Electrical installation
Notes on project planning
Mains choke/mains filter assignment
6
111
EDS82EV903   EN   3.0
Operation at increased rated power on 400/500 V mains, 3/PE
8200 vector
Mains choke
Interference voltage category (EN 61800−3) and motor cable length
Component
Component
Type
Var.
Type
C2
Max. [m]
C1
Max. [m]
E82xV551K4C
0xx
EZN3A1500H003−001
20
1)
2xx
E82ZZ75134B200
20
E82ZZ75134B200
20
E82ZZ75134B210
50
E82ZZ75134B210
50
E82xV751K4C
0xx
EZN3A1500H003−001
20
1)
2xx
E82ZZ75134B200
20
E82ZZ75134B200
20
E82ZZ75134B210
50
E82ZZ75134B210
50
E82xV222K4C
0xx
ELN3−0680H006−001
20
1)
2xx
E82ZZ22234B200
20
E82ZZ22234B200
20
E82ZZ22234B210
50
E82ZZ22234B210
50
E82xV302K4C
0xx
ELN3−0500H007−001
20
1)
2xx
E82ZZ55234B200
20
E82ZZ55234B200
20
E82ZZ55234B210
50
E82ZZ55234B210
50
E82xV402K4C
0xx
ELN3−0250H013−001
20
1)
2xx
E82ZZ55234B200
20
E82ZZ55234B200
20
E82ZZ55234B210
50
E82ZZ55234B210
50
E82xV752K4C
0xx
ELN3−0150H024−001
20
1)
2xx
E82ZZ11334B200
20
E82ZZ11334B200
20
E82ZZ11334B210
50
E82ZZ11334B210
50
E82xV153K4B
2xx
ELN3−0075H045
EZN3A0080H042
25
EZN3B0080H042
50
E82ZN22334B230
50
E82ZN22334B230
10
3xx
50
10
E82xV223K4B
2xx
ELN3−0055H055
EZN3A0055H060
25
EZN3B0055H060
50
E82ZN30334B230
50
E82ZN30334B230
10
3xx
50
10
E82xV303K4B
2xx
EZN3B0055H060N003
50
3xx
50
10
E82xV453K4B
2xx
ELN3−0027H105
EZN3A0030H110
EZN3A0030H110N0014)
25
EZN3B0030H110
50
E82ZN55334B230
50
10
5)
E82ZN55334B230
10
0
5)
3xx
50
10
E82xV553K4B
2xx
ELN3−0022H130
EZN3A0030H110
EZN3A0030H110N001
4)
25
10
3xx
50
10
E82xV753K4B
2xx
ELN3−0017H170
EZN3A0017H200
25
EZN3B0017H200
50
E82ZN90334B230
50
10
5)
E82ZN90334B230
10
0
5)
3xx
50
10
E82xV903K4B
2xx
ELN3−0014H200
EZN3A0017H200
25
EZN3B0017H200
50
3xx
50
10
1)
The motor cable length depends on the inverter type and the switching frequency
4)
For E82DV553K4B (push−through technique)
5)
at switching frequency f
ch
= 16 kHz; the interference voltage category C1 cannot be achieved
Extract text from pdf image - Select, copy, paste PDF images in C#.net, ASP.NET, MVC, Ajax, WinForms, WPF
Support PDF Image Extraction from a Page, a Region on a Page, and PDF Document
pdf image extractor c#; some pdf image extractor
Extract text from pdf image - VB.NET PDF Image Extract Library: Select, copy, paste PDF images in vb.net, ASP.NET, MVC, Ajax, WinForms, WPF
Support PDF Image Extraction from a Page, a Region on a Page, and PDF Document
extract vector image from pdf; extract images pdf
Electrical installation
Notes on project planning
Motor cable
6
112
EDS82EV903  EN  3.0
6.2.9
Motor cable
Specification
ƒ
The used motor cables must
–comply with the requirements that apply to the site of installation (e.g.
EN 60204−1, UL),
–comply with the following voltage data: EN 0.6/1 kV, UL 600 V.
ƒ
For shielded motor cables only use cables with braid made of tinned or nickel−plated
copper. Shields made of steel braid are not suitable.
–The overlap rate of the braid must be at least 70 % with an overlap angle of 90°.
