetworx on this network         
to update the module’s keeper 
object.
BW
XCED
Module is receiving too much 
network traffic and 
connections are timing out. 
The network bandwidth has 
been exceeded.
None required (temporary 
condition).
If this happens frequently, add 
another 1756-CNB or -CNBR and 
split the traffic between them.
SW
ERR
Module’s network address has 
been changed since module 
power-up.
1. Optional, see page.)
Turn chassis power supply off.
2. Remove the module from the 
chassis.
3. Set the network address 
switches to a unique address 
(01-99).
4. Install the module in the chassis.
5. If off, turn chassis power supply 
on.
Flashing 
Green
NET
ERR
Network cabling error or no 
other nodes on network.
Re-check your network cabling and 
make sure another node on the 
network is active (online).
Cause
Action
Off
No power
None or power up.
Steady red
Faulted unit
Cycle power or reset unit
If fault persists, contact A-B 
representative or distributor.
Alternating 
red/green
Self-test
None
LED
Display
Cause
Action
OK
and
A
B
application control utility:C# PDF Page Insert Library: insert pages into PDF file in C#.net
page processing functions, such as how to merge PDF document files by C# code, how to rotate PDF document page, how to delete PDF page using C# .NET, how to
www.rasteredge.com
application control utility:C# PDF File & Page Process Library SDK for C#.net, ASP.NET, MVC
Page Process. File: Merge, Append PDF Files. File: Split PDF Document. File: Compress PDF. Page: Create Thumbnails. Page: Insert PDF Pages. Page: Delete Existing
www.rasteredge.com
1756-6.5.3 - December 1999
12-4
Troubleshooting
Alternating red/off Incorrect node configuration Check network address and other 
ControlNet configuration 
parameters.
Off
Channel disabled
Program network for redundant 
media, if required.
Steady green
Normal operation
None.
Flashing green/off Temporary errors 
None; unit will self-correct.
Node is not configured to go 
on line
Make sure the Keeper node is 
present and working
.
(1)
Flashing red/off
Media fault 
Check media for broken cables, 
loose connectors, missing 
terminators, etc.
No other nodes present on 
network
Add other nodes to the network.
Flashing red/green Incorrect network 
configuration
Cycle power or reset unit.
If fault persists, contact A-B 
representative or distributor.
(1)
The Keeper node is the node responsible for distributing ControlNet configuration data to 
all nodes on the network.
Cause
Action
and
A
B
application control utility:VB.NET PDF Page Insert Library: insert pages into PDF file in vb.
Easy to Use VB.NET APIs to Add a New Blank Page to PDF Document in VB.NET Program. DLLs for Adding Page into PDF Document in VB.NET Class.
www.rasteredge.com
application control utility:VB.NET PDF File & Page Process Library SDK for vb.net, ASP.NET
document. If you find certain page in your PDF document is unnecessary, you may want to delete this page directly. Moreover, when
www.rasteredge.com
1756-6.5.3 - December 1999
Appendix A
Allocating Communication Connections
What This Appendix Contains
This appendix describes how to determine the connection requirements for 
a ControlLogix system.
How the ControlLogix System 
Uses Connections
The ControlLogix system uses a connection to establish a communication 
link between two devices. This includes Logix5550 controllers, 
communication modules, input/output modules, produced/consumed tags, 
and messages. Connections take many forms:
• Logix5550 controller direct to local I/O or local communication module
• Logix5550 controller direct to remote I/O or remote communication 
module
• Logix5550 controller to remote chassis (rack optimized)
• produced and consumed tags
• messaging, including block-transfers
You indirectly determine the number of connections that the Logix5550 
controller requires by configuring the controller to communicate with other 
devices in the system.
Each module in the ControlLogix system supports a limited number of 
active connections. Take these connection limits into account when 
designing your system.
