Function library
Operating mode
Vector control
10
261
EDS82EV903   EN   3.0
10.2.2
Vector control 
Description
Compared with the V/f characteristic control the vector control offers considerably higher
torque and lower current consumption during idle running. The vector control is an
improved motor current control following the Lenze FTC technology.  Select vector control
for operation of the following drives:
ƒ
Single drives with extremely changing loads
ƒ
Single drives with heavy start conditions
ƒ
Sensorless speed control of standard three−phase AC motors
Note!
ƒ
The connected motor should maximally be two power classes lower than
the motor assigned to the controller.
ƒ
The operation with vector control is not possible if several drives are
operated on one controller.
ƒ
The motor parameter identification is absolutely vital! Otherwise
commissioning is not possible.
Codes for parameter setting
Code
Possible settings
IMPORTANT
No.
Name
Lenze
Selection
C0014
Operating
mode
2
2
V/f characteristic control V ~ f
(linear characteristic with constant
V
min
boost)
Commissioning is possible
without identifying motor
parameters
Advantage of identification
with C0148:
–Improved smooth running at
low speeds
–V/f rated frequency (C0015)
and slip (C0021) are
calculated and saved. They do
not have to be entered
  255
3
V/f characteristic control V ~ f
2
(square−law characteristic with
constant V
min
boost)
4
Vector control
In the case of the first selection
enter the motor data and identify
them with C0148
Otherwise commissioning is not
possible
When C0014 = 5, C0019 must be
set = 0 (automatic DC injection
brake is deactivated)
5
Sensorless torque control with speed
limitation
Torque setpoint via C0412/6
Speed limitation via setpoint 1
(NSET1−N1) if C0412/1 is assigned,
otherwise via maximum frequency
(C0011)
C0015
uSEr
V/f rated
frequency
50.00
7.50
{0.02
Hz}
960.00
C0015 is calculated and saved
during the motor parameter
identification with C0148.
The setting applies to all
permitted mains voltages
  257
  261
C0021
Slip
compensation
0.0
−50.0
{0.1 %}
50.0
C0021 is calculated and saved
during the motor parameter
identification with C0148.
  268
C0054
*
Apparent
motor current
(MCTRL1−IMOT)
0.0
{A}
2000.0
Read only
C0087
Rated motor
speed
300
{1 rpm}
16000
Device−dependent
  315
Extract image from pdf acrobat - Select, copy, paste PDF images in C#.net, ASP.NET, MVC, Ajax, WinForms, WPF
Support PDF Image Extraction from a Page, a Region on a Page, and PDF Document
pdf image extractor online; extract image from pdf java
Extract image from pdf acrobat - VB.NET PDF Image Extract Library: Select, copy, paste PDF images in vb.net, ASP.NET, MVC, Ajax, WinForms, WPF
Support PDF Image Extraction from a Page, a Region on a Page, and PDF Document
extract images from pdf online; pdf image extractor c#
Function library
Operating mode
Vector control
10
262
EDS82EV903  EN  3.0
IMPORTANT
Possible settings
Code
Selection
Lenze
Name
No.
C0088 Rated motor
current
0.0
0.1 (A)
650.0
Device−dependent
0.0 ... 2.0 x rated output current of
the controller
  315
C0089
Rated motor
frequency
50
10
{1 Hz}
960
  315
C0090
Rated motor
voltage
50
{1 V}
500
230 V for 230 V controllers,
400 V for 400 V controllers
  315
C0091
Motor cos ϕ
0.40
{0.1}
1.0
Device−dependent
  315
C0092
Motor stator
inductance
0.0
0.000
{0.1 mH}
Device−dependent
  315
0.00
0.00
{0.01
mH}
Device−dependent
Only 8200 vector 15 ... 90 kW
C0148
*
Identifying
motor data
0
0
Ready
Only when the motor is cold!
1. Inhibit controller, wait until
drive is at standstill
2. Enter the correct values from
the motor nameplate in C0087,
C0088, C0089, C0090, C0091
3. Set C0148 = 1, confirm with
4. Enable controller:
The identification
–starts,  goes out
–the motor "whistles" faintly
but it does not rotate!
