Safety instructions
General safety information
3
21
EDS82EV903   EN   3.0
Transport, storage
ƒ
Transport and storage in a dry, low−vibration environment without aggressive
atmosphere; preferably in the packaging provided by the manufacturer.
–Protect against dust and shocks.
–Comply with climatic conditions according to the technical data.
Mechanical installation
ƒ
Install the product according to the regulations of the corresponding
documentation. In particular observe the section "Operating conditions" in the
chapter "Technical data".
ƒ
Provide for a careful handling and avoid mechanical overload. During handling
neither bend components, nor change the insulation distances.
ƒ
The product contains electrostatic sensitive devices which can easily be damaged by
short circuit or static discharge (ESD). Thus, electronic components and contacts
must not be touched unless ESD measures are taken beforehand.
Electrical installation
ƒ
Carry out the electrical installation according to the relevant regulations (e. g. cable
cross−sections, fusing, connection to the PE conductor). Additional notes are
included in the documentation.
ƒ
Applicable national regulations for the prevention of accidents (e.g. VBG 4) must be
observed when working on live products.
ƒ
The documentation contains information about EMC−compliant installation
(shielding, earthing, arrangement of filters and laying cables). The system or
machine manufacturer is responsible for compliance with the limit values required
by EMC legislation.
Warning: The controllers are products which can be used in category C2 drive systems
as per EN 61800−3. These products may cause radio interference in residential areas. If
this happens, the operator may need to take appropriate action.
ƒ
For compliance with the limit values for radio interference emission at the site of
installation, the components − if specified in the technical data − have to be mounted
in housings (e. g. control cabinets). The housings have to enable an EMC−compliant
installation. In particular observe that for example control cabinet doors preferably
have a circumferential metallic connection to the housing. Reduce openings or
cutouts through the housing to a minimum.
ƒ
Only plug in or remove pluggable terminals in the deenergised state!
Commissioning
ƒ
If required, you have to equip the system with additional monitoring and protective
devices in accordance with the respective valid safety regulations (e. g. law on
technical equipment, regulations for the prevention of accidents).
ƒ
Before commissioning remove transport locking devices and keep them for later
transports.
Operation
ƒ
Keep all protective covers and doors closed during operation.
Extract photo from pdf - Select, copy, paste PDF images in C#.net, ASP.NET, MVC, Ajax, WinForms, WPF
Support PDF Image Extraction from a Page, a Region on a Page, and PDF Document
pdf extract images; extract pdf images
Extract photo from pdf - VB.NET PDF Image Extract Library: Select, copy, paste PDF images in vb.net, ASP.NET, MVC, Ajax, WinForms, WPF
Support PDF Image Extraction from a Page, a Region on a Page, and PDF Document
how to extract images from pdf; extract images from pdf online
Safety instructions
General safety information
3
22
EDS82EV903  EN  3.0
Safety functions
ƒ
Without a higher−level safety system, the described product must neither be used
for the protection of machines nor persons.
ƒ
Certain controller versions support safety functions (e.g. "Safe torque off", formerly
"Safe standstill").
The notes on the safety functions provided in the documentation of the versions must
be observed.
Maintenance and servicing
ƒ
The components are maintenance−free if the required operating conditions are
observed.
ƒ
If the cooling air is polluted, the cooling surfaces may be contaminated or the air
vents may be blocked. Under these operating conditions, the cooling surfaces and air
vents must be cleaned at regular intervals. Never use sharp objects for this purpose!
ƒ
Only replace defective fuses in the deenergised state to the type specified.
ƒ
After the system has been disconnected from the supply voltage, live components
and power connections must not be touched immediately because capacitors may
be charged. Please observe the corresponding notes on the device.
Disposal
ƒ
Recycle metals and plastic materials. Ensure professional disposal of assembled
PCBs.
C# PDF insert image Library: insert images into PDF in C#.net, ASP
vector images to PDF file. Import graphic picture, digital photo, signature and logo into PDF document. Ability to put image into
how to extract images from pdf files; extract images pdf
VB.NET PDF insert image library: insert images into PDF in vb.net
project. Import graphic picture, digital photo, signature and logo into PDF document. Add images to any selected PDF page in VB.NET.
extract pictures pdf; extract jpeg from pdf
Safety instructions
Residual hazards
3
23
EDS82EV903   EN   3.0
3.2
Residual hazards
Protection of persons
ƒ
According to their enclosure, Lenze controllers (frequency inverters, servo inverters,
DC speed controllers) and their components can carry a voltage, or parts of the
controllers can move or rotate during operation. Surfaces can be hot.