ƒ
Use low−capacitance motor cables:
Power class
Capacitance per unit length
Core/core
Core/shield
0.25 ... 2.2 kW
Up to 1.5 mm2 75 pF/m
 150 pF/m
3 ... 11 kW
From 2.5 mm2 100 pF/m
 150 pF/m
15 ... 30 kW
 140 pF/m
 230 pF/m
45 ... 55 kW
 190 pF/m
 320 pF/m
75 ... 90 kW
 250 pF/m
 410 pF/m
Cable length
ƒ
The motor cable must be as short as possible for having a positive effect on the drive
behaviour.
ƒ
For group drives (several motors connected to one drive controller) the resulting
cable length l
res
is the crucial factor:
I
res
[m]  (l
1
l
2
l
3
...l
i
) i
l
x
Length of the individual motor cable
l
res
Resulting length of the motor cable
i
Number of the individual motor cables
ƒ
At rated mains voltage and a switching frequency of 8 kHz and without additional
output filters, the maximum permissible length of the motor cable is as follows:
–50 m shielded
–100 m unshielded
Note!
For compliance with EMC regulations, the permissible cable lengths must be
changed.
C# PDF Text Extract Library: extract text content from PDF file in
Ability to extract highlighted text out of PDF document. Supports text extraction from scanned PDF by using XDoc.PDF for .NET Pro. Image text extraction control
some pdf image extract; extract photos pdf
VB.NET PDF Text Extract Library: extract text content from PDF
Extract highlighted text out of PDF document. Image text extraction control provides text extraction from PDF images and image files.
extract images from pdf file; extract jpg from pdf
Electrical installation
Notes on project planning
Motor cable
6
113
EDS82EV903   EN   3.0
Cable cross−section
Note!
The assignment of the cable cross−sections to the ampacity of the motor
cables was carried out under the following conditions:
ƒ
Compliance with IEC/EN 60204−1 with fixed cable laying
ƒ
Compliance with IEC 60354−2−52, table A.52−5 if the cable is used as part of
a trailing cable
ƒ
Laying system C
ƒ
Ambient temperature 45 °C
ƒ
Continuous operation of the motor with rated current I
rated
If the specifications and conditions differ, the user is responsible for using a
motor cable which complies with the requirements of the real conditions.
Deviations may e.g. be:
ƒ
Laws, standards, national and regional regulations
ƒ
Type of application
ƒ
Motor utilisation
ƒ
Ambient and operating conditions
ƒ
Laying system and bundling of cables
ƒ
Cable type
Motor cable
permanently installed
for trailing cable
Cable cross−section
I
M
[A]
I
M
[A]
[mm2]
[AWG]
10.0
11.8
1.0
18
13.8
17.3
1.5
16
19.1
23.7
2.5
14
25.5
30.9
4.0
12
32.8
41.0
6.0
10
45.5
55.5
10
8
60.1
75.5
16
6
76.4
92.8
25
4
94.6
115
35
2
114
140
50
1
146
179
70
00
177
217
95
000
205
252
120
0000
Note!
Information on the design of the motor cable is provided in the "System cables
and system connectors" manual.
C# PDF insert image Library: insert images into PDF in C#.net, ASP
Free PDF image processing SDK library for Visual Studio .NET program. Powerful .NET PDF image edit control, enable users to insert vector images to PDF file.
extract image from pdf c#; online pdf image extractor
VB.NET PDF insert image library: insert images into PDF in vb.net
VB.NET code to add an image to the inputFilePath As String = Program.RootPath + "\\" 1.pdf" Dim doc New PDFDocument(inputFilePath) ' Get a text manager from
extract color image from pdf in c#; extract images from pdf c#
Electrical installation
Basics for wiring according to EMC
Cable specifications
6
114
EDS82EV903  EN  3.0
6.3
Basics for wiring according to EMC 
6.3.1
Cable specifications
Motor cable design
ƒ
Only use shielded, four−core motor cables (core: U, V, W, PE and outer shield).
ƒ
Cables with a YCY copper braid have a good shielding effect, cables with SY steel
reinforcement are less suitable (high shield resistance).
ƒ
The contact ratio of the braid:
–At least 70 to 80 % with an overlap angle of 90°
ƒ
Use low−capacitance cables to minimise the leakage currents.
–The values depend on the cross−sections of the cables.