For information about
See page
How the ControlLogix system uses connections
A-1
Determining I/O connection requirements
A-2
Determining connections for produced and 
consumed tags
A-6
Determining connections for messaging
A-8
Determining total connection requirements
A-9
application control utility:C# PDF metadata Library: add, remove, update PDF metadata in C#.
C#.NET PDF SDK - Edit PDF Document Metadata in C#.NET. Allow C# Developers to Read, Add, Edit, Update and Delete PDF Metadata in .NET Project.
www.rasteredge.com
application control utility:VB.NET PDF delete text library: delete, remove text from PDF file
187.0F) Dim aChar As PDFTextCharacter = textMgr.SelectChar(page, cursor) ' delete a selected As String = Program.RootPath + "\\" output.pdf" doc.Save
www.rasteredge.com
1756-6.5.3 - December 1999
A-2
Allocating Communication Connections
These modules support the following number of connections:
Determining Connections
for I/O Modules
All I/O modules can have a direct, bidirectional connection to the 
Logix5550 controller. A 1756-CNB ControlNet interface module supports 
the ability to organize a chassis of digital I/O modules into one bidirectional 
connection (rack connection), rather than requiring a direct bidirectional 
connection for each individual I/O module.
You can configure these types of connections to these modules:
Direct connections for I/O modules
A direct connection is a real-time, data transfer link between the Logix5550 
controller and an I/O module. The Logix5550 controller maintains and 
monitors the connection between the controller and the I/O module. Any 
break in the connection, such as a module fault or the removal of a module 
from the chassis while under power, causes the controller to set fault status 
bits in the data area associated with the module.
If a Logix5550 controller has a module configuration that references a slot 
in the control system, the controller periodically checks for the presence of 
a device in that slot. When a device’s presence is detected there, the 
controller automatically sends the module configuration.
Device
Description
Connections
1756-L1
Logix5550 Controller
250 connections
1756 I/O modules
ControlLogix I/O modules
16 connections
1756-CNB
1756-CNBR
ControlLogix ControlNet 
Interface module
64 connections
1756-ENET
ControlLogix Ethernet Bridge
64 TCP/IP connections
48 ControlLogix connections maximum per 1 TCP/IP connection
128 ControlLogix connections maximum per module
The Ethernet module also supports 128 in and 128 out 
unscheduled ControlLogix connections. Unscheduled connections 
within a TCP/IP connection do not count toward the total of 48 
possible ControlLogix connections.
1756-DHRIO
ControlLogix DH+ Bridge and 
Remote I/O Scanner
32 connections per DH+ channel
32 rack connections and 16 block-transfer connections per 
remote I/O channel
1756-DNB
ControlLogix DeviceNet Bridge
2 connections
A Logix5550 connection to
Can use this connection type
local I/O
direct connection only
remote I/O
direct connection
or
rack optimized connection
1756-6.5.3 - December 1999
Allocating Communication Connections
A-3
If the module configuration is appropriate for the I/O module found in the 
slot, a connection is made and operation begins. If the module configuration 
is not appropriate, the connection is rejected. You can view the fault 
message on the Connection tab of the module’s properties. Module 
configuration can be inappropriate for any of a number of reasons (for 
example, a mismatch in electronic keying that prevents normal operation).
In this example, the owner controller has three direct connections with I/O 
modules in the remote chassis.    
The local controller in this example uses these bidirectional connections:
When you select the communication format for the I/O module, the owner 
and listen-only formats are direct connections.
Rack optimized connections for I/O modules
When a digital I/O module is located in a remote chassis (with respect to its 
owner), you can select rack optimized communication. A rack optimized 
connection consolidates connection usage between the owner and the digital 
I/O in the remote chassis. Rather than having individual, direct connections 
for each I/O module, there is one connection for the entire chassis.
