1756-6.5.3 - December 1999
Logix5550 to Logix5550 Controller: Scheduled Communication
4-17
4. Select the AB_KTC-1, ControlNet driver and click on OK.
The software will browse the network. When it is finished, your network 
window should appear similar to that shown below:
5. Verify that the devices shown and the network node addresses displayed 
are correct.
Verify the Network Properties
Make sure that the network update time (NUT), Max Scheduled Address, 
and Max Unscheduled Address are set correctly.
1. Select Network from the main menu bar and Properties from the 
pull-down menu:
Extract pages from pdf file online - control SDK system:C# PDF Page Extract Library: copy, paste, cut PDF pages in C#.net, ASP.NET, MVC, Ajax, WinForms, WPF
Easy to Use C# Code to Extract PDF Pages, Copy Pages from One PDF File and Paste into Others
www.rasteredge.com
Extract pages from pdf file online - control SDK system:VB.NET PDF Page Extract Library: copy, paste, cut PDF pages in vb.net, ASP.NET, MVC, Ajax, WinForms, WPF
Detailed VB.NET Guide for Extracting Pages from Microsoft PDF Doc
www.rasteredge.com
1756-6.5.3 - December 1999
4-18
Logix5550 to Logix5550 Controller: Scheduled Communication
2. Make sure that these parameters to are set to the following values:
3. Click on OK.
Next, have RSNetWorx for ControlNet survey the network for all 
connected devices.
4. From Selection menu, select Survey Network.
RSNetWorx for ControlNet will survey the network for connected 
devices. When it is finished, the network window should appear similar 
to that shown below.
5. From the Network menu, select Save as.
In this field
Select
Network_Update_Time (ms)
5 ms
(1)
(1)
Remember that the requested packet interval (RPI) for any of the devices on the network 
cannot be faster than the NUT.
Max Scheduled Address
10
(2)
(2)
This should be set to a value 3 or 4 above the highest scheduled node on the network, in this 
case the 1756-CNB module at node 6.
Max Unscheduled Address
20
(3)
(3)
At a minimum, this should be set to the highest node address on the network, in this case 
the 1784-KTXC15 card at node 17.
1
control SDK system:C# PDF File & Page Process Library SDK for C#.net, ASP.NET, MVC
File: Merge PDF; C# File: Split PDF; C# Page: Insert PDF pages; C# Page: Delete PDF pages; C# Read: PDF Text Extract; C# Read: PDF
www.rasteredge.com
control SDK system:C# PDF Text Extract Library: extract text content from PDF file in
to C#: Extract Text Content from PDF File. textMgr = PDFTextHandler.ExportPDFTextManager( doc); // Extract text content for text extraction from all PDF pages.
www.rasteredge.com
1756-6.5.3 - December 1999
Logix5550 to Logix5550 Controller: Scheduled Communication
4-19
The following pop-up window will appear:
6. Select “Optimize and re-write schedule for all connections” and click on 
OK.
The Save As window will appear
7. Enter an appropriate name for the network (e.g., “Sched_L1_to_L1”) 
and click on Save.
RSNetWorx for ControlNet will save the configured and scheduled 
network.
8. Minimize the RSNetWorx for ControlNet software.
control SDK system:VB.NET PDF Text Extract Library: extract text content from PDF
advanced PDF Add-On, developers are able to extract target text content from source PDF document and save extracted text to other file formats through
www.rasteredge.com
control SDK system:C# PDF Page Insert Library: insert pages into PDF file in C#.net
Offer PDF page break inserting function. Free components and online source codes for .NET framework 2.0+. Add and Insert Blank Pages to PDF File in C#.NET.
www.rasteredge.com
1756-6.5.3 - December 1999
4-20
Logix5550 to Logix5550 Controller: Scheduled Communication
Test the Communications
1. Restore the session of RSLogix5000 for the Consumer controller.
2. Double-click on the Controller Tags folder in the Controller view 
window and select the Monitor Tags tab.
3. Examine the consumed_data field. You should see the value changing 
to keep up with the accumulated value of the timer in the controller in 
the left chassis.
This completes the Logix5550 controller to Logix5550 scheduled 
communication example.
You should see this value changing.
control SDK system:VB.NET PDF Page Insert Library: insert pages into PDF file in vb.
to create a blank PDF page with related by using following online VB.NET may use the following VB.NET demo code to insert multiple pages of a PDF file to a
www.rasteredge.com
control SDK system:C# PDF File Split Library: Split, seperate PDF into multiple files
splitting PDF file into two or multiple files online. Support to break a large PDF file into smaller files. Separate PDF file into single ones with defined pages
www.rasteredge.com
1756-6.5.3 - December 1999
Chapter 5
Logix5550 Controller to PLC-5C:
Unscheduled Messaging 
About the Example Application
This example application sends an unscheduled message from a Logix5550 
processor to a PLC-5C processor. The Logix5550 processor is in slot 0 of 
the ControlLogix chassis and the1756-CNB module (configured as node 1) 
is in slot 1. The PLC-5C is configured as ControlNet node 11. A Counter 
that increments continuously provides the test data for the message.
