Electrical installation
Standard devices in a power range from 3 ... 11 kW
EMC−compliant wiring
6
131
EDS82EV903   EN   3.0
6.5
Standard devices in a power range from 3 ... 11 kW
6.5.1
EMC−compliant wiring
(Design of a CE−typical drive system)
The drives comply with the EC Directive on "Electromagnetic Compatibility" if they are
installed in accordance with the specifications for the CE−typical drive system. The user is
responsible for the compliance of the machine application with the EC Directive.
Note!
ƒ
Control cables and mains cables must be separated from the motor cable to
avoid interference injections.
ƒ
Always use shielded control cables.
ƒ
Generally we recommend to shield the cable for the PTC or thermal contact
and route it separately from the motor cable.
ƒ
If you route the cores for the motor connection and the cores for the
connection of the PTC or thermal contact within one cable with a common
shield:
–To reduce interference injections on the PTC cable we recommend to
additionally install the PTC kit type E82ZPEx.
ƒ
Optimum HF shield connection of the motor cable is obtained by using the
terminal for motor PE and motor shield.
Extract image from pdf file - Select, copy, paste PDF images in C#.net, ASP.NET, MVC, Ajax, WinForms, WPF
Support PDF Image Extraction from a Page, a Region on a Page, and PDF Document
pdf image text extractor; extract pdf pages to jpg
Extract image from pdf file - VB.NET PDF Image Extract Library: Select, copy, paste PDF images in vb.net, ASP.NET, MVC, Ajax, WinForms, WPF
Support PDF Image Extraction from a Page, a Region on a Page, and PDF Document
pdf image extractor online; how to extract images from pdf in acrobat
Electrical installation
Standard devices in a power range from 3 ... 11 kW
EMC−compliant wiring
6
132
EDS82EV903  EN  3.0
Realisation
M
3~
L<500mm
L<40mm
PES
PES
PE
PE
PE
PES
8200vec066
Fig. 6−12
Wiring in compliance with EMC standards
 Mounting plate with electrically conductive surface
 Control cable to the function module, connect the shielding to the EMC shield sheet (PES) with
a surface as large as possible
 2−pole terminal for motor PE and motor shield
 PE of the motor cable
 Shield of the motor cable
 Shielded motor cable, low−capacitance
(Core/core 1.5 mm2  75 pF/m; from 2.5 mm 100 pF/m; core/shield  150 pF/m)
 Shielded PTC cable or thermal contact cable
 Connect the cable shields to the EMC shield sheet (PES) with a surface as large as possible. Use
the supplied shield clamps.
 Star or delta connection as indicated on the motor nameplate
 EMC cable connector (not included in the delivery package)
C# PDF Text Extract Library: extract text content from PDF file in
Ability to extract highlighted text out of PDF document. text extraction from PDF images and image files. Enable extracting PDF text to another PDF file, TXT and
extract image from pdf using; how to extract images from pdf files
VB.NET PDF Text Extract Library: extract text content from PDF
Extract and get partial and all text content from PDF file. Extract highlighted text out of PDF document. Image text extraction control provides text extraction
extract image from pdf java; extract pictures pdf
Electrical installation
Standard devices in a power range from 3 ... 11 kW
Mains connection
6
133
EDS82EV903   EN   3.0
6.5.2
Mains connection
Controller of type E82xVxxxK2C (230/240 V mains)
Stop!
ƒ
Only connect the controller to the permitted mains voltage ( Technical
data). A higher mains voltage destroys the controller!
ƒ
Some controllers may only be actuated with a mains choke or mains filter.
This requirement can differ with regard to operation at rated power and
operation at an increased rated power.
ƒ
The leakage current to earth (PE) is > 3.5 mA. In accordance with
EN 61800−5−1 a fixed installation is required. The PE conductor has to be
designed double.
X1.1
3PEAC230/240V
45Hz-0%...65Hz+0% 100V-0%...264V+0%
X1.1
PE L1
L3
+UG -UG
L2
E82EVXXXK2 C
L1
L2
L3
N
PE
0,7...0,8Nm
6.2...7.1lb-in
6mm/0.24in
8200vec065
Fig. 6−13
Mains connection 230/240 V 3 ... 7.5 kW
X1.1/+UG,
X1.1/−UG
Supply for DC−bus operation
VB.NET PDF File Compress Library: Compress reduce PDF size in vb.
