APPENDIX 4 PROCESSING MX Sheet 
This section explains the processing of MX Sheet. 
Appendix 4.1 Collection Delay and Data Dropout 
On MX Sheet, collection delay, data dropout or similar problem may occur depending 
on the communication time with the PLC and the collection timing of device data. 
The following explains the collection delay and data dropout. 
(1)  Collection delay 
Device data collection delay will occur depending on the communication time 
with the PLC and the corresponding processing time. 
Collection delay occurs only when "Operation time" is set to "Regular interval". 
When a collection delay occurs, it will be registered to the ErrorLog sheet as error 
information. 
When a collection delay occurs, check the ErrorLog sheet. 
The following explains the cases where a collection delay occurs. 
(a)  When the actual communication time is longer than the 
specified operation interval 
When the communication time with the PLC is longer than the operation 
interval of MX Sheet, a device data collection delay occurs. 
(Example) "Operation time" is set to "Regular interval (3s)" but the communication time with the PLC is 5s
Time
Communication 
time: 5s
Since communication 
time is longer, actual 
operation interval is 5s.
3s
2s waiting time 
occurs.
Operation interval 
set to 3s
Find and replace text in pdf file - search text inside PDF file in C#.net, ASP.NET, MVC, Ajax, WinForms, WPF
Learn how to search text in PDF document and obtain text content and location information
pdf find highlighted text; how to select all text in pdf
Find and replace text in pdf file - VB.NET PDF Text Search Library: search text inside PDF file in vb.net, ASP.NET, MVC, Ajax, WinForms, WPF
Learn How to Search Text in PDF Document and Obtain Text Content and Location Information in VB.NET application
select text in pdf reader; convert a scanned pdf to searchable text
APP - 6                                                                                                                                                      APP - 6 
MELSOFT
APPENDICES 
(b)  Collection delay when device trigger function is used 
When the sum of the device trigger condition check time and the 
communication time with PLC is longer than the operation interval of MX 
Sheet, a collection delay occurs during the next device trigger condition 
check. 
(Example) When "B0" = "When ON" has been set as the device trigger condition (operation interval is 3s)
Time
Time necessary for communication: 5s
3s
1)
2)
1) Device trigger condition check time
2) Communication time
B0
OFF
ON
1) + 2) is time necessary 
for communication.
2s waiting time 
occurs.
Operation interval 
set to 3s
(c)  Collection delay when handshake function is used 
When the sum of the requesting device check time, the communication 
time with PLC and the handshake processing time is longer than the 
operation interval of MX Sheet, a collection delay occurs during the next 
requesting device check. 
(Example) When the PLC side requesting device has been set to "M0" and the PC side responding device 
to "M100" (operation interval is 3s)
Time
Time necessary for communication: 5s
3s
1)
2)
1) Requesting device check time
2) Communication time
3) Handshake processing time
M100
OFF
ON
3)
M0
OFF
ON
1) + 2) + 3) is time necessary 
for communication.
2s waiting time 
occurs.
Operation interval 
set to 3s
VB.NET PDF replace text library: replace text in PDF content in vb
and ASP.NET webpage. Find and replace text in PDF file in preview without adobe PDF reader component installed. Able to pull text
how to make a pdf document text searchable; pdf text select tool
VB.NET PDF File Merge Library: Merge, append PDF files in vb.net
project along with sample codes, which you can find in the Demos folder under RasterEdge.Imaging.Demo directory with the file name RasterEdge.Imaging.Demo.PDF.
search pdf documents for text; search text in pdf image
APP - 7                                                                                                                                                      APP - 7 
MELSOFT
APPENDICES 
(2)  Data dropout 
The data to be collected may dropout depending on the communication time with 
the PLC and the collection timing of device data. 
The following explains the cases where a data dropout occurs. 
(a)  When the actual communication time is longer than the 
specified operation interval 
When the communication time with the PLC is longer than the operation 
interval, the data to be collected dropouts. 
If a data dropout has occurred, increase the operation interval setting of MX 
Sheet. 