Set Up the Example Application
Change your system configuration to that shown below:
• Verify that the Logix5550 processor and the 1756-CNB module are in 
slots 0 and 1 as shown. 
• Verify that the node address for the 1756-CNB module is 1 and the node 
address for the PLC-5C processor is 11 as shown.
What you will do
See page
Set Up the Example Application
5-1
Create the Example Application
5-2
Create the Controller Tags for the Write Message Program
5-3
Create the Write Message Ladder Program
5-4
Download the Write Message Program
5-6
Test the Example Application
5-7
ControlNet Network
Logix5550
1756-CNB
(Node 1)
PLC-5C
ControlLogix
Chassis
1771 I/O
Chassis
PC with
1784-KTCX15
Interface 
Message
Slot  0    1
(Node 11)
Processor
control SDK system:C# PDF Image Extract Library: Select, copy, paste PDF images in C#
Extract various types of image from PDF file, like XObject Image, XObject Form, Inline Image, etc. Extract image from PDF free in .NET framework
www.rasteredge.com
control SDK system:VB.NET PDF Image Extract Library: Select, copy, paste PDF images
Online source codes for quick evaluation in VB.NET class. By using RsterEdge XDoc PDF SDK for .NET, VB.NET users are able to extract image from PDF page or file
www.rasteredge.com
1756-6.5.3 - December 1999
5-2
Logix5550 Controller to PLC-5C: Unscheduled Messaging
• Verify that the KTCX15 driver card is configured as described on 
page 2-3.
• Verify that all wiring and cabling is properly connected.
Create the Example Application
Perform the following steps to create the example application:
1. Open the RSLogix5000 software.
2. From the File menu, select New. The New Controller pop-up window 
will appear.
3. Enter an appropriate name for the Controller, e.g., “CNET_Messaging.”
4. Select the correct Chassis TypeSlot Number of the Logix5550 
processor, and folder where you want to save the file (Create In). Click 
on OK.
1756-6.5.3 - December 1999
Logix5550 Controller to PLC-5C: Unscheduled Messaging
5-3
Create the Controller Tags for the Write Message Program
You must create a source tag for the message under the controller scope and 
assign it the same data type as the destination element (e.g., INT).
1. Double-click on the Controller Tags folder in the Project window.
The Controller Tags window will appear.
2. Select the Edit Tags tab and create the following tags:
Tag
Alias For
Type
Style
SUM
INT
Decimal
PLUS_ONE
INT
Decimal
L1_to_PLC5
MESSAGE
Mssg_to_PLC5
SUM
INT
Decimal
1756-6.5.3 - December 1999
5-4
Logix5550 Controller to PLC-5C: Unscheduled Messaging
3. Select the Monitor Tags tab.
4. Enter a 1 in the PLUS_ONE field.
Create the Write Message Ladder Program
1. Double-click on Main Routine under the Main Program folder, and 
enter the following ladder program:
2. Click on the  button in the MSG instruction.
1756-6.5.3 - December 1999
Logix5550 Controller to PLC-5C: Unscheduled Messaging
5-5
The Message Configuration window will appear.
3. Under the Configuration tab, enter the following configuration:
4. Select the Communication tab and enter the following path to the 
PLC-5C on ControlNet.
5. In the Communication Method area, click on the CIP radio button.
In this field
Select
Message Type
PLC5 Typed Write
Source Tag
Mssg_to_PLC5
Number of Elements
1
Destination Element
N7:0
For the path in this example:
“1” indicates a connection to the backplane of 
the ControlLogix chassis.
“1” indicates a connection to the CNB module 
in slot 1.
“2” indicates a connection to port 2 of the CNB 
module (get on the ControlNet wire).
“11” indicates a connection to the PLC-5C at 
node 11.
1756-6.5.3 - December 1999
5-6
Logix5550 Controller to PLC-5C: Unscheduled Messaging
6. Click on OK.
7. Save the program.
Download the Write Message Program
(1)
1. Click on the Communications menu and select Who Active.
2. The Who Active window will appear (Your window may look different 
depending upon the drivers and other devices you have installed).
3. Drill down the tree through ControlNet driver and the 1756-CNB 
module at node 1 to the controller in slot 0.
4. Highlight the controller and click on the Download button.
5. Put the controller into Run mode.
6. Minimize RSLogix5000.
If the Cache Connections option is selected, the controller keeps the 
connection open after it completes the data transfer. The next data transfer 
uses the open connection and avoids the delay required to open the 
connection. If this option is not selected, the controller closes the 
connection after the data transfer operation is complete. Selecting the option 
results in faster data transfers, but indefinitely retains a connection. Since 
the controller has a limited number of connections, this could eventually 
result in the controller being unable to establish connections.
(1)