Reduce image resources: Since images are usually or large size, images size reducing can help to reduce PDF file size effectively.
extract jpg from pdf; pdf image extractor c#
C# PDF insert image Library: insert images into PDF in C#.net, ASP
Create high resolution PDF file without image quality losing in ASP.NET application. Add multiple images to multipage PDF document in .NET WinForms.
extract vector image from pdf; extract image from pdf file
Electrical installation
Standard devices in a power range from 3 ... 11 kW
Mains connection
6
134
EDS82EV903  EN  3.0
Controller of type E82xVxxxK4C (400/500 V mains)
Stop!
ƒ
Only connect the controller to the permitted mains voltage ( Technical
data). A higher mains voltage destroys the controller!
ƒ
Some controllers may only be actuated with a mains choke or mains filter.
This requirement can differ with regard to operation at rated power and
operation at an increased rated power.
ƒ
The leakage current to earth (PE) is > 3.5 mA. In accordance with
EN 61800−5−1 a fixed installation is required. The PE conductor has to be
designed double.
X1.1
3PEAC400V
45Hz-0%...65Hz+0% 320V-0%...550V+0%
X1.1
PE L1
L3
+UG-UG
L2
E82EVXXXK4C
L1
L2
L3
N
PE
0,7...0,8Nm
6.2...7.1lb-in
6mm/0.24in
8200vec067
Fig. 6−14
Mains connection 400/500 V controller 3 ... 11 kW
X1.1/+UG,
X1.1/−UG
Supply for DC−bus operation
C# PDF File Split Library: Split, seperate PDF into multiple files
Application. Best and professional adobe PDF file splitting SDK for Visual Studio .NET. outputOps); Divide PDF File into Two Using C#.
extract text from image pdf file; extract photos pdf
VB.NET PDF File Merge Library: Merge, append PDF files in vb.net
When you have downloaded the RasterEdge Image SDK for also provided you with detailed PDF processing demo Imaging.Demo directory with the file name RasterEdge
extract images pdf; extract color image from pdf in c#
Electrical installation
Standard devices in a power range from 3 ... 11 kW
Fuses and cable cross−sections according to EN 60204−1
6
135
EDS82EV903   EN   3.0
6.5.3
Fuses and cable cross−sections according to EN 60204−1
Supply conditions
Range
Description
Fuses
Utilisation category: only gG/gL or gRL
Cables
Laying systems B2 and C: Use of PVC−insulated copper cables, conductor temperature < 70 °C,
ambient temperature < 40 °C, no bundling of the cables or cores, three loaded cores. The data are
recommendations. Other dimensionings/laying systems are possible (e.g. in accordance with
VDE 0298−4).
RCCB
Controllers can cause a DC current in the PE conductor. If a residual current device (RCD) or a
fault current monitoring unit (RCM) is used for protection in the case of direct or indirect
contact, only one RCD/RCM of the following type can be used on the current supply side:
–Type B (universal−current sensitive) for connection to a three−phase system
–Type A (pulse−current sensitive) or type B (universal−current sensitive) for connection to a
1−phase system
Alternatively another protective measure can be used, like for instance isolation from the
environment by means of double or reinforced insulation, or isolation from the supply system
by using a transformer.
Earth−leakage circuit breakers must only be installed between mains supply and controller.
Observe all national and regional regulations!
VB.NET PDF insert image library: insert images into PDF in vb.net
Create high resolution PDF file without image quality losing in .NET WinForms application. Insert single or multiple images or graphics to PDF document.
pdf image text extractor; how to extract a picture from a pdf
C# PDF File Compress Library: Compress reduce PDF size in C#.net
Reduce image resources: Since images are usually or large size, images size reducing can help to reduce PDF file size effectively.
