Electrical installation
Notes on project planning
Operation at earth−leakage circuit breaker (e.l.c.b.)
6
101
EDS82EV903   EN   3.0
6.2.3
Operation at earth−leakage circuit breaker (e.l.c.b.)
Danger!
The controllers are internally fitted with a mains rectifier. In case of a short
circuit to frame a pulsating DC residual current can prevent the AC sensitive or
pulse current sensitive earth−leakage circuit breakers from being activated,
thus cancelling the protective function for the entire equipment being
operated on this earth−leakage circuit breaker.
ƒ
For the protection of persons and farm animals (DIN VDE 0100), we recommend
–pulse current sensitive earth−leakage circuit breakers for plants including
controllers with a single−phase mains connection (L1/N).
–universal−current sensitive earth−leakage circuit breakers for plants including
controllers with a three−phase mains connection (L1/L2/L3).
ƒ
Only install the earth−leakage circuit breaker between supplying mains and drive
controller.
ƒ
Earth−leakage circuit breakers may trigger a false alarm due to
–capacitive compensation currents flowing in the cable shields during operation
(particularly with long, shielded motor cables),
–simultaneous connection of several inverters to the mains
–the use of additional interference filters.
ƒ
The specifications for earth−leakage circuit breakers provided in the chapter
"Technical data" apply to low−capacitance, shielded motor cables with a length of 10
m (guide value):
–E82EVxxxKxC without external measures
–E82EVxxxKxC200 with "SD" RFI filter
6.2.4
Interaction with compensation equipment
ƒ
Controllers only consume very little reactive power of the fundamental wave from
the AC supply mains. Therefore, a compensation is not required.
ƒ
If the controllers are connected to a supply system with compensation equipment,
this equipment must comprise chokes.
–For this, contact the supplier of the compensation equipment.
Online pdf image extractor - Select, copy, paste PDF images in C#.net, ASP.NET, MVC, Ajax, WinForms, WPF
Support PDF Image Extraction from a Page, a Region on a Page, and PDF Document
how to extract images from pdf in acrobat; extract image from pdf in
Online pdf image extractor - VB.NET PDF Image Extract Library: Select, copy, paste PDF images in vb.net, ASP.NET, MVC, Ajax, WinForms, WPF
Support PDF Image Extraction from a Page, a Region on a Page, and PDF Document
extract images from pdf c#; extract pictures from pdf
Electrical installation
Notes on project planning
Discharge current for mobile systems
6
102
EDS82EV903  EN  3.0
6.2.5
Discharge current for mobile systems
Frequency inverters with internal or external RFI filters usually have a discharge current to
PE potential that is higher than 3.5 mA AC or 10 mA DC.
Therefore, fixed installation as protection is required (see EN 61800−5−1). This must be
indicated in the operational documents.
If a fixed installation is not possible for a mobile consumer although the discharge current
to  PE  potential  is  higher than 3.5 mA AC or 10  mA DC, an additional two−winding
transformer (isolating transformer) can be included in the current supply as a suitable
countermeasure. Here, the PE conductor is connected to the PEs of the drive (filter, inverter,
motor, shieldings) and also to one of the poles of the secondary winding of the isolating
transformer.
Devices with a three−phase supply must have a corresponding isolating transformer with
a secondary star connection, the star point being connected to the PE conductor.
prim.
sec.
L1
N
PE
L11
L
L2
N1
N
N2
U
V
W
filter
inverter
M
3~
8200vec017
Fig. 6−1
Installation of a two−winding transformer (isolating transformer)
Note!
For controllers in a single−phase power range from 0.25 to 0.55 kW, RFI filters
of type E82ZZxxxxxB220 (version: "LL"; low leakage) are available. Hence, the
controller and the filter generate a leakage current < 3.5 mA AC or < 10 mA DC,
respectively.
