Commissioning
Important codes for quick commissioning
8
221
EDS82EV903   EN   3.0
IMPORTANT
Possible settings
Code
Selection
Lenze
Name
No.
C0517
*
User menu
After mains switching or in the
 function the code from
C0517/1 is displayed.
In the Lenze setting the user
menu contains the most
important codes for
commissioning the operating
mode "V/f characteristic control
with a linear characteristic"
If the password protection is
active, only the codes entered
in C0517 can be freely accessed
If less than 10 codes are
required, assign the value "0"
(zero) to the memory locations
not used. Please observe that
the software automatically
assigns code C0050 to a
memory location that is not
used, if it has not been
explicitly assigned to another
memory location.
on.
.
  373
1
Memory 1
50
C0050
Output frequency (MCTRL1−NOUT)
2
Memory 2
34
C0034
Range of analog setpoint selection
3
Memory 3
7
C0007
Fixed configuration of digital input
signals
4
Memory 4
10
C0010
Minimum output frequency
5
Memory 5
11
C0011
Maximum output frequency
6
Memory 6
12
C0012
Acceleration time main setpoint
7
Memory 7
13
C0013
Deceleration time main setpoint
8
Memory 8
15
C0015
V/f rated frequency
9
Memory 9
16
C0016
V
min
boost
10
Memory 10
2
C0002
Parameter set transfer
Possible entries for C0517
xxxx
All codes apart from the codes labelled
with "(A)".
Syntax:
Codes: C0517/x = cccc
Subcodes: C0517/x = cccc.ss
Extract images pdf - Select, copy, paste PDF images in C#.net, ASP.NET, MVC, Ajax, WinForms, WPF
Support PDF Image Extraction from a Page, a Region on a Page, and PDF Document
extract image from pdf using; pdf extract images
Extract images pdf - VB.NET PDF Image Extract Library: Select, copy, paste PDF images in vb.net, ASP.NET, MVC, Ajax, WinForms, WPF
Support PDF Image Extraction from a Page, a Region on a Page, and PDF Document
extract images from pdf online; extract vector image from pdf
Parameter setting
Important notes
9
222
EDS82EV903  EN  3.0
9
Parameter setting
9.1
Important notes
Adapt the functions of the controller to the application
The  controller  functions  can  be  adapted  to  your  applications  by  means  of
parameterisation. You can either parameterise via keypad, PC or via the parameter channel
of a bus system.
The function library contains a detailed description of the functions, the signal flow
diagrams contain all configurable signals.
Parameters and codes
The parameters for the functions are stored in numbered codes:
ƒ
Codes are marked in the text with a "C" (e.g. C0002).
ƒ
The code table provides a quick overview of all codes. The codes are sorted in
numerically ascending order and can be used as a reference. (  378)
Parameter setting via operating module
A quick parameter setting is provided by two operating modules, "keypad", in different
versions. Both serve as status displays, error diagnosis and transfer of parameters to other
drive controllers.
Keypad
E82ZBC
Keypad XT
EMZ9371BC
Can be used with
8200 vector, 8200 motec,
starttec
8200 vector, 8200 motec,
starttec, Drive PLC, 9300 vector,
9300 servo
Operator buttons
8
8
Text display
yes
yes
Plain text display
no
yes
Menu structure
User menu, code list
User−specific menus
Configurable menu (user menu")
yes
yes
Menu for quick commissioning ("Quick start")
no
yes
Predefined basic configurations
no
yes
Non−volatile memory for parameter transfer
yes
yes
Password protection
yes
yes
Diagnosis terminal
yes
yes
Installation in control cabinet
yes
no
Type of protection
IP 55
IP 20
Detailed description
  224
  235
C# PDF Text Extract Library: extract text content from PDF file in
Ability to extract highlighted text out of PDF document. Image text extraction control provides text extraction from PDF images and image files.
extract pictures from pdf; extract photos from pdf
VB.NET PDF Text Extract Library: extract text content from PDF
Extract highlighted text out of PDF document. Image text extraction control provides text extraction from PDF images and image files.
extract images from pdf acrobat; how to extract images from pdf in acrobat
Parameter setting
Important notes
9
223
EDS82EV903   EN   3.0
Parameter setting via PC
As an alternative to the operation with an operating module, the free−of−charge "Global
Drive Control easy" PC program is available (can be downloaded at www.Lenze.com).
GDCeasy  is  a  generally  understandable  and  clearly  structured  tool  for  convenient
operation, parameter setting and diagnostics of the 8200 vector frequency inverter.
Parameter setting via GDCeasy is carried out by means of a PC and the LECOM−A/B
(RS232/RS485) or LECOM−LI (optical fibre) communication module. In a CAN network,
parameter  setting  is  also  possible  via  a  PC  system  bus  adapter  (see  "Automation"
catalogue).
Parameter setting via bus system
Detailed information can be found in the documentation of the corresponding bus system.
C# Create PDF from images Library to convert Jpeg, png images to
C#.NET Project DLLs for Conversion from Images to PDF in C#.NET Program. C# Example: Convert More than Two Type Images to PDF in C#.NET Application.
pdf image extractor online; extract image from pdf file
VB.NET PDF Page Extract Library: copy, paste, cut PDF pages in vb.
VB.NET: Extract All Images from PDF Document. This is an example that you can use it to extract all images from PDF document. ' Get page 3 from the document.
extract jpg from pdf; extract photos pdf
Parameter setting
Parameter setting with E82ZBC keypad
General data and operating conditions
9
224
EDS82EV903  EN  3.0
9.2
Parameter setting with E82ZBC keypad
9.2.1
General data and operating conditions 
0b
c
a
 