–If the required cover is removed, the controllers are used inappropriately or
installed or operated incorrectly, severe damage to persons or material assets can
occur.
–For more detailed information please see the documentation.
ƒ
There is a high amount of energy within the controller. Therefore always wear
personal protective equipment (body protection, headgear, eye protection, ear
protection, hand guard) when working on the controller when it is live.
ƒ
Before working on the controller, check if no voltage is applied to the power
terminals.
–the power terminals U, V, W, +UG, −UG, BR1 and BR2 still carry dangerous voltage
for at least 3 minutes after power−off.
–the power terminals L1, L2, L3; U, V, W, +UG, −UG, BR1 and BR2 carry dangerous
voltage when the motor is stopped.
–the relay outputs K11, K12, K14 can carry dangerous voltage when the drive
controller is disconnected from the mains.
ƒ
Before power−off during DC−bus operation, all controllers must be inhibited and
disconnected from the mains.
ƒ
The discharge current to PE potential is > 3.5 mA. In accordance with EN 61800−5−1
–a fixed installation is required.
–the design of the PE conductor has to be double or, in the case of a single design,
must have a cable cross−section of at least 10 mm2.
ƒ
The controller can only be safely disconnected from the mains via a contactor on the
input side.
ƒ
Controllers can cause a DC current in the PE conductor. If a residual current device
(RCD) or a fault current monitoring unit (RCM) is used for protection in the case of
direct or indirect contact, only one RCD/RCM of the following type can be used on
the current supply side:
–Type B for the connection to a three−phase system
–Type A or type B for the connection to a single phase system
Alternatively another protective measure can be used, like for instance isolation from
the environment by means of double or reinforced insulation, or isolation from the
supply system by using a transformer.
VB.NET Image: Image Cropping SDK to Cut Out Image, Picture and
function from following aspects. Key functions of VB.NET image cropper control SDK; VB.NET image cropping method to crop picture / photo;
extract image from pdf; extract photos pdf
VB.NET Image: Image Resizer Control SDK to Resize Picture & Photo
VB.NET Image & Photo Resizing Overview. The practical values of this VB We are dedicated to provide powerful & profession imaging controls, PDF document, image
extract jpg from pdf; extract images from pdf acrobat
Safety instructions
Residual hazards
3
24
EDS82EV903  EN  3.0
ƒ
If you use the Selection of direction of rotation" function via the digital signal
DCTRL1−CW/CCW (C0007 = 0 ... 13, C0410/3  255):
–In the event of an open circuit or failure of the control voltage, the drive can
change its direction of rotation.
ƒ
If you use the function "flying restart circuit" (C0142 = 2, 3) for machines with a low
moment of inertia and low friction:
–After controller enable at standstill, the motor can start for a short time or change
its direction of rotation for a short time.
Device protection
ƒ
Frequent switching of the supply voltage (e.g. inching mode via mains contactor)
can overload and destroy the input current limitation of the controller:
–Wait for at least 3 minutes between two starting operations.
ƒ
Only switch contactors in the motor cable when the controller is inhibited.
Otherwise ...
–monitoring functions of the controller can be activated.
–the controller can be destroyed under unfavourable operating conditions.
Motor protection
ƒ
For some controller settings, the connected motor may overheat (e.g. when
operating the DC injection brake or a self−ventilated motor at low speed for longer
periods).
–Using an overcurrent relay or a temperature monitoring device provides a large
degree of protection against overload.
–We recommend to use PTC thermistors or thermal contacts for motor temperature
monitoring. (Lenze three−phase AC motors are equipped with thermal contacts
(NC contacts) as standard)
–PTC thermistors or thermal contacts can be connected to the controller.
ƒ
Drives can attain dangerous overspeeds (e.g. setting of high output frequencies with
motors and machines not qualified for this purpose).
VB.NET Image: Mark Photo, Image & Document with Polygon Annotation
What's more, if coupled with .NET PDF document imaging add-on, the VB.NET annotator SDK can easily generate polygon annotation on PDF file without using
extract photos from pdf; extract image from pdf in
VB.NET Image: Image Scaling SDK to Scale Picture / Photo
A 1: Using this VB.NET image scaling control SDK API, developer can only scale one image / picture / photo at a time in .NET class application.
extract pdf pages to jpg; extract image from pdf acrobat
Safety instructions
Safety instructions for the installation according to U
L
or U
R
3
25
EDS82EV903   EN   3.0
3.3
Safety instructions for the installation according to U
L
or U
R
Warnings!
