Electrical installation
Standard devices in the power range 75 ... 90 kW
Fuses and cable cross−sections according to UL
6
161
EDS82EV903   EN   3.0
6.8.4
Fuses and cable cross−sections according to UL
Supply conditions
Range
Description
Fuses
Only according to UL 248
Mains short−circuit current up to 10000 A
rms
: All classes permissible
Mains short−circuit current up to 50000 A
rms
: Only classes "J", "T" or "R" permissible
Cables
Only in accordance with UL
The cable cross−sections specified in the following apply under the following conditions:
–Conductor temperature < 75 °C
–Ambient temperature < 40 °C
Observe all national and regional regulations!
Operation at rated power
8200 vector
Rated fuse current / cable cross−section
Fuse
Circuit−breaker
Type
L1, L2, L3, PE
Type
L1, L2, L3, PE
Type
[A]
[AWG]
[A]
[AWG]
Mains 3/PE AC 400/500 V − operation without mains choke/mains filter
E82xV753K4B
Operation only permitted with mains choke or mains filter
E82xV903K4B
Mains 3/PE AC 400/500 V − operation with mains choke/mains filter
E82xV753K4B
175
2/0
E82xV903K4B
200
3/0
Operation with increased rated power
Operation at an increased rated power is not UL−certified.
Extract pdf pages to jpg - Select, copy, paste PDF images in C#.net, ASP.NET, MVC, Ajax, WinForms, WPF
Support PDF Image Extraction from a Page, a Region on a Page, and PDF Document
extract image from pdf in; pdf image extractor c#
Extract pdf pages to jpg - VB.NET PDF Image Extract Library: Select, copy, paste PDF images in vb.net, ASP.NET, MVC, Ajax, WinForms, WPF
Support PDF Image Extraction from a Page, a Region on a Page, and PDF Document
extract pictures from pdf; extract image from pdf acrobat
Electrical installation
Standard devices in the power range 75 ... 90 kW
Motor connection
6
162
EDS82EV903  EN  3.0
6.8.5
Motor connection
PE
PE
M
3~
M
3~
PTC
PE
PES
PE
U
V
W
T1
T2

PES
PES
PES
PES
PES
PES
T1
T2
U,V,W,
PE
30 Nm
264 lb-in
M 10
U
V
W
PE
T1
T2
2.5 Nm
22.1 lb-in
2,5 Nm/22.1
3 Nm/26.5
lb-in
lb-in
M4 × 12
M5 × 12
PE
8200vec287
Fig. 6−27
Motor connection 75 ... 90 kW

Strain relief with cable clamps and screws M4 × 12 mm.
 Place the shield of the motor cables with shield clamp and M5 × 12 mm screws onto the shield
sheet.
 Strain relief with cable binders.
Use low−capacitance motor cables! (core/core  250 pF/m, core/shield  410 pF/m)
The shorter the motor cable, the better the drive behaviour!
PES HF shield termination by PE connection through shield clamp.
T1,
T2
Terminals of motor temperature monitoring with PTC thermistor or thermal contact (NC
contact).
Lay a separate cable (shielded) to X2/T1 and X2/T2 for motor temperature monitoring.
Activate motor temperature monitoring with C0119 (e.g. C0119 = 1)!
Lay the control and mains cables separately from the motor cable!
Cable cross−sections U, V, W, PE
8200 vector
mm2
AWG
E82xV753K4B
70
2 / 0
E82xV903K4B
95
3 / 0
C# PDF Convert to Jpeg SDK: Convert PDF to JPEG images in C#.net
Turn multiple pages PDF into single jpg files respectively online. Support of converting from any single one PDF page and multiple pages.
extract image from pdf file; extract text from pdf image
VB.NET PDF Convert to Jpeg SDK: Convert PDF to JPEG images in vb.