(Example) When "Operation time" has been set to "Hourly (0min, 1min, 2min)" but the communication
time with the PLC is longer than 1min
If previous data collection is still being executed when it has reached the operation time as 
shown below, a data dropout occurs on MX Sheet.
Time
12:00
12:01
12:02
Communication time: 1min 30s
Since data at 12:00 is 
being collected, data at 
12:01 is not collected.
(b)  Data dropout when device trigger function is used 
When the device trigger condition holds for the specified operation time, the 
condition cannot be checked and the data to be collected dropouts. 
If a data dropout occurs during use of the device trigger, decrease the 
operation interval setting of MX Sheet. 
Time
12:00
12:01
12:02
12:03
Device trigger condition 
is checked at every 
operation time.
B0
OFF
ON
Condition has held but data 
collection is not executed 
since condition does not 
hold for condition check.
Data collection is executed 
when condition holds.
(Example) When "B0" = "When ON" has been set as the device trigger condition
(operation interval is 60s)
If the device trigger condition holds for the specified operation time as shown below,
a data dropout occurs on MX Sheet.
REMARK 
Note that if a data dropout occurs during use of the device trigger, error information 
is not registered to the ErrorLog sheet. 
VB.NET PDF File & Page Process Library SDK for vb.net, ASP.NET
find detailed guidance on creating, loading, merge and splitting PDF pages and Files, adding a page into PDF document, deleting unnecessary page from PDF file
pdf text search tool; find and replace text in pdf file
VB.NET Create PDF Library SDK to convert PDF from other file
Create writable PDF file from text (.txt) file in VB with a demo project, which you can find in the programming, you can use specific APIs to create PDF file.
text searchable pdf; find text in pdf image
APP - 8                                                                                                                                                      APP - 8 
MELSOFT
APPENDICES 
(c)  Data dropout when handshake function is used 
When the requesting device condition holds for the specified operation 
time, the data to be collected dropouts. 
If a data dropout occurs during use of the handshake, decrease the 
operation interval setting of MX Sheet. 
Time
12:00
12:01
12:02
12:03
Requesting device is checked 
at every operation time.
M0
OFF
ON
ON
OFF
M100
Data collection is executed 
when requesting device 
condition holds.
Requesting device condition 
has held but data collection 
is not executed since 
condition does not hold 
for condition check.
(Example) When the PLC side requesting device has been set to "M0" and the PC side responding 
device to "M100" (operation interval is 60s)
If the requesting device condition holds for the operation time as shown below, 
a data dropout occurs on MX Sheet.
REMARK 
Note that if a data dropout occurs during use of the handshake, error information is 
not registered to the ErrorLog sheet. 
C# PDF File Permission Library: add, remove, update PDF file
Text: Replace Text in PDF. Image: Insert Image to PDF. Image: Remove read PDF, VB.NET convert PDF to text, VB.NET the following code table, you will find a piece
convert pdf to searchable text; pdf make text searchable
VB.NET PDF File Permission Library: add, remove, update PDF file
Text to PDF. Text: Delete Text from PDF. Text: Replace Text in PDF. NET rotate PDF pages, C#.NET search text in PDF In the following code table, you will find a VB
find text in pdf files; search pdf files for text programmatically
APP - 9                                                                                                                                                      APP - 9 
MELSOFT
APPENDICES 
(3)  Data dropout when modem communication function is used 
When modem communication function is used and "Telephone line connectivity 
time zone" is set for "Connect each time depending on the operation interval", a 
data dropout occurs due to use of a modem. 
To collect PLC device data using modem communication function, set MX Sheet 
while considering the modem connection time. 
If a data dropout occurs during modem communication, increase the operation 
interval setting of MX Sheet. 
Time
As operation interval, 
set time longer than 
sum of 1) + 2) + 3).
1) Time to connect to modem
2) Communication time
3) Time to disconnect from modem
1)
2)
3)
Time necessary for modem 
communication
Operation interval
Appendix 4.2 Date and Time 
When the logging function and CSV logging are used, the date and time in the cell 
area and the CSV file may not be displayed correctly. 
The following describes an example of the incorrect display, the causes and corrective 
actions. 
