1756-6.5.3 - December 1999
ControlNet Communication Basics
1-7
Understanding the Network 
Keeper
Every ControlNet network requires at least one module that is able to store 
programmed parameters for the network and configure the network with 
those parameters upon start-up. This module is called a “keeper” since it 
keeps the network configuration. The keeper is configured by running 
RSNetWorx for ControlNet software.
Series B 1756-CNB modules (firmware version 2.10) are multi-keepers. On 
a multi-keeper network, any CNB module can keep the network at any legal 
node address (01 to 99). In a multi-keeper network, the multi-keeper 
capable node with the lowest node address becomes the active keeper.
If the active keeper is taken off the network, an alternative keeper can take 
over for it and continue to act as keeper. As long as at least one valid 
multi-keeper device is present on the network, new scheduled connections 
can be established.
Network Update Time (NUT)
The network update time (NUT) is the smallest repetitive time interval in 
which data can be sent on the ControlNet network. It represents the fastest 
possible update rate for scheduled data transfers on that network. For 
example, a network that runs with a 5ms NUT cannot send scheduled data 
at a rate faster than 5ms. It can, however, send data at a slower rate.
Requested Packet Interval (RPI)
The RPI is the update rate specified for a particular piece of data on the 
network. When you add a module to the I/O configuration of a controller, 
you must enter the RPI as a parameter. This value specifies how often to 
produce the data for that module. For example, if you specify an RPI of 
50ms, it means that every 50ms the I/O module should send its data to the 
controller or that the controller should send its data to the I/O module.
When you run RSNetWorx for ControlNet an Actual Packet Interval (API) 
will be calculated. The API will be equal to or faster than the RPI.
RPIs are only used for modules that produce data. For example a local CNB 
module does not require an RPI because it is not a data-producing member 
of the system; it is used only as a bridge to remote racks.
Important:You cannot set the RPI to a rate faster than the NUT. The 
network cannot send data at a rate that is faster than NUT.
Delete pages from pdf - control SDK system:C# PDF Page Extract Library: copy, paste, cut PDF pages in C#.net, ASP.NET, MVC, Ajax, WinForms, WPF
Easy to Use C# Code to Extract PDF Pages, Copy Pages from One PDF File and Paste into Others
www.rasteredge.com
Delete pages from pdf - control SDK system:VB.NET PDF Page Extract Library: copy, paste, cut PDF pages in vb.net, ASP.NET, MVC, Ajax, WinForms, WPF
Detailed VB.NET Guide for Extracting Pages from Microsoft PDF Doc
www.rasteredge.com
1756-6.5.3 - December 1999
1-8
ControlNet Communication Basics
Actual Packet Interval (API)
The API is the actual update rate for a particular piece of data on the 
network. ControlNet will set this rate equal to or faster than the RPI, based 
upon the binary multiple of the NUT which is the next fastest rate at which 
a module can send data. If this can not be done, ControlNet will provide 
feedback that the configuration can not be supported. 
Understanding the Effect of the NUT on the API
The following example illustrates how the NUT affects the API. A module 
on the network can produce data only at binary multiples of the NUT to a 
maximum of the NUT multiplied by 128. These multiples are referred to as 
“rates” on ControlNet. Therefore, in the example of a NUT of 5 ms, the 
module can send data at the following rates:
:
In our example, if you specify an RPI of 25ms, then the network produces 
an API of 20ms, which is the next fastest rate at which the module can send 
data. The module places the data on the network at every fourth network 
update interval to produce the 20ms API. Similarly, if you specify an RPI of 
150ms, the network produces an API of 80ms.
Rack Optimized and Direct Connections
A direct connection is a real-time data transfer link between the controller 
and the device that occupies the slot that the configuration data references. 
A rack optimized connection is a grouping of data from more than one I/O 
module into a single block of data sent over a single connection.
Rack optimized connections reduce the total number of connections needed 
to transfer data when using many I/O modules in a system. The following 
example illustrates the benefit of rack optimized connections.
With this 
NUT
And this 
multiple
The module can send 
data at this rate
5ms
1
5 ms
2
10 ms
4
20 ms
8
40 ms
16
80 ms
32
160 ms
64
320 ms
128
640 ms
control SDK system:VB.NET PDF Page Delete Library: remove PDF pages in vb.net, ASP.
doc.Save(outPutFilePath). How to VB.NET: Delete Consecutive Pages from PDF. doc.Save(outPutFilePath). How to VB.NET: Delete Specified Pages from PDF.
www.rasteredge.com
control SDK system:C# PDF Page Delete Library: remove PDF pages in C#.net, ASP.NET
doc.Save(outPutFilePath); Demo Code: How to Delete Consecutive Pages from PDF in C#.NET. Demo Code: How to Delete Specified Pages from PDF in C#.NET.
www.rasteredge.com
1756-6.5.3 - December 1999
ControlNet Communication Basics
1-9
Assume you have set up a system that contains 10 discrete I/O modules in a 
remote ControlNet chassis. If you used direct connections to transfer data to 
each of the these I/O modules, you would need 11 connections to transfer all 
of the data (one connection to the communication module and 1 connection 
to each of the ten I/O modules). If you used a rack-optimized connection to 
transfer the data, you would only need a single connection – the connection 
to the communication module. Since the 1756-CNB module is limited to 64 
connections, using rack-optimized connections can save valuable resources.