–takes approx. 30 s
–is completed when  is lit
again
5. Inhibit controller
  315
1
Start identification
V/f rated frequency (C0015), slip
compensation (C0021) and motor
stator inductance (C0092) are
calculated and saved
The motor stator resistance (C0084)
= total resistance of the motor cable
and motor is measured and saved
Setting of vector control
Use C0014 = 4 to set the operating mode "vector control".
Preparing motor parameter identification
You must enter the motor data of the motor nameplate:
ƒ
Rated motor speed (C0087)
ƒ
Rated motor current (C0088)
ƒ
Rated motor frequency (C0089)
ƒ
Rated motor voltage (C0090)
ƒ
Motor cos  (C0091)
Motor parameter identification
Carry out the motor parameter identification. ( 
  315 
)
.NET PDF Document Viewing, Annotation, Conversion & Processing
Convert image files to PDF. File & Page Process. Extract hyperlink inside PDF. PDF Write. Print. Support for all the print modes in Acrobat PDF.
extract images from pdf files; extract photos from pdf
C# PDF Converter Library SDK to convert PDF to other file formats
without using other external third-party dependencies like Adobe Acrobat. you can easily perform file conversion from PDF document to image or document
extract photo from pdf; pdf image extractor online
Function library
Operating mode
Vector control
10
263
EDS82EV903   EN   3.0
Automatically detected parameters
V/f−rated frequency (C0015), slip compensation (C0021) and motor stator inductivity
(C0092)  are calculated and  saved. The  total resistance of motor cable and motor is
measured and saved as motor stator resistance (C0084).
In general, the vector control is ready for operation without any further measures after the
motor parameters have been identified. The vector control must only be optimised in the
case of the following drive behaviour:
Drive behaviour
Remedy
Rough motor run and motor current (C0054) > 60 %
rated motor current in idle running (steady−state
operation)
1. Reduce motor stator inductance (C0092) by 10 %
2. Check motor current in C0054
3. If the motor current (C0054) is > 50 % of the rated
motor current:
–Reduce C0092 until the motor current is
approx. 50 % of the rated motor current
–Reduce C0092 by max. 20 %!
–Note: If you reduce C0092, the torque will
decrease!
Torque too low for frequencies f < 5 Hz (starting torque)
Increase motor resistance (C0084) or motor inductance
(C0092)
Poor speed stability at high load (setpoint and motor
speed are no longer proportional)
Increase slip compensation (C0021)
Overcompensation results in drive instability!
Error messages OC1, OC3, OC4 or OC5 at acceleration
times (C0012) < 1 s (controller is no longer able to
follow the dynamic processes)
Change reset time of the I
max
controller (C0078):
Reduce C0078 = I
max
controller becomes faster
(more dynamic)
Increase C0078 = I
max
controller becomes slower
("smoother")
C# Windows Viewer - Image and Document Conversion & Rendering in
without using other external third-party dependencies like Adobe Acrobat. Image and Document Conversion Supported by Windows Viewer. Convert to PDF.
pdf extract images; extract images from pdf files without using copy and paste
C# powerpoint - PowerPoint Conversion & Rendering in C#.NET
using other external third-party dependencies like Adobe Acrobat. SDK to convert PowerPoint document to PDF document code for PowerPoint to TIFF image conversion
some pdf image extractor; extract jpeg from pdf
Function library
Operating mode
Sensorless torque control with speed limitation
10
264
EDS82EV903  EN  3.0
10.2.3
Sensorless torque control with speed limitation 
Description
The setpoint linked with C0412/6 is interpreted as torque setpoint. Actual values are not
required. The controller varies the speed within the set frequency range in dependence of
the load and the torque selected.
The speed is limited via setpoint 1 or the maximum frequency.
Application with, for instance, winding drives.
Note!
ƒ
The sensorless torque control only operates in motor mode, not in generator
mode.
ƒ
The motor parameter identification is absolutely vital! Otherwise
commissioning is not possible.