ƒ
Motor Overload Protection
–For information on the protection level of the internal overload protection
for a motor load, see the corresponding manuals or software helps.
–If the integral solid state motor overload protection is not used, external or
remote overload protection must be provided.
ƒ
Branch Circuit Protection
–The integral solid state protection does not provide branch circuit
protection.
–Branch circuit protection has to be provided externally in accordance with
corresponding instructions, the National Electrical Code and any
additional codes.
ƒ
Please observe the specifications for fuses and screw−tightening torques in
these instructions.
ƒ
E82xV251K2C ... E82xV222K2C (0.25 kW ... 2.2 kW, 240 V devices):
–Suitable for use on a circuit capable of delivering not more than 5000 rms
symmetrical amperes, 240 V maximum, when protected by fuses or circuit
breakers.
–Suitable for use on a circuit capable of delivering not more than 50000 rms
symmetrical amperes, 240 V maximum, when protected by CC, J, T or R
class fuses.
–Shall be installed in a Pollution Degree 2 macro−environment.
–Maximum surrounding air temperature: 0 ... +55 °C
–> +40 °C: reduce the rated output current by 2.5 %/°C
–Use 60/75 °C or 75 °C copper wire only.
ƒ
E82xV551K4C ... E82xV222K4C (0.55 kW ... 2.2 kW, 400/500 V devices):
–Suitable for use on a circuit capable of delivering not more than 5000 rms
symmetrical amperes, 500 V maximum, when protected by fuses or circuit
breakers.
–Suitable for use on a circuit capable of delivering not more than 50000 rms
symmetrical amperes, 500 V maximum, when protected by CC, J, T or R
class fuses.
–Shall be installed in a Pollution Degree 2 macro−environment.
–Maximum surrounding air temperature: 0 ... +55 °C
–> +40 °C: reduce the rated output current by 2.5 %/°C
–Use 60/75 °C or 75 °C copper wire only.
C# Image: How to Add Antique & Vintage Effect to Image, Photo
creating control add-on is widely used in modern photo editors, which We are dedicated to provide powerful & profession imaging controls, PDF document, tiff
extract jpg pdf; pdf image extractor c#
VB.NET Image: How to Save Image & Print Image Using VB.NET
is developed to help VB.NET programmers save & print image / photo / picture from ASP Capable of saving and printing multi-page document files, like PDF and Word
extract text from image pdf file; extract vector image from pdf
Safety instructions
Safety instructions for the installation according to U
L
or U
R
3
26
EDS82EV903  EN  3.0
ƒ
E82xV302K2C ... E82xV752K2C  (3.0 kW ... 7.5 kW, 240 V devices):
–Suitable for use on a circuit capable of delivering not more than 5000 rms
symmetrical amperes, 240 V maximum, when protected by fuses.
–Suitable for use on a circuit capable of delivering not more than 50000 rms
symmetrical amperes, 240 V maximum. When protected by CC, J, T or R
class fuses.
–Shall be installed in a Pollution Degree 2 macro−environment.
–Maximum surrounding air temperature: 0 ... +55 °C
–> +40 °C: reduce the rated output current by 2.5 %/°C
–Use 60/75 °C or 75 °C copper wire only.
ƒ
E82xV302K4C ... E82xV113K4C  (3.0 kW ... 11 kW, 400/500 V devices):
–Suitable for use on a circuit capable of delivering not more than 5000 rms
symmetrical amperes, 500 V maximum, when protected by fuses or circuit
breakers (E82xV302K4C only).
–Suitable for use on a circuit capable of delivering not more than 50000 rms
symmetrical amperes, 500 V maximum. When protected by CC, J, T or R
class fuses
–Shall be installed in a Pollution Degree 2 macro−environment.
–Maximum surrounding air temperature: 0 ... +55 °C
–> +40 °C: reduce the rated output current by 2.5 %/°C
–Use 60/75 °C or 75 °C copper wire only.
ƒ
E82xV153K4B ... E82xV303K4B:
–Suitable for use on a circuit capable of delivering not more than 5000 rms
symmetrical amperes, 500 V maximum. When protected by fuses.