88888
8888
8888

PS

Hi
Hz
%sh
rpm
Ω°C
m
V A
Lo
E82ZBC011
Range
Values
Dimensions
Width
a
60 mm
Height
b
74 mm
Depth
c
17 mm
Environmental conditions
Climate
Storage
IEC/EN 60721−3−1
1K3 (−25 ... +60 °C)
Transport
IEC/EN 60721−3−2
2K3 (−25 ... +70 °C)
Operation
IEC/EN 60721−3−3
3K3 (−10 ... +60 °C)
Type of protection
IP 20
C# PDF Convert to Images SDK: Convert PDF to png, gif images in C#
Professional .NET library and Visual C# source code for creating high resolution images from PDF in C#.NET class. Cut and paste any areas in PDF pages to images.
extract color image from pdf in c#; extract photo from pdf
C# PDF Page Extract Library: copy, paste, cut PDF pages in C#.net
Page: Extract, Copy and Paste PDF Pages. Easy to Use C# Code to Extract PDF Pages, Copy Pages from One PDF File and Paste into Others in C#.NET Program.
extract images from pdf files without using copy and paste; extract images from pdf files
Parameter setting
Parameter setting with E82ZBC keypad
Installation and commissioning
9
225
EDS82EV903   EN   3.0
9.2.2
Installation and commissioning 
Note!
The keypad is rear−mounted to the terminal with a screw (remove rubber
protection).
The keypad can be mounted into a control cabinet door using the "Mounting
kit for control cabinets" E82ZBHT (board cutout 45.3 mm x 45.3 mm).
E82ZWLxxx
E82ZBB
E82ZBC
 