Codes for parameter setting
Code
Possible settings
IMPORTANT
No.
Name
Lenze
Selection
C0014
Operating
mode
2
2
V/f characteristic control V ~ f
(linear characteristic with constant
V
min
boost)
Commissioning is possible
without identifying motor
parameters
Advantage of identification
with C0148:
–Improved smooth running at
low speeds
–V/f rated frequency (C0015)
and slip (C0021) are
calculated and saved. They do
not have to be entered
  255
3
V/f characteristic control V ~ f2
(square−law characteristic with
constant V
min
boost)
4
Vector control
In the case of the first selection
enter the motor data and identify
them with C0148
Otherwise commissioning is not
possible
When C0014 = 5, C0019 must be
set = 0 (automatic DC injection
brake is deactivated)
5
Sensorless torque control with speed
limitation
Torque setpoint via C0412/6
Speed limitation via setpoint 1
(NSET1−N1) if C0412/1 is assigned,
otherwise via maximum frequency
(C0011)
C0047
*
Torque
setpoint or
torque limit
(MCTRL1−
MSET)
400
0
{1 %}
400
The set value will be lost during
mains switching!
  264
Reference: Rated motor torque determined
through motor parameter identification
In "Sensorless torque control"
operating mode (C0014 = 5):
Torque setpoint selection if
C0412/6 = FIXED−FREE (not
assigned)
Torque setpoint display if
C0412/6 is linked to a signal
source
In "V/f characteristic control" or
"Vector control" operating mode
(C0014 = 2, 3, 4):
Display of the torque limit
value if C0412/6 is linked to a
signal source
Display C0047 = 400 if C0412/6
= FIXED−FREE (not assigned)
JPEG to PDF Converter | Convert JPEG to PDF, Convert PDF to JPEG
It can be used standalone. JPEG to PDF Converter is able to convert image files to PDF directly without the software Adobe Acrobat Reader for conversion.
extract images from pdf online; extract images from pdf acrobat
C# Word - Word Conversion in C#.NET
using other external third-party dependencies like Adobe Acrobat. Word SDK to convert Word document to PDF document. demo code for Word to TIFF image conversion
extract text from pdf image; extract color image from pdf in c#
Function library
Operating mode
Sensorless torque control with speed limitation
10
265
EDS82EV903   EN   3.0
IMPORTANT
Possible settings
Code
Selection
Lenze
Name
No.
C0077
*
Gain of the
I
max
controller
0.25
0.00
= P component
inactive
{0.01}
16.00
  327
C0078
*
Reset time of
the I
max
controller
65
13
0
12
{1 ms}
9990
= I component
inactive
Only 8200 vector 15 ... 90 kW)
  327
C0087
Rated motor
speed
300
{1 rpm}
16000
Device−dependent
  315
C0088
Rated motor
current
0.0
0.1 (A)
650.0
Device−dependent
0.0 ... 2.0 x rated output current of
the controller
  315
C0089
Rated motor
frequency
50
10
{1 Hz}
960
  315
C0090
Rated motor
voltage
50
{1 V}
500
230 V for 230 V controllers,
400 V for 400 V controllers
  315
C0091
Motor cos ϕ
0.40
{0.1}
1.0
Device−dependent
  315
C0092
Motor stator
inductance
0.0
0.000
{0.1 mH}
Device−dependent
  315
0.00
0.00
{0.01
mH}
Device−dependent
Only 8200 vector 15 ... 90 kW
C0148
*
Identifying
motor data
0
0
Ready
Only when the motor is cold!
1. Inhibit controller, wait until
drive is at standstill
2. Enter the correct values from
the motor nameplate in C0087,
C0088, C0089, C0090, C0091
3. Set C0148 = 1, confirm with
4. Enable controller:
The identification
–starts,  goes out
–the motor "whistles" faintly
but it does not rotate!
–takes approx. 30 s
–is completed when  is lit
again
5. Inhibit controller
  315
1
Start identification
V/f rated frequency (C0015), slip
compensation (C0021) and motor
stator inductance (C0092) are
calculated and saved
The motor stator resistance (C0084)
= total resistance of the motor cable
and motor is measured and saved
Setting of torque control
Use C0014 = 5 to set the operating mode "sensorless torque control".