VB.NET TIFF: TIFF Text Extractor SDK; Extract Text Content from
In this online tutorial, we will offer you information on Standalone VB.NET TIFF text extractor SDK that extracts control SDK into VB.NET image application by
extract pdf pages to jpg; extract text from pdf image
VB.NET PowerPoint: Extract & Collect PPT Slide(s) Using VB Sample
Divided in following several aspects, this VB.NET online tutorial page provide powerful & profession imaging controls, PDF document, image to pdf files and
how to extract images from pdf file; extract color image from pdf in c#
Electrical installation
Notes on project planning
Optimisation of the controller and mains load
6
103
EDS82EV903   EN   3.0
6.2.6
Optimisation of the controller and mains load
A mains choke is an inductance which can be included in the mains cable of the frequency
inverter. As a result, the load of the supplying mains and the controller is optimised:
ƒ
Reduced system perturbation: The curved shape of the mains current approaches a
sinusoidal shape.
ƒ
Reduced mains current: The effective mains current is reduced, i.e. the mains, cable,
and fuse loads are reduced.
ƒ
Increased service life of the controller: The electrolytic capacitors in the DC bus have
a considerably increased service life due to the reduced AC current load.
There are no restrictions for the combinations of mains chokes and RFI filters and/or motor
filters. Alternatively, a mains filter can be used (combination of mains choke and RFI filter
in a common housing).
Note!
ƒ
Some controllers must generally be operated with a mains choke or a mains
filter.
ƒ
Some controller variants have a factory−set RFI filter (EMC filter) or mains
filter. Additional mains chokes or filters must not be used in conjunction
with a mains filter.
ƒ
During operation with a mains choke or a mains filter, the maximally
possible output voltage does not reach the mains voltage value (typical
voltage drop at the rated point: 4 ... 6 %).
VB.NET Word: Extract Word Pages, DOCX Page Extraction SDK
this VB.NET Word page extractor add-on can be also used to merge / split Word file, add / delete Word page, sort Word page order or insert image into Word page
extract photo from pdf; extract text from image pdf file
VB.NET TIFF: TIFF to Text (TXT) Converter SDK; Convert TIFF to
From this online tutorial page, you will find information on to interpret and decode TIFF image file powerful & profession imaging controls, PDF document, tiff
how to extract pictures from pdf files; pdf image text extractor
Electrical installation
Notes on project planning
Reduction of noise emissions
6
104
EDS82EV903  EN  3.0
6.2.7
Reduction of noise emissions
Due to internal switching operations, every controller causes noise emissions which may
interfere with the functions of other consumers. Depending on the site of the frequency
inverter, European standard EN 61800−3 defines limit values for these noise emissions:
Limit class C2: Limit class C2 is often required for industrial mains which are isolated from
the mains of residential areas.
Limit class C1: If the controller is operated in a residential area, it may interfere with other
devices such as radio and television receivers. Here, interference suppression measures
according to limit class C1 are often required.
Limit class C1 is much more strict than limit class C2. Limit class C1 includes limit class C2.
For compliance with limit class C1 / C2, corresponding measures for the limitation of noise
emissions are required, e.g. the use of RFI filters.
There are no restrictions for the combinations of RFI filters and mains chokes and/or motor
filters. Alternatively, a mains filter can be used (combination of mains choke and RFI filter
in a common housing).
The selection of the frequency inverter and the corresponding filters, if applicable, always
depends on the application in question and is determined by e.g. the switching frequency
of the controller, the motor cable length, or the protective circuit (e.g. earth−leakage circuit
breakers).
Note!
ƒ
Some controllers must generally be operated with a mains choke or a mains
filter.
ƒ
Some controller variants have a factory−set RFI filter (EMC filter) or mains
filter. Additional mains chokes or filters must not be used in conjunction
with a mains filter.
ƒ
During operation with a mains choke or a mains filter, the maximally
possible output voltage does not reach the mains voltage value (typical
voltage drop at the rated point: 4 ... 6 %).
C# Word: How to Extract Text from C# Word in .NET Project
you can rest assured because this Word text extractor preserves both to provide powerful & profession imaging controls, PDF document, image to pdf files and
extract images from pdf acrobat; extract jpg pdf
Electrical installation
Notes on project planning
Reduction of noise emissions
6
105
EDS82EV903   EN   3.0
The illustration below shows the permissible motor cable length depending on the filter
type for compliance with limit classes C2 and C1. The stated permissible motor cable
lengths may  vary  depending on  the  used  motor  cable,  controller  and  its switching
frequency.