88888
8888
8888


PS

Hi
Hz
%sh
rpm
°CΩ
m
AV
Lo
 


88800
0050
0001


PS

Hi
Hz
%sh
rpm
°CΩ
m
AV
Lo
 


88800
0050
0001


PS

Hi
Hz
%sh
rpm
°CΩ
m
AV
Lo
888888888
8888

 
P S

H i
H
z
% s
h
rpm
°C
Ω
m A
V
Lo
 
88888
8888
8888


PS

Hi
Hz%sh
rp m
° C
Ω
m
AV
Lo
 


88800
0050
000
PS

Hi
Hz
%sh
rpm
Ω°C
m
VA
Lo
E82ZBC018
Fig. 9−1
Installation and commissioning of the E82ZBC keypad or E82ZBB diagnosis terminal
Connect keypad to the AIF interface on the front of the standard device.
It is possible to connect the keypad and remove it during operation.
As soon as the keypad is supplied with voltage, it carries out a short self−test.
The keypad is ready for operation, if it displays the "Disp" mode:
Current state of the standard device
Parameter set activated via terminal
Memory location 1 of the user menu (C0517):
Code number, subcode number, and current value
Current value in % of the status display defined in C0004
Press  to leave the "Disp" mode
VB.NET Create PDF from images Library to convert Jpeg, png images
VB.NET Guide for Converting Raster Images to PDF File Using VB.NET Sample Code. VB.NET Example of More than Two Images to PDF Conversion. This VB.
extract images pdf; extract images from pdf file
C# PDF Convert to Jpeg SDK: Convert PDF to JPEG images in C#.net
Following demo code will show how to convert all PDF pages to Jpeg images with C# .NET. // Load a PDF file. String inputFilePath
extract text from image pdf file; extract pdf images
Parameter setting
Parameter setting with E82ZBC keypad
Display elements and function keys
9
226
EDS82EV903  EN  3.0
9.2.3
Display elements and function keys 
Front view
Display mode
 


88888
8888
8888
PS

Hi
Hz
%sh
rpm
Ω°C
m
V A
Lo
 


000
0050
0001
PS

Hi
Hz
Lo
5
E82ZBC002
E82ZBC003
Fig. 9−2
Display elements and function keys of the E82ZBC keypad
Status displays
Meaning
Explanation
Ready for operation
Pulse inhibit active
Power outputs inhibited
Current limit set in motor mode or in
generator mode exceeded
C0022 (in motor mode) or C0023 (in generator mode)
Warning active
Fault active
Function bar 1
Meaning
Explanation
Setpoint selection via 
Not possible with active password protection (display
= ”loc”)
Display function:
User menu, memory location 1 (C0517/1),
display
Display active parameter set
Active after every mains connection
Select codes
Four−digit display of the active code number 
Select subcodes
Three−digit display of the active subcode number 
Change parameter value of a (sub−) code
Five−digit display of the current value 
Display values with more than 5 digits
H:
high−order digits
Display ”HI”
L:
low−order digits
Display ”lo”
Function bar 2
Meaning
Explanation
Select parameter set 1 ... 4 for changing
Display e.g. PS 2()
Activating parameter sets can be effected via
digital signals only (configuration with C0410)
Select node on system bus (CAN)
The node selected is paramaterisable from the
current drive
 = function active
Select menu
The user menu is active after every mains
switching
user
List of the codes in the user menu (C0517)
all
List of all codes
funci
Only specific codes for bus function modules
e.g. INTERBUS, PROFIBUS−DP, LECOM-B, ...
Bar graph display
Set value in C0004 in %
(Lenze setting: device utilisation C0056)
Display range: − 180 % ... + 180 % (every scale
line = 20 %)
Parameter setting
Parameter setting with E82ZBC keypad
Display elements and function keys
9
227
EDS82EV903   EN   3.0
Display parameter set
In mode :
display of the parameter set activated via
the digital signal
Otherwise:
Display of the parameter set that is active
for changing
Select the individual parameter sets in mode  in
function bar 2
Display of code number
Display of subcode number
Display of parameter value or fault indication
Function keys
Function
Explanation
Enable controller
Terminal X3/28 must additionally be at HIGH level
Inhibit drive controller (CINH) or quick stop
(QSP)
Configuration in C0469
Change function bar 1  function bar 2

To right/left in active function bar
The active function is framed

Increase/decrease value
change quickly: keep key pressed
Only blinking values can be changed
Save parameters when is blinking
Confirmation by STOre in display
Parameter setting
Parameter setting with E82ZBC keypad
Changing and saving parameters
9
228
EDS82EV903  EN  3.0
9.2.4
Changing and saving parameters 
Note!
ƒ
The user menu is active after mains switching. Change to the all menu to
address all codes.
ƒ
With the keypad you can only change parameter values in the parameter
sets.
ƒ
A parameter set can only be activated for operation by means of digital
signals (configuration via C0410)!
ƒ
In the  function, the keypad shows the parameter set which is currently
active during operation.
Step
Key seq.
Result
Action
1.
Connect keypad
xx.xx  Hz
The  function is active. The first code in the user
menu is displayed (C0517/1,
Lenze setting: C0050 = output frequency).
2.
If required, change
to the "ALL" menu
Change to function bar 2
3.

4.

all
Select "ALL" menu (list of all codes)
5.
Confirm selection and change to function bar 1
6.
Select parameter
set for change
Change to function bar 2
7.

8.