–Suitable for use on a circuit capable of delivering not more than 50000 rms
symmetrical amperes, 500 V maximum. When protected by  J, T or R class
fuses
–Maximum surrounding air temperature: 0 ... +50 °C
–> +40 °C: reduce the rated output current by 2.5 %/°C
–Use 60/75 °C or 75 °C copper wire only.
ƒ
E82xV453K4B ... E82xV903K4B:
–Suitable for use on a circuit capable of delivering not more than 10000 rms
symmetrical amperes, 500 V maximum. When protected by fuses.
–Suitable for use on a circuit capable of delivering not more than 50000 rms
symmetrical amperes, 500 V maximum. When protected by  J, T or R class
fuses
–Maximum surrounding air temperature: 0 ... +50 °C
–> +40 °C: reduce the rated output current by 2.5 %/°C
–Use 60/75 °C or 75 °C copper wire only.
VB.NET Image: Tutorial for Flipping Image Using Our .NET Image SDK
on the right instantly becomes a mirror reflection of the photo on the We are dedicated to provide powerful & profession imaging controls, PDF document, tiff
extract color image from pdf in c#; some pdf image extractor
C# PDF remove image library: remove, delete images from PDF in C#.
convert PDF to text, VB.NET extract PDF pages, VB vector image, graphic picture, digital photo, scanned signature remove multiple or all images from PDF document.
online pdf image extractor; pdf image text extractor
Technical data
General data and operating conditions
4
27
EDS82EV903   EN   3.0
4
Technical data
4.1
General data and operating conditions
General data
Conformity and approval
Conformity
CE
2006/95/EC
Low−Voltage Directive
2004/108/EG
EMC Directive
Approval
UL
cULus
Power Conversion Equipment (File No. E132659)
Protection of persons and equipment
Type of protection
EN 60529
IP20
IP41 in case of thermally separated installation
(push−through technique) between the control cabinet
(inside) and the environment.
NEMA 250
Protection against accidental contact in accordance with type
1
Earth leakage current
IEC/EN 61800−5−1
> 3.5 mA
Observe stipulations and safety
instructions!
Insulation of control
circuits
IEC/EN 61800−5−1
Safe mains isolation through double (reinforced) insulation
Insulation resistance
IEC/EN 61800−5−1
< 2000 m site altitude: overvoltage category III
> 2000 m site altitude: overvoltage category II
Protective measures
Against short circuit, earth fault (protected against short to
earth on power−up, limited protection against short to earth
during operation), overvoltage, motor stalling, motor
overtemperature (input for PTC thermistor or thermal
contact, I2t monitoring)
EMC
Noise emission
IEC/EN 61800−3
Cable−guided, category C1 or C2 when using shielded motor
cables1), dependent on the device variant with integrated
interference suppression or additional RFI/mains filter
0.25 ... 11 kW
E82xVxxxKxC0xx
no additional measures
E82xVxxxKxC2xx
with external filter techniques
15 ... 90 kW
E82EVxxxK4B3xx
no additional measures
E82xVxxxK4B2xx
with external filter techniques
Noise immunity
IEC/EN 61800−3
Category C2
1)
Motor cable lengths depend on the inverter type and the switching frequency
Technical data
General data and operating conditions
4
28
EDS82EV903  EN  3.0
Operating conditions
Ambient conditions
Climatic conditions
Storage
IEC/EN 60721−3−1
1K3 (−25 ... +60 °C)
< 6 months
1K3 (−25 ... +40 °C)
> 6 months
> 2 years: form the DC bus
capacitors
Transport
IEC/EN 60721−3−2
2K3 (−25 ... +70 °C)
Operation
2.2 ... 11 kW
IEC/EN 60721−3−3
3K3 (−10 ... +55 °C)
> +40 °C: reduce the rated output current by 2.5 %/°C.
15 ... 90 kW
3K3 (0 ... +50 °C)
> +40 °C: reduce the rated output current by 2.5 %/°C.
Pollution
IEC/EN 61800−5−1
Degree of pollution 2
Site altitude
< 4000 m amsl
> 1000 m amsl: reduce the rated output current by
5 %/ 1000 m.
Electrical
AC mains connection
Max. mains voltage range
E82xV251K2... and E82xV371K2...
1/N/PE 180 V − 0 % ... 264 V + 0 %
E82xV551K2... to E82xV752K2...