extract pictures pdf; extract images from pdf c#
Electrical installation
Standard devices in a power range from 3 ... 11 kW
Fuses and cable cross−sections according to EN 60204−1
6
136
EDS82EV903  EN  3.0
Operation at rated power
8200 vector
Rated fuse current
Cable cross−section
ELCB 1)
Fuse
Circuit−breaker
Laying system L1, L2, L3, N, PE
B2
C
Type
[A]
[A]
[mm2]
[mm2]
[mA]
Mains 3/PE AC 230/240 V − operation without mains choke/mains filter
E82xV302K2C
20
B20
4
 300 2)
 30 3)
E82xV402K2C
32
B25
6
4)
E82xV552K2C
B32
6
4)
E82xV752K2C
Operation only permitted with mains choke or mains filter
E82xV302K2C
16
B16
2.5
 300 2)
 30 3)
E82xV402K2C
20
B20
4
E82xV552K2C
B25
6
4)
E82xV752K2C
B32
6
4)
E82xV302K2C
16
B16
2.5
 300 2)
 30 3)
E82xV402K2C
20
B20
4
E82xV552K2C
B25
6
4)
E82xV752K2C
B32
6
4)
Mains 3/PE AC 400/500 V − operation without mains choke/mains filter
E82xV302K4C
16
B16
2.5
 300 2)
 30 3)
E82xV402K4C
16
B16
2.5
E82xV552K4C
25
B25
4
E82xV752K4C
32
B32
4)
E82xV113K4C
Operation only permitted with mains choke or mains filter
Mains 3/PE AC 400/500 V − operation with mains choke/mains filter
E82xV302K4C
10
B10
1.5
 300 
2)
 30 3)
E82xV402K4C
16
B16
2.5
E82xV552K4C
20
B20
4
E82xV752K4C
20
B20
4
E82xV113K4C
32
B32
6
4)
1)
Earth−leakage circuit breaker
2)
Is used with E82EVxxxKxC0xx (with integrated EMC filter)
3)
Is used with E82EVxxxKxC2xx (without integrated EMC filter)
4)
Pin−end connector required
Electrical installation
Standard devices in a power range from 3 ... 11 kW
Fuses and cable cross−sections according to UL
6
137
EDS82EV903   EN   3.0
Operation with increased rated power
8200 vector
Rated fuse current
Cable cross−section
ELCB 1)
Fuse
Circuit−breaker
Laying system L1, L2, L3, N, PE
B2
C
Type
[A]
[A]
[mm2]
[mm2]
[mA]
Mains 3/PE AC 230/240 V − operation without mains choke/mains filter
E82xV302K2C
25
B25
4)
 300 2)
 30 3)
E82xV552K2C
Operation only permitted with mains choke or mains filter
E82xV302K2C
16
B16
2.5
 300 2)
 30 3)
E82xV402K2C
20
B20
4
E82xV552K2C
B25
6
4
)
E82xV752K2C
B32
6
4
)
E82xV302K2C
20
B20
4
 300 2)
 30 3)
E82xV552K2C
32
B32
4)
Mains 3/PE AC 400 V − operation without mains choke/mains filter
E82xV302K4C
16
B16
2.5
 300 2)
 30 3)
E82xV402K4C
Operation only permitted with mains choke or mains filter
E82xV752K4C
Mains 3/PE AC 400 V − operation with mains choke/mains filter
E82xV302K4C
10
B10
1.5
 300 2)
 30 3)
E82xV402K4C
16
B16
2.5
E82xV752K4C
B20
4
1)
Earth−leakage circuit breaker
2)
Is used with E82EVxxxKxC0xx (with integrated EMC filter)
3)
Is used with E82EVxxxKxC2xx (without integrated EMC filter)
4)
Pin−end connector required
6.5.4
Fuses and cable cross−sections according to UL
Supply conditions
Range
Description
Fuses
Only in accordance with UL 248
System short−circuit current up to 5000 A
rms
: All classes are permissible
System short−circuit current up to 50000 A
rms
: Only classes "CC", "J", "T" or "R" permissible
Circuit−brea
ker
Only in accordance with UL 489
Manufacturer/type
–ABB: S 200 U Charact. K
–Schneider Electric: Multi9 C60 Charact. C
–Moeller: FAZ−C Charact. C
Cables
Only in accordance with UL
The cable cross−sections specified in the following apply under the following conditions:
–Conductor temperature < 60 °C
–Ambient temperature < 40 °C
Observe all national and regional regulations!