E82ZZxxxxxB2001) 2)
E82ZZxxxxxB210
1)
E82ZZxxxxxB220
1)
E82ZZxxxxxB230
E82ZNxxxxxB230
1)
1)
(f = 2/4/8 kHz)
(f = 2/4/8 kHz)
ch
ch
E82ZZxxxxxB230
E82ZNxxxxxB230
1)
1)
(f = 16 kHz)
(f = 16 kHz)
ch
ch
EZN3A...
10
20
30
40
50
10
l [m]
mot
C2
E82ZZxxxxxB200
1) 2)
E82ZZxxxxxB210
1)
E82ZZxxxxxB220
1)
E82ZZxxxxxB230
E82ZNxxxxxB230
1)
1)
(f = 2/4/8 kHz)
(f = 2/4/8 kHz)
ch
ch
EZN3B...
10
20
30
40
50
10
l [m]
mot
C1
8200vec032
Fig. 6−2
Permissible motor cable lengths1) depending on the filter type for compliance with limit class C2 or
C1
1) Use low−capacitance cables
2) RFI filters are suitable for operation on 30 mA earth−leakage circuit breaker (guide value: motor cable length = 10 m)
Electrical installation
Notes on project planning
Mains choke/mains filter assignment
6
106
EDS82EV903  EN  3.0
6.2.8
Mains choke/mains filter assignment
Operation at rated power on 230 V mains, 1/N/PE
8200 vector
Mains choke
Interference voltage category (EN 61800−3) and motor cable length
Component
Component
Type
Var.
Type
C2
Max. [m]
C1
Max. [m]
E82xV251K2C
0xx
ELN1−0900H005
20
1)
2xx
E82ZZ37112B220
5
E82ZZ37112B220
5
E82ZZ37112B200
20
E82ZZ37112B200
20
E82ZZ37112B210
50
E82ZZ37112B210
50
E82xV371K2C
0xx
ELN1−0900H005
20
1)
2xx
E82ZZ37112B220
5
E82ZZ37112B220
5
E82ZZ37112B200
20
E82ZZ37112B200
20
E82ZZ37112B210
50
E82ZZ37112B210
50
E82xV551K2C
0xx
ELN1−0500H009
20
1)
2xx
E82ZZ75112B220
5
E82ZZ75112B220
5
E82ZZ75112B200
20
E82ZZ75112B200
20
E82ZZ75112B210
50
E82ZZ75112B210
50
E82xV751K2C
0xx
ELN1−0500H009
20
1)
2xx
E82ZZ75112B200
20
E82ZZ75112B200
20
E82ZZ75112B210
50
E82ZZ75112B210
50
E82xV152K2C
0xx
ELN1−0250H018
20
1)
2xx
E82ZZ22212B200
20
E82ZZ22212B200
20
E82ZZ22212B210
50
E82ZZ22212B210
50
E82xV222K2C
0xx
ELN1−0250H018
20
1)
2xx
E82ZZ22212B200
20
E82ZZ22212B200
20
E82ZZ22212B210
50
E82ZZ22212B210
50
1)
The motor cable length depends on the inverter type and the switching frequency
Electrical installation
Notes on project planning
Mains choke/mains filter assignment
6
107
EDS82EV903   EN   3.0
Operation with rated power at the 230V mains, 3/PE
8200 vector
Mains choke
Interference voltage category (EN 61800−3) and motor cable length
Component
Component
Type
Var.