Important:Although rack optimized connections offer an efficient way to 
use resources, there are a few limitations on their use:
• You can only use rack optimized connections to send data 
to and from discrete digital I/O modules. Analog I/O 
requires direct connections.
• Rack optimized connections can contain I/O data and status 
information only. Additional module information, such as 
diagnostics, is not available through a rack-optimized 
connection.
• You must use a consistent RPI for all data in a single 
rack-optimized connection. Since you are using a single 
connection to send the data, all of the data will be 
transferred in the same message at a uniform rate.
Mixing Communication Formats
When multiple I/O modules exist in the same chassis, the user can mix 
Comm Formats for the different I/O modules. I/O modules set up to use 
Rack Optimization will communicate at the rate of the RPI configured for 
the 1756-CNB module. I/O modules configured for direct communication 
will communicate at their set RPI and ignore the CNB RPI.
Important:After the proper I/O configuration is set up in RSLogix5000, 
I/O communication on ControlNet is not established until 
RSNetWorx for ControlNet software is run. RSNetWorx is used 
to set up the network parameters of a ControlNet network.
See Appendix A for more information on connections.
control SDK system:C# PDF File & Page Process Library SDK for C#.net, ASP.NET, MVC
C# view PDF online, C# convert PDF to tiff, C# read PDF, C# convert PDF to text, C# extract PDF pages, C# comment annotate PDF, C# delete PDF pages, C# convert
www.rasteredge.com
control SDK system:C# PDF Page Insert Library: insert pages into PDF file in C#.net
how to merge PDF document files by C# code, how to rotate PDF document page, how to delete PDF page using C# .NET, how to reorganize PDF document pages and how
www.rasteredge.com
1756-6.5.3 - December 1999
1-10
ControlNet Communication Basics
Default Parameters
When a ControlNet network is powered on for the first time, it comes up 
with a default set of ControlNet parameters capable of sending only 
unscheduled data. The default set of network parameters in the 1756-CNB, 
as well as all ControlNet devices, is:
• Network Update Time (NUT) of 100ms
• Scheduled Maximum Node Address (SMAX) of 0
The SMAX is the highest network address of a node that can use the 
scheduled service.
• Unscheduled Maximum Node Address (UMAX) of 99
The UMAX is the highest network address of a node that can 
communicate on the ControlNet network. The UMAX must be set equal 
to or higher than the SMAX.
• Assumed maximum cable lengths and maximum number of repeaters
With this default ControlNet network, you can communicate between the 
various devices on the network by using such packages as RSNetWorx for 
ControlNet, RSLogix5000, and the ControlLogix Gateway Tool 
(1756-GTWY).
If used in this default state, optimum performance may not be achieved. 
However, the default network can be commissioned (tuned) for optimum 
performance, as described later in this manual.
Important:The ControlNet network should be configured using 
RSNetWorx for ControlNet to improve performance.
At a minimum, we recommend that the Unscheduled Maximum 
Node Address (UMAX) be set equal to the highest node 
address on the network. Leaving this parameter at the default 
value of 99 will waste bandwidth and reduce system 
performance.
We also recommend setting the Scheduled Maximum Node 
Address (SMAX) to a value 3 or 4 above the highest scheduled 
node address to allow for future expandability.
control SDK system:VB.NET PDF Page Insert Library: insert pages into PDF file in vb.
Page: Insert PDF Pages. |. Home ›› XDoc.PDF ›› VB.NET PDF: Insert PDF Page. Add and Insert Multiple PDF Pages to PDF Document Using VB.
www.rasteredge.com
control SDK system:VB.NET PDF delete text library: delete, remove text from PDF file
VB.NET PDF - How to Delete Text from PDF File in VB.NET. VB.NET Programming Guide to Delete Text from PDF File Using XDoc.PDF SDK for VB.NET.
www.rasteredge.com
1756-6.5.3 - December 1999
Chapter 2
Installing the ControlNet Network
What this Chapter Contains
This chapter describes how to install the ControlLogix and PLC-5C 
modules and connect them to the ControlNet network.