text, C#.NET convert PDF to images, C#.NET PDF file & pages edit, C#.NET PDF pages extract, copy, paste Turn multiple pages PDF into multiple jpg files in
extract photo from pdf; extract image from pdf c#
Electrical installation
Standard devices in the power range 75 ... 90 kW
Connection relay outputs K1 and K2
6
163
EDS82EV903   EN   3.0
6.8.6
Connection relay outputs K1 and K2
K14
K1
K2
K12
K11
K24
nc
K11
K21
K12
K22
X1.2
X1.3
K14
K24
nc
K22
K21
8200vec261
Fig. 6−28
Relay connections K1 and K2
Relay K1
Function
Relay position
switched
Message
(Lenze setting)
Technical data
X1.2/K11
Relay output
normally−closed
contact
opened
TRIP
250 VAC/3 A
DC 24 V/2 A ... DC 240 V/0.22 A
X1.2/K12
Relay mid−position
contact
X1.2/K14
Relay output
normally−open
contact
closed
TRIP
PES
HF shield termination by PE connection through shield clamp
Note!
ƒ
Switching of control signals:
–Use shielded cables
–HF shield termination by PE connection
–The minimum load for switching the signals through correctly is 12 V and
5 mA. Both values have to be exceeded at the same time.
ƒ
Switching of mains potentials:
–Unshielded cables are sufficient
ƒ
For the protection of the relay contacts a corresponding suppressor circuit is
absolutely required for an inductive or a capacitive load!
ƒ
The service life of the relay depends on the type of load (ohmic, inductive or
capacitive) and the value of the switching capacity.
ƒ
The message that is output can be changed in code C0008 or C0415/1.
C# Image Convert: How to Convert Adobe PDF to Jpeg, Png, Bmp, &
C# sample code for PDF to jpg image conversion. This demo code convert PDF file all pages to jpg images. // Define input and output files path.
extract text from image pdf file; extract images from pdf files without using copy and paste
C# Image Convert: How to Convert Tiff Image to Jpeg, Png, Bmp, &
RasterEdge.XDoc.Office.Inner.Office03.dll. RasterEdge.XDoc.PDF.dll. RasterEdge.XDoc. PowerPoint.dll. This demo code convert TIFF file all pages to jpg images.
how to extract images from pdf files; how to extract pictures from pdf files
Electrical installation
Standard devices in the power range 75 ... 90 kW
Connection relay outputs K1 and K2
6
164
EDS82EV903  EN  3.0
Relay K2
Function
Relay position
switched
Message
(Lenze setting)
Technical data
X1.3/K21
Relay output
normally−closed
contact
opened
not assigned
AC 250 V/3 A
DC 24 V/2 A ... DC 240 V/0.22 A
X1.3/K22
Relay mid−position
contact
X1.3/K24
Relay output
normally−open
contact
closed
not assigned
PES
HF shield termination by PE connection through shield clamp
Note!
ƒ
Switching of control signals:
–Use shielded cables
–HF shield termination by PE connection
–The minimum load for switching the signals through correctly is 12 V and
5 mA. Both values have to be exceeded at the same time.
ƒ
Switching of mains potentials:
–Unshielded cables are sufficient
ƒ
For the protection of the relay contacts a corresponding suppressor circuit is
absolutely required for an inductive or a capacitive load!
ƒ
The service life of the relay depends on the type of load (ohmic, inductive or
capacitive) and the value of the switching capacity.
ƒ
The output message can be changed with C0409.
ƒ
If you use an application I/O function module:
–The relay K2 is only active with application I/O E82ZAFAC from version
Vx21 onwards.
C# Create PDF from images Library to convert Jpeg, png images to
Batch convert PDF documents from multiple image formats, including Jpg, Png, Bmp, Gif, Tiff, Bitmap, .NET Graphics, and REImage.
extract jpg from pdf; how to extract images from pdf file
VB.NET PDF - Convert PDF with VB.NET WPF PDF Viewer
convert PDF to text, VB.NET extract PDF pages, VB.NET Create multiple pages Tiff file from PDF document. formats with high quality, support converting PDF to PNG
extract image from pdf using; extract image from pdf online
Extensions for automation
Standard devices in a power range from 0.25 ... 2.2 kW
I/O function modules
7
165
EDS82EV903   EN   3.0
7
Extensions for automation
7.1
Standard devices in a power range from 0.25 ... 2.2 kW
The frequency inverters are equipped with two module slots on the front of the housing:
ƒ
The lower slot (FIF interface) serves to connect an I/O or bus function module.