1 ... 4
Select parameter set to be changed
9.
Confirm selection and change to function bar 1
10.
Inhibit controller

Only necessary if you change C0002, C0148, C0174,
and/or C0469
11.
Set parameters

12.

XXXX
Select code
13.
001
For codes without subcodes: automatic skip to 
14.

xxx
Select subcode
15.
16.

XXXXX
Set parameter
17.
STOre
Confirm entry if  is blinking
Confirm entry if  is not blinking; 
is inactive
18.
Restart "loop" at 11. or 6. to set further parameters
Parameter setting
Parameter setting with E82ZBC keypad
Transferring parameters to other standard devices
9
229
EDS82EV903   EN   3.0
9.2.5
Transferring parameters to other standard devices
Parameter settings can be easily copied from one standard device to another using the
keypad.
Copy parameter sets from the standard device to the keypad
Step
Key seq.
Result
Action
1.
Connect the keypad to standard
device 1
xx.xx 
Hz
Function  is active. The first code in the
user menu (C0517/1, Lenze setting: C0050 =
output frequency) is displayed.
2.
Inhibit controller

The drive coasts.
3.
Select C0002 from the user menu
4.
0002
Select C0002
5.
6.
Select the correct copy function
The settings stored in the keypad are
overwritten.
Copy all available parameter sets (PAR1 ... PAR4, if required FPAR1) into the keypad:
–Standard device with function
module application I/O, AS
interface, 
INTERBUS, PROFIBUS,
LECOM−B, DeviceNet,
CANopen
80
Copy PAR1 ... PAR4 and FPAR1:
 Set "80"
–Standard device with all other
function modules
20
Copy PAR1 ... PAR4:
 Set "20"
Only copy the module−specific parameter set FPAR1 into the keypad:
–Only possible with standard
devices including function
module INTERBUS, 
PROFIBUS, LECOM−B,
DeviceNet, CANopen
50
Copy FPAR1:
 Set "50"
7.
Start copying
STOre
or
SaUe
The selected parameter sets are copied to the
keypad.
If STOrE or SaUe goes off, the copy process is
complete.
8.
Enable controller
The drive operates again.
Parameter setting
Parameter setting with E82ZBC keypad
Transferring parameters to other standard devices
9
230
EDS82EV903  EN  3.0
Copy parameter set from the keypad to the standard device
Step
Key seq.
Result
Action
1. Connect the keypad to standard
device 2
xx.xx 
Hz
Function  is active. The first code in the user
menu (C0517/1, Lenze setting: C0050 = output
frequency) is displayed.
2.
Inhibit controller

The drive is coasting.
3.
Select C0002 from the user menu
4.
0002
Select C0002
5.
6.
Select the correct copy function
The settings stored in the standard device or in
the function module are overwritten.
Copy all available parameter sets (PAR1 ... PAR4, if required FPAR1) into the standard device:
–Standard device with function
module application I/O, AS
interface, 
INTERBUS, PROFIBUS, LECOM−B,
DeviceNet, CANopen
70
Copy PAR1 ... PAR4 and FPAR1:
 Set "70"
–Standard device with all other
function modules
10
Copy PAR1 ... PAR4:
 Set "10"
Only copy the module−specific parameter set FPAR1 into the function module:
–Only possible with standard
devices including function
module INTERBUS, 
PROFIBUS, LECOM−B, DeviceNet,
CANopen
40
Copy FPAR1:
 Set "40"
Copy individual parameter sets (PARx and FPAR1 if available) to the standard device:
–Standard device with function
module application I/O,
INTERBUS, 
PROFIBUS, LECOM−B, DeviceNet,
CANopen
71
Copy PAR1 and FPAR1:
 Set "71"
72
Copy PAR2 and FPAR1:
 Set "72"
73
Copy PAR3 and FPAR1:
 Set "73"
74
Copy PAR4 and FPAR1:
 Set "74"
–Standard device with all other
function modules
11
Copy PAR1:  Set "11"
12
Copy PAR2:  Set "12"
13
Copy PAR3:  Set "13"
14
Copy PAR4:  Set "14"
7.
Start copying
STOre
or
load
The selected parameter sets are copied to the
standard device or to the function module.
If STOrE or load goes off, the copy process is
complete.
8.
Enable controller
The drive operates again.
Documents you may be interested