1/N/PE 180 V − 0 % ... 264 V + 0 % or
3/PE 100 V − 0 % ... 264 V + 0 %
E82xV551K4... to E82xV903K4...
3/PE 320 V − 0 % ... 550 V + 0 %
Mains frequency
45 Hz − 0 % ... 65 Hz + 0 %
Mains system
With earthed neutral (TT, TN): unrestricted operation
permitted
Other mains systems: observe restrictions described in the
system manual, chapter about project planning
Operation on public
supply systems
EN 61000−3−2
Limitation of harmonic currents
Total power drawn from
the mains
Compliance with the
requirements 1)
< 1 kW
With mains choke.
> 1 kW
Without additional measures.
1)
The additional measures described only ensure that the controllers comply
with the requirements of EN 61000−3−2. Compliance of the machine/system
with the requirements is in the responsibility of the machine/system
manufacturer!
DC mains connection
Max. mains voltage range
450 V − 0 % ... 740 V + 0 %
E82xV251K2... and E82xV371K2...
not possible
E82xV551K2... to E82xV752K2...
140 V − 0 % ... 370 V + 0 %
E82xV551K4... to E82xV903K4...
450 V − 0 % ... 775 V + 0 %
Operation at rated power
450 V − 0 % ... 625 V + 0 %
Operation at an increased rated
power
Operating conditions
The DC voltage must be symmetrical to PE.
The controller will be destroyed if the +U
G
conductor or −U
G
conductor is earthed.
Technical data
General data and operating conditions
4
29
EDS82EV903   EN   3.0
Ambient conditions
Motor connection
Length of the motor cable
< 50 m
shielded
< 100 m
unshielded
For rated mains voltage and switching frequency   8 kHz
without additional output filters.
For compliance with EMC regulations, the permissible cable
length may be different.
Mechanical
Vibration resistance 
(9.81 m/s2 = 1 g)
Germanischer Lloyd
5 ... 13.2 Hz
Amplitude ±1 mm 13.2 ... 100 Hz: 
acceleration resistant up to 0.7 g
IEC/EN 60068−2−6
10 ... 57 Hz
Amplitude 0.075 mm 57 ... 150 Hz: 
acceleration resistant up to 1 g
Mounting conditions
Mounting place
In the control cabinet
Mounting position
Vertical
Dimensions,
free spaces
  Chapter  "Mechanical installation"
Weights
  Chapter "Technical data", "Operation at rated power" or
"Operation at increased rated power"
Technical data
Open and closed loop control
4
30
EDS82EV903  EN  3.0
4.2
Open and closed loop control
Open and closed loop control
Open and closed loop
control modes
V/f characteristic control (linear, quadratic), vector control, torque selection
Switching frequency
0.25 ... 11 kW
2 kHz, 4 kHz, 8 kHz, 16 kHz noise optimised
15 ... 90 kW
1 kHz, 2 kHz, 4 kHz, 8 kHz, 16 kHz,
optionally noise optimised or power loss optimised
Torque behaviour
Maximum torque
0.25 ... 11 kW
1.8 x M
rated
for 60 s
if rated motor power = rated controller power
Maximum torque
15 ... 90 kW
1.8 x M
rated
for 60 s
2.1 x M
rated
for 3 s after
controller enable
Setting range
1 : 10
in speed setting range 3 ... 50 Hz, accuracy < 8 %
Torque/speed
characteristic
1.8
2.0
1.0
M/M
N
n[min -1]
500
1000
1500
Vector control (sensorless
speed control)
Minimum output
frequency
1.0 Hz (0 ... M
rated
)
Setting range
1 : 50
based on 50 Hz and M
rated
Accuracy
0.5 %
in speed setting range 3 ... 50 Hz
Smooth running
0.1 Hz
Output frequency
Range
− 650 Hz ... + 650 Hz
Absolute resolution
0.02 Hz
Standardised
resolution
Parameter data: 0.01 %, process data: 0.006 % (= 214)
Digital setpoint selection
Accuracy
0.0001 %
Analog setpoint selection
Linearity
0.5 %
based on instantaneous value
Temperature
sensitivity
+ 0.3 % (0 ... +60 °C)
based on instantaneous value
Offset
0 %
A/D converter
10−bit resolution
Error: 1 digit
 0.1 % based on final value
Operation in generator
mode
0.25 ... 11 kW
Integrated brake chopper
15 ... 90 kW
With 9352 brake chopper