1756-6.5.3 - December 1999
Installing the ControlNet Network
2-7
Important:You can install or remove a module while chassis power is 
applied.
Connecting the ControlNet 
Network
Connect the 1756-CNB modules and the 1784-KTCX15 communication 
interface card to the ControlNet network using taps (1786-TPS, -TPYS, 
-TPR, -TPYR).
1. Remove and save the dust cap(s) from the ControlNet tap(s)
.
!
ATTENTION:  When you insert or remove a module 
while backplane power is on, an electrical arc may 
occur. An electrical arc can cause personal injury or 
property damage by:
• sending an erroneous signal to your system’s field 
devices causing unintended machine motion or loss 
of process control.
• causing an explosion in a hazardous environment.
Repeated electrical arcing causes excessive wear to 
contacts on both the module and its mating connectors. 
Worn contacts may create electrical resistance that can 
affect module operation.
When connecting a 
ControlNet network, you 
should also refer to the 
ControlNet Cable System 
Planning and Installation 
Manual, publication number 
1786-6.2.1.
!
ATTENTION:  Do not allow any metal portions of the 
tap to contact any conductive material. If you 
disconnect the tap from the module, place the dust cap 
back on the connector to prevent the connector from 
accidentally contacting a metallic grounded surface.
segment 1
segment 2
dust cap
dust cap
1756-CNB - segment 1
1756-CNBR - segments 1 and 2
Delete page from pdf - application Library utility:C# PDF Page Extract Library: copy, paste, cut PDF pages in C#.net, ASP.NET, MVC, Ajax, WinForms, WPF
Easy to Use C# Code to Extract PDF Pages, Copy Pages from One PDF File and Paste into Others
www.rasteredge.com
Delete page from pdf - application Library utility:VB.NET PDF Page Extract Library: copy, paste, cut PDF pages in vb.net, ASP.NET, MVC, Ajax, WinForms, WPF
Detailed VB.NET Guide for Extracting Pages from Microsoft PDF Doc
www.rasteredge.com
1756-6.5.3 - December 1999
2-8
Installing the ControlNet Network
2. Connect the tap’s straight or right angle connector to the module’s BNC 
connector.
.
If your node supports
Connect the tap’s connector
non-redundant media 
(1756-CNB, -CNBR)
to the channel A connectors
(channel B is not used)
redundant media (1756-CNBR)
from trunkline A to channel A
from trunkline B to channel B
Tap
segment 2
tap
tap
tap
segment 1
segment 1
20956
application Library utility:VB.NET PDF Page Delete Library: remove PDF pages in vb.net, ASP.
Home ›› XDoc.PDF ›› VB.NET PDF: Delete PDF Page. This page is aimed to help you learn how to delete page from your PDF document in VB.NET application.
www.rasteredge.com
application Library utility:C# PDF Page Delete Library: remove PDF pages in C#.net, ASP.NET
Pages. |. Home ›› XDoc.PDF ›› C# PDF: Delete PDF Page. Demo Code: How to Delete a Single PDF Page from PDF File in C#.NET. How
www.rasteredge.com
1756-6.5.3 - December 1999
Installing the ControlNet Network
2-9
Installing the PLC-5C 
Controllers
Install the PLC-5C controller in a 1771 I/O chassis. 
1. Set the backplane switches in the I/O chassis so that you can download 
the ladder logic programs in the example applications. Put switches 5 
and 6 in the “on” position, and all of the others in the “off” position.
2. Set the PLC-5C ControlNet node addresses using the two 10-digit rotary 
switches on top of the PLC-5C modules.
For the example applications use node addresses 11 and 16.
3. Insert the PLC-5C into the 1771 chassis.
4. Connect the PLC-5C’s ControlNet port to the ControlNet network.
See the ControlNet 1.5 PLC-5 Programmable Controller User 
Manual, publication 1785-6.5.22, for further information.