Type
C2
Max. [m]
C1
Max. [m]
E82xV551K2C
0xx
E82ZL75132B
20
1)
2xx
E82ZZ75132B200
20
E82ZZ75132B200
20
E82ZZ75132B210
50
E82ZZ75132B210
50
E82xV751K2C
0xx
E82ZL75132B
20
1)
2xx
E82ZZ75132B200
20
E82ZZ75132B200
20
E82ZZ75132B210
50
E82ZZ75132B210
50
E82xV152K2C
0xx
E82ZL22232B
20
1)
2xx
E82ZZ22232B200
20
E82ZZ22232B200
20
E82ZZ22232B210
50
E82ZZ22232B210
50
E82xV222K2C
0xx
E82ZL22232B
20
1)
2xx
E82ZZ22232B200
20
E82ZZ22232B200
20
E82ZZ22232B210
50
E82ZZ22232B210
50
E82xV302K2C
0xx
ELN3−0120H017
20
1)
2xx
E82ZZ40232B200
20
E82ZZ40232B200
20
E82ZZ40232B210
50
E82ZZ40232B210
50
E82xV402K2C
0xx
ELN3−0120H017
20
1)
2xx
E82ZZ40232B200
20
E82ZZ40232B200
20
E82ZZ40232B210
50
E82ZZ40232B210
50
E82xV552K2C
0xx
ELN3−0120H025
20
1)
2xx
E82ZZ75232B200
20
E82ZZ75232B200
20
E82ZZ75232B210
50
E82ZZ75232B210
50
E82xV752K2C
0xx
ELN3−0088H035
20
1)
2xx
E82ZZ75232B200
20
E82ZZ75232B200
20
E82ZZ75232B210
50
E82ZZ75232B210
50
1)
The motor cable length depends on the inverter type and the switching frequency
Electrical installation
Notes on project planning
Mains choke/mains filter assignment
6
108
EDS82EV903  EN  3.0
Operation at rated power on 400/500 V mains, 3/PE
8200 vector
Mains choke
Interference voltage category (EN 61800−3) and motor cable length
Component
Component
Type
Var.
Type
C2
Max. [m]
C1
Max. [m]
E82xV551K4C
0xx
ELN3−1500H003−001
20
1)
2xx
E82ZZ75134B200
20
E82ZZ75134B200
20
E82ZZ75134B210
50
E82ZZ75134B210
50
E82xV751K4C
0xx
ELN3−1500H003−001
20
1)
2xx
E82ZZ75134B200
20
E82ZZ75134B200
20
E82ZZ75134B210
50
E82ZZ75134B210
50
E82xV152K4C
0xx
ELN3−0680H006−001
20
1)
2xx
E82ZZ22234B200
20
E82ZZ22234B200
20
E82ZZ22234B210
50
E82ZZ22234B210
50
E82xV222K4C
0xx
ELN3−0680H006−001
20
1)
2xx
E82ZZ22234B200
20
E82ZZ22234B200
20
E82ZZ22234B210
50
E82ZZ22234B210
50
E82xV302K4C
0xx
ELN3−0500H007−001
20
1)
2xx
E82ZZ55234B200
20
E82ZZ55234B200
20
E82ZZ55234B210
50
E82ZZ55234B210
50
E82xV402K4C
0xx
ELN3−0250H013−001
20
1)
2xx
E82ZZ55234B200
20
E82ZZ55234B200
20
E82ZZ55234B210
50
E82ZZ55234B210
50
E82xV552K4C
0xx
ELN3−0250H013−001
20
1)
2xx
E82ZZ55234B200
20
E82ZZ55234B200
20
E82ZZ55234B210
50
E82ZZ55234B210
50
E82xV752K4C
0xx
ELN3−0120H017−001
20
1)
2xx
E82ZZ11334B200
20
E82ZZ11334B200
20
E82ZZ11334B210
50
E82ZZ11334B210
50
E82xV113K4C
0xx
ELN3−0150H024−001
20
1)
2xx
E82ZZ11334B200
20
E82ZZ11334B200
20
E82ZZ11334B210
50
E82ZZ11334B210
50
E82xV153K4B
2xx
ELN3−0088H035−001
EZN3A0110H030
25
EZN3B0110H030 2)
EZN3B0110H030U 3)
50
E82ZN22334B230
50
10
5)
E82ZN22334B230
10
0
5)
E82ZZ15334B230
50
10
5)
E82ZZ15334B230
10
0
5)
3xx
50
10
E82xV223K4B
2xx
ELN3−0075H045
EZN3A0080H042
25
EZN3B0080H042
50
E82ZN22334B230
50
10
5)
E82ZN22334B230
10
0
5)
3xx
50
10
E82xV303K4B
2xx
ELN3−0055H055
EZN3A0055H060
25
EZN3B0055H060
50
E82ZN30334B230
50
10
5)
E82ZN30334B230
10
0
5)
3xx
50
10
E82xV453K4B
2xx
ELN3−0038H085
EZN3A0037H090
25
EZN3B0037H090
50
E82ZN45334B230
50
10
5)
E82ZN45334B230
10
0
5)
3xx
50
10
Electrical installation
Notes on project planning
Mains choke/mains filter assignment
6
109
EDS82EV903   EN   3.0
Interference voltage category (EN 61800−3) and motor cable length
Mains choke
8200 vector
Component
Component
Mains choke
8200 vector
Max. [m]
C1
Max. [m]
C2
Type
Var.