Electrical installation
Standard devices in a power range from 3 ... 11 kW
Fuses and cable cross−sections according to UL
6
138
EDS82EV903  EN  3.0
Operation at rated power
8200 vector
Rated fuse current / cable cross−section
Fuse
Circuit−breaker
Type
L1, L2, L3, N, PE
Type
L1, L2, L3, N, PE
Type
[A]
[AWG]
[A]
[AWG]
Mains 3/PE AC 230/240 V − operation without mains choke/mains filter
E82xV302K2C
20
12
E82xV402K2C
25
10
E82xV552K2C
30
8
4)
E82xV752K2C
Operation only permitted with mains choke or mains filter
Mains 3/PE AC 230/240 V − operation with mains choke/mains filter
E82xV302K2C
20
12
E82xV402K2C
25
10
E82xV552K2C
35
E82xV752K2C
35
8
4)
Mains 3/PE AC 400/500 V − operation without mains choke/mains filter
E82xV302K4C
15
14
E82xV402K4C
15
14
E82xV552K4C
20
12
E82xV752K4C
25
10
E82xV113K4C
Operation only permitted with mains choke or mains filter
Mains 3/PE AC 400/500 V − operation with mains choke/mains filter
E82xV302K4C
10
16
E82xV402K4C
15
14
E82xV552K4C
20
12
E82xV752K4C
25
10
E82xV113K4C
25
10
4)
Pin−end connector required
Operation with increased rated power
Operation at an increased rated power is not UL−certified.
Electrical installation
Standard devices in a power range from 3 ... 11 kW
Connection motor/external brake resistor
6
139
EDS82EV903   EN   3.0
6.5.5
Connection motor/external brake resistor
Danger!
ƒ
All control terminals only have basic insulation (single isolating distance)
after connecting a PTC thermistor or a thermal contact.
ƒ
Protection against accidental contact in case of a defective isolating
distance is only guaranteed through external measures, e.g. double
insulation.
U
PES
V
W
BR2
PE
PE
PE
PES
PES
PES
PES
T1
T2
M
3~
ϑ>
PES
PES
M
3~
PTC
8200vector
X2.2
X2.1
X2.1
P E
W
B r2
U
Br 1
V
T2
T1
X2.2
BR1
PE
0,7...0,8Nm
6.2...7.1lb-in
6mm/0.24in
PES
PE
8200vec064
Fig. 6−15
Motor connection 3 ... 11 kW
Use low−capacitance motor cables! (Core/core up to 1.5 mm2  75 pF/m; from 2.5 mm2  100 pF/m; core/shield
150 pF/m). Motor cables that are as short as possible have a positive effect on the drive behaviour!
PES
HF shield termination through PE connection via shield clamp or EMC cable gland.
X2.1/PE
Earthing of the 8200 vector at the output
X2.1/BR1, X2.1/BR2
Terminals of brake resistor
X2.2/T1, X2.2/T2
Terminals of motor temperature monitoring with PTC thermistor or thermal contact
Activate motor temperature monitoring with C0119 (e.g. C0119 = 1)!
Cable cross−sections U, V, W, PE
Type
mm
2
AWG
Type
mm
2
AWG
E82xV302K2C
2.5
12
E82xV302K4C
1
16
E82xV402K2C
4
10
E82xV402K4C
1.5
14
E82xV552K2C
6
10
E82xV552K4C
2.5
12
E82xV752K2C
6
10
E82xV752K4C
4
10
E82xV113K4C
4
10
Electrical installation
Standard devices in a power range from 3 ... 11 kW
Connection of relay output
6
140
EDS82EV903  EN  3.0
6.5.6
Connection of relay output
8200vec061
Fig. 6−16
Relay connection 3 ... 11 kW
Function
Relay position
(activated)
Message
(Lenze setting)
Technical data
X1.2/K11 Relay output
normally−closed contact
opened
TRIP
AC 250 V/3 A
DC 24 V/2 A ... DC 240 V/0.16 A
X1.2/K12
Relay mid−position
contact
X1.2/K14
Relay output
normally−open contact
closed
TRIP
PES
HF shield termination by PE connection through shield clamp
Note!
ƒ
Switching of control signals:
–Use shielded cables
–HF shield termination by PE connection
–The minimum load for switching the signals through correctly is 12 V and
5 mA. Both values have to be exceeded at the same time.
ƒ
Switching of mains potentials:
–Unshielded cables are sufficient
ƒ
For the protection of the relay contacts a corresponding suppressor circuit is
absolutely required for an inductive or a capacitive load!
ƒ
The service life of the relay depends on the type of load (ohmic, inductive or
capacitive) and the value of the switching capacity.
ƒ
The message that is output can be changed in code C0008 or C0415/1.