–An I/O function module (standard I/O or application I/O) expands the controller by
control terminals for analog or digital inputs/outputs.
–Via a bus function module (e.g. PROFIBUS−DP PT or CAN PT) you connect the
controller to a fieldbus.
–A bus function module with control terminals (e.g. PROFIBUS−I/O, CAN−IO PT) is a
combination of the above−mentioned function modules.
ƒ
You can connect a keypad or a communication module to the upper slot (AIF
interface).
–Via the keypad you parameterise the controller according to its application, read
out its status and diagnose errors.
–Via a communication module you connect the controller to a PC or to a fieldbus.
7.1.1
I/O function modules
Possible modules
Type
Comment
Standard I/O PT
E82ZAFSC010
1 analog input (switchable between master
current/voltage)
1 analog output (voltage)
4 digital inputs
1 digital output
Application I/O PT
E82ZAFAC010
2 analog inputs (switchable between master
current/voltage)
2 analog outputs (voltage or current)
6 digital inputs
2 digital outputs
1 frequency output
Note!
Information about the wiring and application is provided later on in this
chapter:
Standard I/O (  190)
Application I/O (  196)
C# WPF PDF Viewer SDK to convert and export PDF document to other
PDF file & pages edit, C#.NET PDF pages extract, copy, paste Create multiple pages Tiff file from PDF document. with high quality, support converting PDF to PNG
extract images pdf; how to extract images from pdf in acrobat
VB.NET Create PDF from images Library to convert Jpeg, png images
Support create PDF from multiple image formats in VB.NET, including Jpg, Png, Bmp, Gif, Tiff, Bitmap, .NET Graphics, and REImage.
extract images from pdf acrobat; pdf extract images
Extensions for automation
Standard devices in a power range from 0.25 ... 2.2 kW
Bus function modules
7
166
EDS82EV903  EN  3.0
7.1.2
Bus function modules
Possible modules
Type
Comment
PROFIBUS−DP
E82ZAFPC010
PROFIBUS I/O
E82ZAFPC201
With two digital inputs
System bus CAN PT
E82ZAFCC010
System bus CAN I/O PT
E82ZAFCC210
With two digital inputs
System bus CAN I/O RS PT
E82ZAFCC100
With two digital inputs and possible external supply of
the control section of the 8200 vector
CANopen PT
E82ZAFUC010
DeviceNet PT
E82ZAFVC010
INTERBUS PT
E82ZAFIC010
LECOM−B PT
E82ZAFLC010
RS485 interface
AS interface PT
E82ZAFFC010
Note!
Information on how to wire and use the modules can be found in the
corresponding mounting instructions and communication manuals.
7.1.3
Communication modules
Possible modules
Type
Comment
PROFIBUS−DP
EMF2133IB
System bus CAN
EMF2171IB
System bus CAN
EMF2172IB
Addressing via DIP switch
CANopen
EMF2178IB
DeviceNet
EMF2179IB
INTERBUS
EMF2113IB
LECOM−A
EMF2102IBCV004
RS232 interface
LECOM−B
EMF2102IBCV002
RS485 interface
LECOM−A/B
EMF2102IBCV001
RS232/RS485 interface
LECOM−LI
EMF2102IBCV003
Optical fibre
Note!
Information on how to wire and use the modules can be found in the
corresponding mounting instructions and communication manuals.