<Example (when "Regular interval" is set to 1s)>
Although communication is made at the specified interval,  the date and time are not displayed correctly as shown
below, since the time when data has been  actually read exceeds the regular interval.
(Unlike with collection delay, the error information is not displayed in the ErrorLog sheet.)
<Corrective actions>
Decrease the number of cells set to the Excel book.
Increase the "Regular interval" setting.
Reexamine the cell area settings. (Refer to APPENDIX 5.)
Time of 13:08:27 is incorrectly
displayed as 13:08:28.
<Causes>
Multiple cell areas have been set to the Excel book.
Multiple cell areas use the same communication path.
"Operation time" of the <<Operation Interval>> tab has been set to "Regular interval". 
C# HTML5 PDF Viewer SDK deployment on Visual Studio .NET
C#.NET rotate PDF pages, C#.NET search text in PDF, C# Unzip the download package and you can find a project Once done debugging with x86 dlls, replace the x86
search text in multiple pdf; text select tool pdf
VB.NET PDF - Deploy VB.NET HTML5 PDF Viewer on Visual Studio.NET
C#.NET rotate PDF pages, C#.NET search text in PDF, C# Unzip the download package and you can find a project Once done debugging with x86 dlls, replace the x86
pdf searchable text converter; how to make a pdf file text searchable
APP - 10                                                                                                                                                      APP - 10 
MELSOFT
APPENDICES 
APPENDIX 5 CREATING THE Excel SHEET FOR MX Sheet 
When collecting/writing device data by using MX Sheet, the efficiency of 
communication with the PLC varies depending on the cell area settings. 
The following provides the example of setting cell area for more effective 
communication. 
(1)  Communication efficiency and cell area specifying method 
When multiple cell areas have been set, MX Sheet executes communication with 
the PLC in order of the cell areas. 
When the same communication path has been set to multiple cell areas, 
communication efficiency decreases since all cell areas use one communication 
path to communicate with the PLC. 
The following setting example indicates the case where the same communication 
path has been set to multiple cell areas. 
<Setting example> 
(a)  Inefficient setting 
When the above setting example is divided into four cell areas as indicated 
in the following table, MX Sheet executes communication four times. This 
causes communication load to increase, decreasing communication 
efficiency. 
Access Data Settings 
Cell Area Name 
Cell Area 
Logical station 
number 
Device setting 
Number of 
cells 
Operation 
Interval 
Product type 
C2 
0: Ethernet 
D0 Character string 
1s interval 
Lot No. 
C3 
0: Ethernet 
D5 Character string 
1s interval 
C5: C7 
0: Ethernet 
D10 16 bit integer 
1s interval 
E5: E7 
0: Ethernet 
D20 16 bit integer 
1s interval 
(b)  Efficient setting 
When the above setting example is integrated into one cell area as 
indicated in the following table, the collection/write of device data is 
completed by making communication once. This enables communication 
load to decrease, improving communication efficiency. 
Access Data Settings 
Cell Area Name 
Cell Area 
Logical station 
number 
Device setting 
Number of 
cells 
Operation 
Interval 
D0 Character string 
D5 Character string 
D10 16 bit integer 
Product information  C2, C3, C5: C7, E5: E7 0: Ethernet 
D20 16 bit integer 
1s interval 
APP - 11                                                                                                                                                      APP - 11 
MELSOFT
APPENDICES 
(2)  Communication efficiency and access data setting 
When one type of device is set as multiple devices, the efficiency of 
communication with the PLC decreases. 
The following setting example indicates the case where one type of device is 
specified consecutively. 
<Setting example> 
(a)  Inefficient setting 
If the above setting example is divided into three access data as indicated 
below, MX Sheet recognizes them as three types of devices and executes 
communication, decreasing communication efficiency. 
(b)  Efficient setting 
If the above setting example is integrated into one access data as indicated 
below, MX Sheet recognizes it as one type of device and executes 
communication, improving communication efficiency. 
REMARK 
Any of the following settings prevents the improvement of communication efficiency 
even if efficient setting has been made. 
(1)  When "Data Type" has been set to "Bit", the device number setting of "Device" is 
not a multiple of 16. 