Card Guides
Battery
Battery
Battery
PLC-5/40C Controller
Lift Ejector Tab
Locking Bar
Connector
Cover
ControlNet Node Address Switches
PLC-5C Controller and 1771 I/O Chassis
1
2
3
4
5
6
7
8
OPEN
Switches 5 and 6 “on”
ControlNet PLC-5C controller’s NET address = 11
30
40
50
60
70
80
90
00
10
20
3
4
5
6
7
8
9
0
1
2
30
40
50
60
70
80
90
00
10
20
application Library utility:C# PDF File & Page Process Library SDK for C#.net, ASP.NET, MVC
C# File: Merge PDF; C# File: Split PDF; C# Page: Insert PDF pages; C# Page: Delete PDF pages; C# Read: PDF Text Extract; C# Read: PDF
www.rasteredge.com
application Library utility:C# PDF Page Insert Library: insert pages into PDF file in C#.net
page processing functions, such as how to merge PDF document files by C# code, how to rotate PDF document page, how to delete PDF page using C# .NET, how to
www.rasteredge.com
1756-6.5.3 - December 1999
2-10
Installing the ControlNet Network
The following figure shows an example of a completed ControlNet network 
used for the examples in chapters 5 and 6 of this manual.
Required Software
In order to run the example applications, you will need RSNetworx for 
ControlNet, RSLogix5, and RSLogix5000 software installed on your 
personal computer. Refer to the System Components table on page P-3 for 
information on which versions of the software are required. Follow the 
instructions that appear on your screen when installing the software.
For further information, refer to the publications listed on page P-5.
ControlNet Trunk Cable
Logix5550
1756-CNB
PLC-5C
ControlLogix
Chassis
1771 I/O
Chassis
PC with
1784-KTCX15
Interface 
Controller
tap
tap with end
terminator
tap with end
terminator
application Library utility:VB.NET PDF Page Insert Library: insert pages into PDF file in vb.
PDF: Insert PDF Page. VB.NET PDF - How to Insert a New Page to PDF in VB.NET. Easy to Use VB.NET APIs to Add a New Blank Page to PDF Document in VB.NET Program.
www.rasteredge.com
application Library utility:C# PDF remove image library: remove, delete images from PDF in C#.
C# File: Merge PDF; C# File: Split PDF; C# Page: Insert PDF pages; C# Page: Delete PDF pages; C# Read: PDF Text Extract; C# Read: PDF
www.rasteredge.com
1756-6.5.3 - December 1999
Chapter 3
Logix5550 to Logix5550 Controller: 
Unscheduled Messaging
About the Example Application
This example application sends an unscheduled message from one 
Logix5550 controller to another Logix5550 controller. Both controllers are 
on the same ControlNet but in different chassis. In both chassis the 
controller is in slot 0 and the 1756-CNB module is in slot 1. The 1756-CNB 
modules are configured at node addresses 1 and 6, respectively. A Timer 
provides the test data for the message.
Set Up the Example Application
Change your system configuration to that shown below:
What you will do
See page
Set Up the Example Application
3-1
Create the Example Application
3-2
Create the Controller Tags for the Write Message Program
3-3
Create the Write Message Ladder Program
3-4
Download and Run the Program
3-6
Test the Example Application
3-6
Create the Controller Tags for the Test Program
3-7
Download the Test Program
3-9
Test the Communications
3-10
ControlNet Network
Logix5550
1756-CNB
(Node 1)
1756-CNB
(Node 6)
Logix5550
Left
Chassis
Right
Chassis
PC with
1784-KTCX15
Interface 
Message
Slot  0    1
Slot  0    1
application Library utility:VB.NET PDF delete text library: delete, remove text from PDF file
VB.NET: Delete a Character in PDF Page. It demonstrates how to delete a character in the first page of sample PDF file with the location of (123F, 187F).
www.rasteredge.com
application Library utility:VB.NET PDF remove image library: remove, delete images from PDF in
C# File: Split PDF; C# Page: Insert PDF pages; C# Page: Delete PDF pages; C# Read: PDF Text Extract; Delete image objects in selected PDF page in ASPX webpage.
www.rasteredge.com
1756-6.5.3 - December 1999
3-2
Logix5550 to Logix5550 Controller: Unscheduled Messaging
• Verify that the Logix5550 controllers and the 1756-CNB modules are in 
slots 0 and 1 in each ControlLogix chassis, as shown. 
• Verify that the node addresses for the 1756-CNB modules are 1 and 6 as 
shown.