Extensions for automation
Standard devices in a power range from 0.25 ... 2.2 kW
Combine function and communication modules
7
167
EDS82EV903   EN   3.0
7.1.4
Combine function and communication modules
Possible combinations
Function module on FIF
Communication module on AIF
Keypad E82ZBC
Keypad XT
EMZ9371BC
PROFIBUS−DP
EMF2133IB
System bus
CAN
EMF2171IB
EMF2172IB
CANopen
EMF2178IB
DeviceNet
EMF2179IB
Ethernet
PowerLink
EMF2191IB
Standard I/O PT
E82ZAFSC010
Application I/O PT
E82ZAFAC010
)
)
)
)
)
PROFIBUS−DP
E82ZAFPC010
PROFIBUS I/O
E82ZAFPC201
Sys. bus CAN PT
E82ZAFCC010
Sys. bus CAN PT
E82ZAFCC210
Sys.−bus CAN−I/O RS PT
E82ZAFCC100
CANopen PT
E82ZAFUC010
DeviceNet PT
E82ZAFVC010
INTERBUS PT
E82ZAFIC010
LECOM−B PT
E82ZAFLC010
AS interface PT
E82ZAFFC010
Function module on FIF
Communication module on AIF
INTERBUS
EMF2113IB
LECOM−A/B
EMF2102IBC V001
LECOM−A
EMF2102IBC V004
LECOM−B
EMF2102IBC V002
LECOM−LI
EMF2102IBC V003
Standard I/O PT
E82ZAFSC010
Application I/O PT
E82ZAFAC010
)
)
)
)
)
PROFIBUS−DP
E82ZAFPC010
)
)
)
PROFIBUS I/O
E82ZAFPC201
Sys. bus CAN PT
E82ZAFCC010
Sys. bus CAN PT
E82ZAFCC210
Sys.−bus CAN−I/O RS PT
E82ZAFCC100
CANopen PT
E82ZAFUC010
)
)
)
DeviceNet PT
E82ZAFVC010
)
)
)
INTERBUS PT
E82ZAFIC010
)
)
)
LECOM−B PT
E82ZAFLC010
)
)
)
AS interface PT
E82ZAFFC010
)
)
)
Combination possible, communication module can be supplied internally or externally
(keypad only internally)
Combination possible, communication module has to be supplied externally
Combination not possible
7.1.5
Mounting and dismounting function modules
Danger!
Dangerous electrical voltage
During operation of the standard device and up to 3 minutes after power−off
dangerous electrical voltages may be applied at the power terminals.
Possible consequences:
ƒ
Death or severe injuries when touching the terminals.
Protective measures:
ƒ
Disconnect the standard device from the mains and wait for 3 minutes
before you start working.
ƒ
Check all power terminals for isolation from supply.
Extensions for automation
Standard devices in a power range from 0.25 ... 2.2 kW
Mounting and dismounting function modules
7
168
EDS82EV903  EN  3.0
Mounting
8200vec601
Fig. 7−1
Worksteps
1. Disconnect the drive controller from mains and wait at least 3 minutes!
2. Remove the FIF cover  from the FIF interface.
3. Remove protective cap  of the function module  and plug function module onto
the FIF interface.
4. Insert the plug connector  into the contact strip of the function module until it
snaps in.
Additionally fit the retaining clip so that the module cannot be removed together with the
terminal strips  during wiring:
5. Insert the retaining clip  into the recess, place it on the function module and latch
it.
6. Wire the function module (see mounting instructions of the function module).
Note!
Keep the FIF cover  and the protection cover of the function module  so that
you can attach them again after you have dismounted the function module.
The controller can only be commissioned if a function module or the FIF cover
 is plugged on the FIF interface.
Extensions for automation
Standard devices in a power range from 0.25 ... 2.2 kW
Mounting and dismounting function modules
7
169
EDS82EV903   EN   3.0
Dismounting
8200vec602
Fig. 7−2
Worksteps
1. Disconnect the drive controller from mains and wait at least 3 minutes!
2. To unlatch the circlip , position the screwdriver between the circlip and the
function module and press it to the right. Then remove the circlip .
3. Grasp the bar of the plug connector  using tongs and unplug the plug connector
together with the function module .
4. Fit the FIF cover  onto the FIF interface.
Extensions for automation
Standard devices in a power range from 0.25 ... 2.2 kW
Mounting and dismounting communication modules
7
170
EDS82EV903  EN  3.0
7.1.6
Mounting and dismounting communication modules
Mounting
Note!
Communication modules can be supplied by an internal or external voltage
source. An external voltage source is only required if communication to a node
is to be maintained in the case of a switch−off or if the node fails.
8200vec606
Fig. 7−3
Worksteps
1. Set the type of voltage supply via the jumper .
–Position I: external voltage supply (delivery status; +24 V DC 10%, max. 100 mA
per module)
–Position II: voltage supply via the internal voltage source
2. Plug the communication module  to the AIF interface on the controller.
3. If the communication module is provided with a safety screw , screw the module
together with the controller.