Type
E82xV553K4B
2xx
ELN3−0027H105
EZN3A0030H110
EZN3A0030H110N001
4)
25
EZN3B0030H110
50
E82ZN55334B230
50
10
5)
E82ZN55334B230
10
0
5)
3xx
50
10
E82xV753K4B
2xx
ELN3−0022H130
EZN3A0022H150
25
EZN3B0022H150
50
E82ZN75334B230
50
10
5)
E82ZN75334B230
10
0
5)
3xx
50
10
E82xV903K4B
2xx
ELN3−0017H170
EZN3A0017H200
25
EZN3B0017H200
50
E82ZN90334B230
50
10
5)
E82ZN90334B230
10
0
5)
3xx
50
10
1)
The motor cable length depends on the inverter type and the switching frequency
2)
Side−mounted filter
3)
Footprint filter
4)
For E82DV553K4B (push−through technique)
5)
at switching frequency f
ch
= 16 kHz; the interference voltage category C1 cannot be achieved
Electrical installation
Notes on project planning
Mains choke/mains filter assignment
6
110
EDS82EV903  EN  3.0
Operation at increased rated power on 230 V mains, 1/N/PE
8200 vector
Mains choke
Interference voltage category (EN 61800−3) and motor cable length
Component
Component
Type
Var.
Type
C2
Max. [m]
C1
Max. [m]
E82xV251K2C
0xx
ELN1−0900H005
20
1)
2xx
E82ZZ37112B220
5
E82ZZ37112B220
5
E82ZZ37112B200
20
E82ZZ37112B200
20
E82ZZ37112B210
50
E82ZZ37112B210
50
E82xV551K2C
0xx
ELN1−0500H009
20
1)
2xx
E82ZZ75112B220
5
E82ZZ75112B220
5
E82ZZ75112B200
20
E82ZZ75112B200
20
E82ZZ75112B210
50
E82ZZ75112B210
50
E82xV751K2C
0xx
ELN1−0500H009
20
1)
2xx
E82ZZ75112B200
20
E82ZZ75112B200
20
E82ZZ75112B210
50
E82ZZ75112B210
50
E82xV152K2C
0xx
ELN1−0250H018
20
1)
2xx
E82ZZ22212B200
20
E82ZZ22212B200
20
E82ZZ22212B210
50
E82ZZ22212B210
50
1)
The motor cable length depends on the inverter type and the switching frequency
Operation at increased rated power on 230 V mains, 3/PE
8200 vector
Mains choke
Interference voltage category (EN 61800−3) and motor cable length
Component
Component
Type
Var.
Type
C2
Max. [m]
C1
Max. [m]
E82xV551K2C
0xx
E82ZL75132B
20
1)
2xx
E82ZZ75132B200
20
E82ZZ75132B200
20
E82ZZ75132B210
50
E82ZZ75132B210
50
E82xV751K2C
0xx
E82ZL75132B
20
1)
2xx
E82ZZ75132B200
20
E82ZZ75132B200
20
E82ZZ75132B210
50
E82ZZ75132B210
50
E82xV152K2C
0xx
E82ZL22232B
20
1)
2xx
E82ZZ22232B200
20
E82ZZ22232B200
20
E82ZZ22232B210
50
E82ZZ22232B210
50
E82xV302K2C
0xx
ELN3−0120H017
20
1)
2xx
E82ZZ40232B200
20
E82ZZ40232B200
20
E82ZZ40232B210
50
E82ZZ40232B210
50
E82xV552K2C
0xx
ELN3−0088H035−001
20
1)
2xx
E82ZZ75232B200
20
E82ZZ75232B200
20
E82ZZ75232B210
50
E82ZZ75232B210
50
1)
The motor cable length depends on the inverter type and the switching frequency