Using Direct Connections with I/O in a Remote Chassis
Owner Logix 5550
ControlNet
Slot 1 RPI = 5mS
Slot 2 RPI = 50mS
Slot 3 RPI = 25mS
ControlNet
Local chassis
Remote chassis
I
N
P
U
T
I
N
P
U
T
O
U
T
P
U
T
ControlNet
I
N
P
U
T
O
U
T
P
U
T
Interface module
Interface Module
Controller
Connection Type
Module Quantity
Connections 
per Module
Total 
Connections
Logix5550 controller to local I/O module
2
1
2
Logix5550 controller to remote I/O module
3
1
3
Logix5550 controller to remote 1756-CNB module
1
1
1
Total
6
1756-6.5.3 - December 1999
A-4
Allocating Communication Connections
In this example, the owner controller communicates with all the digital I/O 
in the remote chassis but uses only one connection. The data from all three 
modules is sent together simultaneously at a rate specified by the 
1756-CNB connection. This option eliminates the need for the three 
separate connections shown in the previous example. 
The local controller in this example uses these bidirectional connections:
The rack optimized connection conserves ControlNet connections and 
bandwidth, but it limits the status and diagnostic information that is 
available from the I/O modules.
Using a Rack Optimized Connection with I/O in a Remote Chassis
Local chassis
Remote chassis
I
N
P
U
T
I
N
P
U
T
O
U
T
P
U
T
Rack optimized 
connection for all I/O
ControlNet
41021
I
N
P
U
T
O
U
T
P
U
T
Owner Logix 5550
ControlNet
ControlNet
Interface module
Interface Module
Controller
Connection Type
Module Quantity
Connections 
per Module
Total 
Connections
Logix5550 controller to local I/O module
2
1
2
Logix5550 controller to remote 1756-CNB module
1
1
1
total
3
1756-6.5.3 - December 1999
Allocating Communication Connections
A-5
To configure an I/O module for a rack optimized connection, you select the 
Rack Optimization communication format. Most discrete I/O modules 
support a rack optimized connection. If this option does not appear when 
you are selecting communication format for an I/O module, the module 
does not support the rack optimized connection.
Combining direct and rack optimized connections
A remote chassis can have both a rack optimized connection and direct 
connections to analog or digital I/O. In this example, the owner controller 
uses a rack optimized connection to communicate with two digital I/O 
modules. The owner controller also uses a direct connection to 
communicate with an analog module in the same chassis.
Select Rack Optimized for a 
rack connection
Using a Rack Optimized Connection and a Direct Connection with I/O in a Remote Chassis
Local chassis
Remote chassis
I
N
P
U
T
A
N
A
L
O
G
O
U
T
P
U
T
ControlNet
41030
Rack optimized 
connection
Slot 3 RPI = 25mS
I
N
P
U
T
O
U
T
P
U
T
Owner Logix 5550
ControlNet
ControlNet
Interface module
Interface Module
Controller
1756-6.5.3 - December 1999
A-6
Allocating Communication Connections
The local controller in this example uses these bidirectional connections:
Determining Connections for 
Produced and Consumed Tags
The Logix5550 controller supports the ability to produce (broadcast) and 
consume (receive) system-shared tags. System-shared data is accessible by 
multiple controllers over the ControlBus backplane or over a ControlNet 
network. Produced and consumed tags each require connections.
Connections for produced tags
By default, a produced tag allows two other controllers to consume the tag, 
which means that as many as two controllers can simultaneously receive the 
tag data. The local controller (producing) must have one unidirectional 
connection for each consumer and one more unidirectional connection for 
the produced tag. The default produced tag requires three unidirectional 
connections.
You define the number of consumers through the Tag Properties.
As you increase the number of controllers that can consume a produced tag, 
you also reduce the number of connections the controller has available for 
other operations, like communications and I/O.
Connection Type
Module Quantity
Connections 
per Module
Total 
Connections
Logix5550 controller to local I/O module
2
1
2
Logix5550 controller to remote analog I/O module
1
1
1
Logix5550 controller to remote 1756-CNB module
1
1
1
total
4
specify the maximum number of 
consumers for this produced tag
Documents you may be interested
Documents you may be interested