• Verify that the KTCX15 driver card is configured as described on 
page 2-3.
• Verify that all wiring and cabling is properly connected.
Create the Example Application
Perform the following steps to create the example application.
1. Open the RSLogix5000 software.
2. From the File menu, select New. The New Controller window will 
appear.
3. Enter an appropriate name for the Controller, e.g., “CNET_Messaging.”
4. Select the correct Chassis TypeSlot Number of the Logix5550 
controller, and folder where you want to save the file (Create In). Click 
on OK.
application Library utility:C# PDF delete text Library: delete, remove text from PDF file in
C#.NET Sample Code: Delete Text from Specified PDF Page. The following demo code will show how to delete text in specified PDF page. // Open a document.
www.rasteredge.com
application Library utility:C# PDF metadata Library: add, remove, update PDF metadata in C#.
Allow C# Developers to Read, Add, Edit, Update and Delete PDF Metadata in .NET Project. Remove and delete metadata from PDF file.
www.rasteredge.com
1756-6.5.3 - December 1999
Logix5550 to Logix5550 Controller: Unscheduled Messaging
3-3
Create the Controller Tags for the Write Message Program
1. Double-click on the Controller Tags folder in the project window.
The Controller Tags window will appear.
2. Select the Edit Tags tab and create the following tags:
Tag Name
Alias For
Base Tag
Type
Style
L1_to_L1
MESSAGE
Source_data_buffer
T1.ACC
T1.ACC
DINT
Decimal
T1
TIMER
1756-6.5.3 - December 1999
3-4
Logix5550 to Logix5550 Controller: Unscheduled Messaging
Create the Write Message Ladder Program
1. Double-click on Main Routine under the Main Program folder, and 
create the following ladder program:
2. Click on the  button in the MSG instruction.
The Message Configuration window will appear.
3. Under the Configuration tab, enter the following configuration:
Important:Make sure the Destination Element tag is created in the other 
controller with the same name (“destination_data_buffer”) and 
data type. The tag must be created under the Controller scope.
In this field
Select
Message Type
CIP Data Table Write
Source Tag
Source_data_buffer
Number of Elements
1
Destination Element
destination_data_buffer
1756-6.5.3 - December 1999
Logix5550 to Logix5550 Controller: Unscheduled Messaging
3-5
4. Select the Communication tab and enter the following path to the 
destination Logix5550 controller:  1, 1, 2, 6, 1, 0.
5. Click on OK
6. Save the program.
For the path in this example:
“1” indicates a connection to the backplane of 
the left ControlLogix chassis.
“1” indicates a connection to the CNB module 
in slot 1.
“2” indicates a connection to port 2 of the CNB 
module (get on the ControlNet wire).
“6” indicates a connection to the CNB module 
at node address 6.
“1” indicates a connection to the backplane of 
the right ControlLogix chassis.
“0” indicates a connection to the Logix5550 
controller in slot 0.
If the Cache Connections option is selected, the controller keeps the 
connection open after it completes the data transfer. The next data transfer 
uses the open connection and avoids the delay required to open the 
connection. If this option is not selected, the controller closes the 
connection after the data transfer operation is complete. Selecting the option 
results in faster data transfers, but indefinitely retains a connection. Since 
the controller has a limited number of connections, this could eventually 
result in the controller being unable to establish connections.
1756-6.5.3 - December 1999
3-6
Logix5550 to Logix5550 Controller: Unscheduled Messaging
Download and Run the Program
(1)
1. Click on the Communications menu and select Who Active.
2. The Who Active window will appear (Your window may look different 
depending upon the drivers and other devices you have installed).
3. Drill down the tree through the ControlNet driver and the 1756-CNB 
module at node 1 to the controller in slot 0.
4. Highlight the controller and click on the Download button.
5. Put the controller in Run mode.
6. Minimize RSLogix5000.
Test the Example Application
In order to test the application you have to go online with the Logix5550 
controller in the right chassis and create the tag for a buffer to receive the 
message. 
Perform the following steps:
1. Start another session of RSLogix5000.
2. From the File menu, select New.
(1)
This example uses RSLogix5000 version 2.25. See Appendix D if you are using version 2.10 or earlier.