(2)  CN200 (current value of 32-bit counter device) or later of the FXCPU has been 
set. 
APP - 12                                                                                                                                                      APP - 12 
MELSOFT
APPENDICES 
(3)  Communication efficiency and use of Excel function (cell reference) 
When inconsecutive device data are displayed on Excel, the efficiency of 
communication with the PLC decreases if multiple cell areas are set. 
The following setting example indicates the case where inconsecutive device 
data are displayed on Excel. 
<Setting example> 
(a)  Inefficient setting 
When the above setting example is divided into four cell areas as indicated 
in the following table, MX Sheet executes communication four times. This 
causes communication load to increase, decreasing communication 
efficiency. 
Access Data Settings 
Cell Area Name 
Cell Area 
Logical station 
number 
Device setting 
Number of 
cells 
Operation 
Interval 
Line A 
C3: E3 
0: Ethernet 
D0 16 bit integer 
1s interval 
Line B 
C4: E4 
0: Ethernet 
D5 16 bit integer 
1s interval 
Line C 
C5: E5 
0: Ethernet 
D10 16 bit integer 
1s interval 
Line D 
C6: E6 
0: Ethernet 
D15 16 bit integer 
1s interval 
(b)  Efficient setting 
When the above setting example is integrated into one cell area as 
indicated in the following table and device data are collected in the other 
Excel sheet (Sheet 2), this decreases communication load, improving 
communication efficiency. 
Set cell reference so that Excel sheet 1, which actually displays the device 
data, will refer to the corresponding cells within Excel sheet2, which collects 
the device data. 
(MX Sheet need not be set in the Excel sheet where device data will be 
displayed actually (Sheet 1).) 
Access Data Settings 
Cell Area Name 
Cell Area 
Logical station 
number 
Device setting 
Number of 
cells 
Operation 
Interval 
Line information 
A2: E5 (Area set to Sheet 2)  0: Ethernet 
D0 16 bit integer 
20 
1s interval 
Sheet 1 (Excel sheet where device data will be displayed actually)
Sheet 2 (Excel sheet where device data will be collected)
Set Sheet 1 to refer to cells of Sheet 2.
APP - 13                                                                                                                                                      APP - 13 
MELSOFT
APPENDICES 
APPENDIX 6 PROCEDURE TO TRANSPORT DATA TO OTHER PERSONAL 
COMPUTER 
This section explains the procedure to transport the settings of MX Sheet from a 
development personal computer to an on-site personal computer. 
POINT 
MX Sheet and MX Component must have been installed in the personal computer 
where the settings of MX Sheet will be transported. 
Operation on on-site 
personal computer
Start the Communication Setup Utility and execute the 
export of the communication settings. *2
Copy the following files to the on-site personal computer.
Excel book of MX Sheet
Export file of Communication Setup Utility
Start the Communication Setup Utility and import the export 
file created on the development personal computer. *2
Start the Excel book of MX Sheet and recheck the settings.
Completion
Start *1
Operation on 
development 
personal computer
*1: The Excel book for MX Sheet should have been created on 
the development personal computer.  
*2: For the import and export operations of communication 
settings, refer to the MX Component Operating Manual.
APP - 14                                                                                                                                                      APP - 14 
MELSOFT
APPENDICES 
APPENDIX 7 HTML FILE 
This section explains the HTML file saved during MX Sheet operation. 
(1)  HTML file 
MX Sheet allows an HTML file to be saved automatically into the folder specified 
when any of the following functions is used. 
• Logging function (when cell is full) 
• Alarm summary function (when cell is full) 
• Automatic save setting 
(2)  Convenient use of HTML file 
The data collected by MX Sheet can be snapshot-monitored from a business 
destination, office or other place via the Internet/intranet, with the plant side 
personal computer (personal computer where MX Sheet is operating) used as a 
Web server. 
Internet
Intranet
Plant conditions can be 
snapshot-monitored from 
office and business destination.
Plant
MX Sheet is 
unnecessary.
Web server
HTML file is created 
by automatic save 
function of MX Sheet.
Documents you may be interested
Documents you may be interested