For information about
See page
Installing the 1784-KTCX15 Communication Interface Card
2-2
Installing the ControlLogix Modules
2-5
Connecting the ControlNet Network
2-7
Installing the PLC-5C Controllers
2-7
!
ATTENTION:  The ControlLogix network 
modules are sensitive to electrostatic discharge. 
Electrostatic discharge can damage integrated 
circuits or semiconductors if you touch backplane 
connector pins. Follow these guidelines when you 
handle these components:
• Touch a grounded object to discharge static 
potential.
• Wear an approved wrist-strap grounding device.
• Do not touch the backplane connector or 
connector pins.
• Do not touch the circuit components.
• If available, use a static-safe workstation.
• When not in use, store the modules in their 
static-shield bags.
control SDK system:C# Word - Delete Word Document Page in C#.NET
doc.Save(outPutFilePath); Delete Consecutive Pages from Word in C#. int[] detelePageindexes = new int[] { 1, 3, 5, 7, 9 }; // Delete pages.
www.rasteredge.com
control SDK system:C# PDF metadata Library: add, remove, update PDF metadata in C#.
Allow C# Developers to Read, Add, Edit, Update and Delete PDF Metadata in .NET Project. Remove and delete metadata from PDF file.
www.rasteredge.com
1756-6.5.3 - December 1999
2-2
Installing the ControlNet Network
Installing the 1784-KTCX15 
Communication Interface Card
Perform the following steps to install the 1784-KTCX15 card in your 
personal computer.
1. Set the card’s base memory address location on switches S1 and S2.
2. Set the card’s base I/O space address location on switch S3.
We used the following settings:
Important:When deciding which addresses to use, remember that each 
card in your computer must have a unique base memory 
address and a unique base I/O space memory address. If 
another card in the host computer is using one or both of the 
selected addresses, you must change the card’s switch settings 
to an available address.
3. Insert the card in a vacant 16- or 32-bit ISA/EISA expansion slot.
For detailed information on 
installing the 1784-KTCX15, 
refer to the ControlNet 
Communication Interface 
Card Installation Instructions, 
publication number 
1784-5.33.
Base I/O Space Address
240
Base Memory Address
D000:000
Address 240
Consult with your IT/PC support group to find out if it is necessary to 
change any of your computer’s memory address or IRQ settings. 
1756-6.5.3 - December 1999
Installing the ControlNet Network
2-3
Configuring the 1784-KTCX15 Card
After installing the card in the computer, you must run RSLinx to configure 
the driver.
1. Start the RSLinx software.
2. Select Configure Drivers from the Communications menu.
The following window will appear: 
3. Select the Allen-Bradley 1784-KT/KTC(X) device from the pull-down 
list and click on Add/New.
4. When prompted for a name for the new driver, select the default name 
assigned by the system, i.e., AB_KTC-1.
For more information on installing and using RSLinx see the RSLinx Lite 
User’s Guide, publication 9399-WAB32LUG.
1756-6.5.3 - December 1999
2-4
Installing the ControlNet Network
The Configure Device window will appear:
5. Enter the following configuration:
6. Click on OK to save your settings.
7. Close RSLinx.
Station Name
ABKTC
Net. Address
17
(1)
(1)
This is an unscheduled device. For maximum 
efficiency, set its address higher than the highest 
scheduled address on your network.
Interrupt
None
I/O Base
240
(2)
(2)
Modify as necessary for your system.
Mem. Address
D7
(2)
1756-6.5.3 - December 1999
Installing the ControlNet Network
2-5
Installing the ControlLogix 
Modules
Important:These instructions assume that you have installed your 
ControlLogix chassis and power supplies. If you have not 
installed these components, install them now in accordance 
with the following instructions:
• ControlLogix Chassis Installation Instructions, 
publication number 1756-5.2
• ControlLogix Power Supplies Installation Instructions, 
publication number 1756-5.1
1. Before installing a 1756-CNB module in its chassis, set the module’s 
node address switches.
Important:You must select a unique node address of 01 to 99 for each 
module. 00 is invalid.
For the example applications, set the node address of one 1756-CNB 
module to 1 and another to 6. In the last example (chapter 11), we added 
a third module at node address 3.
20926
top of CNB module
front of module
side of CNB module
This module’s 
network address is 23.
front
1756-6.5.3 - December 1999
2-6
Installing the ControlNet Network
2. Install the1756-CNB modules, Logix5550 controllers, and ControlLogix 
I/O modules by placing them in the formed tracks on the top and bottom 
of the selected slots and sliding them into the chassis.
Press firmly and evenly to seat a module in the backplane 
connector.
!
ATTENTION:  Do not force a module into the 
backplane connector. If you cannot seat the module 
with firm pressure, check the alignment. Forcing 
the module can damage the backplane connector or 
the module.