ƒ
The rated voltage of the motor cable for inverter operation is V
0
/V = 0.6/1 kV.
The EMC safety of the connection for the motor temperature monitoring depends on the
laying system of the shielded connecting cable.
EMC safety
Laying system
Comment
Excellent
Motor cable and PTC cable
are installed separately
Ideal laying system with very low
interference injections
Treat the PTC cable like a control
cable
Satisfactory
Motor cable and PTC cable
are installed together with
separated shields
Permitted laying system, but higher
interference injections
Unfavourable
Motor cable and PTC cable
are installed together with a
common shield
High−energy interference injections
Cable design for DC supply and brake resistor
ƒ
These DC cables must be designed as the motor cable.
–Shielding
–Rated voltage
–Approval
ƒ
Being relatively short, low−capacity versions are not necessary.
Control cable design
Control cables must be shielded to minimise interference injections. 
C# Create PDF from images Library to convert Jpeg, png images to
If you want to turn PDF file into image file format in C# application, then RasterEdge XDoc.PDF for .NET can also help with this.
extract pdf images; extract pictures from pdf
C# PDF insert text Library: insert text into PDF content in C#.net
Text to PDF. C#.NET PDF SDK - Insert Text to PDF Document in C#.NET. Providing C# Demo Code for Adding and Inserting Text to PDF File Page with .NET PDF Library.
extract photo from pdf; extract images from pdf
Electrical installation
Basics for wiring according to EMC
Shielding
6
115
EDS82EV903   EN   3.0
6.3.2
Shielding
Requirements
The quality of shielding is determined by:
ƒ
a good shield connection
–a contact surface as large as possible
ƒ
a low resistance:
–Only use shields with tin−plated or nickel−plated copper braids!
Connection system
ƒ
Connect the shield with a large surface and fix it with metal cable binders or a
conductive clamp.
ƒ
Connect the shield directly to the corresponding device shield sheet.
–If required, additionally connect the shield to the conductive and earthed
mounting plate in the control cabinet.
–If required, additionally connect the shield to the cable clamp rail.
Motor cables
ƒ
If the motor cables must be interrupted due to chokes or terminals, the length of the
unshielded cable must not exceed 40 ... 100 mm (depending on the cable
cross−section).
ƒ
If the motor cable must be interrupted by chokes, switches or terminals, these must
be installed separately from the other components (with a min. distance of
100 mm).
ƒ
For cable lengths of up to 500 mm, a second shield connection is not required.
Motor supply cable
Cable gland
Motorsupplycable
max.500mm
Large-surface
contactof
cableshield
Braid
Heat-shrinkabletube
Cableglandacc.toEMCwith
highdegreeofprotection
Cable gland
8200EMV023
8200EMV024
Fig. 6−3
Shielding of the motor cable
C# PDF Page Extract Library: copy, paste, cut PDF pages in C#.net
Page: Extract, Copy and Paste PDF Pages. Easy to Use C# Code to Extract PDF Pages, Copy Pages from One PDF File and Paste into Others in C#.NET Program.
pdf extract images; extract images from pdf files
VB.NET PDF Form Data Read library: extract form data from PDF in
featured PDF software, it should have functions for processing text, image as well how to read or retrieve field data from PDF and how to extract and get
extract image from pdf acrobat; extract image from pdf in
Electrical installation
Basics for wiring according to EMC
Shielding
6
116
EDS82EV903  EN  3.0
Control cables
ƒ
The cables of the analog and digital inputs and outputs must be shielded. Short (up
to 200 mm), unshielded cables must always be twisted.
ƒ
Analog cables: Place one side of the shield on the inverter.
ƒ
To achieve an optimum shielding effect in unfavourable situations (in case of very
long cables, with high interference) one shield end can be connected to PE potential
via a capacitor (e.g. 10 nF/250 V) (see sketch).
ƒ
Digital cables: Place both sides of the shield on the inverter.
ƒ
The shield connections of the control cables must have a distance of at least 50 mm
to the shield connections of the motor and DC cables.
9300vec043
Fig. 6−4
Shielding of long, analog control cables
Electrical installation
Basics for wiring according to EMC
Installation in the control cabinet
6
117
EDS82EV903   EN   3.0
6.3.3
Installation in the control cabinet
Mounting plate requirements
ƒ
Only use mounting plates with conductive surfaces (zinc−coated or V2A−steel).
ƒ
Painted mounting plates are not suitable even if the paint is removed from the
contact surfaces.
ƒ
If  several mounting plates are used, ensure a large−surface connection between the
mounting plates (e.g. by using earthing strips).
Mounting of the components
ƒ
Connect the controller and RFI filter to the grounded mounting plate with a surface
as large as possible.
ƒ
No DIN rail mounting!
Optimum cable routing
ƒ
Always separate motor cables from mains cables and control cables.
ƒ
Install separate terminals for the motor cable(s) at the control cabinet inlet. Keep a
distance of at least 100 mm to all other terminals.
ƒ
The cables must always be laid close to the mounting plate (reference potential), as
loose cables act like aerials.
ƒ
Route the cables as straight−lined as possible to the terminals (no tangle of cables)!
ƒ
Use a separate cable duct for mains cables and control cables. Do not mix different
cable types in one cable duct.
ƒ
Never lay motor cables in parallel with mains cables and control cables.
ƒ
Cross the motor cable vertically with mains cables and control cables.
ƒ
Twist unshielded cables of the same circuit (both conductors) or keep the surface
between both conductors as small as possible.
ƒ
Minimise coupling capacities and inductances by unnecessary cable lengths and
reserve loops.
ƒ
Short−circuit cable ends of unused cables to the reference potential.
Earth connections
ƒ
Connect all components (drive controllers, chokes, filters) to a central earthing point
(PE rail).
ƒ
Set up a star−shape earthing system.
ƒ
Comply with the corresponding minimum cable cross−sections.
Electrical installation
Basics for wiring according to EMC
Installation in the control cabinet
6
118
EDS82EV903  EN  3.0
Continuation of cable routing
Separation of the "hot" motor cable from the control, signal, and mains cables:
ƒ
Never install motor and signal cables in parallel and only cross at right angles
ƒ
The cables of a 24 V power supply unit (plus and minus cable) must be installed
closely together over their entire length in order that no loops may occur.
Fig. 6−5
Cable routing in the control cabinet
Electrical installation
Basics for wiring according to EMC
Wiring outside of the control cabinet
6
119
EDS82EV903   EN   3.0
6.3.4
Wiring outside of the control cabinet
Notes for cable routing outside the control cabinet:
ƒ
The longer the cables the greater the space between the cables must be.
ƒ
If cables for different signal types are routed in parallel, the interferences can be
minimized by means of a metal barrier or separated cable ducts.
Cover
Barrierwithout
opening
Powercables
Signalcables
EMVallg001
Fig. 6−6
Cable routing in the cable duct with barrier
Wiring on the mains side
ƒ
It is possible to connect the controller, mains choke or RFI filter to the mains via
single cores or unshielded cables.
ƒ
The cable cross−section must be rated for the assigned fuse protection (VDE 0160).
Wiring on the motor side
Stop!
The motor cable is highly susceptible to interference. Therefore you will
achieve an optimum wiring on the motor side if you
ƒ
exclusively use shielded and low−capacitance motor cables.
ƒ
do not integrate any further cable into the motor cable (e.g. for blowers
etc.).
ƒ
shield the supply cable for temperature monitoring of the motor (PTC or
thermostat) and install it separately from the motor cable.
Special conditions allow you to integrate the supply cable for temperature monitoring of
the motor into the motor cable: (  114)
Electrical installation
Basics for wiring according to EMC
Wiring terminal strips
6
120
EDS82EV903  EN  3.0
6.3.5
Wiring terminal strips
The supplied terminal strips are tested according to the specifications of
ƒ
DIN VDE 0627:1986−06 (partially)
ƒ
DIN EN 60999:1994−04 (partially)
Checked and tested are, for instance, mechanical, electrical and thermal load, vibration,
damage of conductors, loose conductors, corrosion, ageing.
Stop!
Proceed as follows to avoid damage of the terminal strip and the contacts:
ƒ
Mount or remove only when the controller is not connected to the mains!
ƒ
Wire the terminal strips before connecting them!
ƒ
Unused terminal strips must also be plugged in to protect the contacts.
8200vec015
Note!
Basically wiring without wire end ferrules is possible.
If safety functions (e.g. "Safe torque off") are used, insulated wire end ferrules
or rigid conductors are required!
Documents you may be interested
Documents you may be interested