Linking setpoint and selecting speed limitation
Link an external setpoint source with the torque setpoint via C0412/6.   (  328)
Select the type of speed limitation. The speed is limited via setpoint 1 or the maximum
frequency:
ƒ
Setpoint 1, if C0412/1 is linked with a setpoint source.
ƒ
Maximum frequency, if C0412/1 is not assigned.
PDF to WORD Converter | Convert PDF to Word, Convert Word to PDF
out transformation between different kinds of image files and Word Converter has accurate output, and PDF to Word need the support of Adobe Acrobat & Microsoft
some pdf image extract; pdf image extractor
VB.NET PDF: How to Create Watermark on PDF Document within
or image (such as business's logo) on any desired PDF page. And with our PDF Watermark Creator, users need no external application plugin, like Adobe Acrobat.
how to extract text from pdf image file; extract pdf images
Function library
Operating mode
Sensorless torque control with speed limitation
10
266
EDS82EV903  EN  3.0
Preparing motor parameter identification
You must enter the motor data of the motor nameplate:
ƒ
Rated motor speed (C0087)
ƒ
Rated motor current (C0088)
ƒ
Rated motor frequency (C0089)
ƒ
Rated motor voltage (C0090)
ƒ
Motor cos  (C0091)
Motor parameter identification
Carry out the motor parameter identification. ( 
  315 
)
Automatically detected parameters
V/f−rated frequency (C0015), slip compensation (C0021) and motor stator inductivity
(C0092)  are calculated and  saved. The  total resistance of motor cable and motor is
measured and saved as motor stator resistance (C0084).
Optimise sensorless torque control
After motor parameter identification, the sensorless torque control is generally ready for
operation without the need for further measures. The drive behaviour can be optimised
through the manual adjustment of a few parameters:
Drive behaviour
Remedy
Torque is not constant
Reduce motor inductance (C0092) by approx. 10 ... 20 %.
No−load current and maximum torque keep decreasing.
Drive does not accelerate from a standstill.
Increase the torque setpoint to 20 ... 25 %.
Controller is not able to follow quick load changes
Adapt gain (C0077) and reset time (C0078) of the I
max
controller:
Reduce C0078 = I
max
controller becomes faster
(more dynamic)
Increase C0078 = I
max
controller becomes slower
("smoother")
C# Excel - Excel Conversion & Rendering in C#.NET
using other external third-party dependencies like Adobe Acrobat. SDK to convert Excel document to PDF document. C# demo code for Excel to TIFF image conversion
extract image from pdf online; online pdf image extractor
VB.NET PowerPoint: VB Code to Draw and Create Annotation on PPT
other documents are compatible, including PDF, TIFF, MS free hand, rubber stamp, callout, embedded image, and ellipse more plug-ins needed like Acrobat or Adobe
extract images pdf acrobat; extract jpg pdf
Function library
Operating mode
Sensorless torque control with speed limitation
10
267
EDS82EV903   EN   3.0
Tip
ƒ
The minimum torque setpoint must not fall below 10 % (setting range 1 : 10).
ƒ
The motor may stall at operation with output frequencies < 3 Hz. If so, reset the
internal control by quickly switching the controller inhibit.
ƒ
If C0412/6 is combined with an analog signal source it is possible to display the
torque setpoint under C0047.
ƒ
If C0412/6 is not combined with an analog signal source (FIXED−FREE) it is possible
to select the torque setpoint under C0047. Please note:
–When disconnecting the mains, the value set will be lost!
–Before enabling the controller it is absolutely necessary at the restart to select the
correct setpoint under C0047. Otherwise the drive would start with the maximum
torque.
Note!
In the control modes "V/f characteristic control" and "vector control" the
signal combined with C0412/6 or C0047 act as a torque limitation.
Function library
Optimising the operating behaviour
Slip compensation
10
268
EDS82EV903  EN  3.0
10.3
Optimising the operating behaviour 
10.3.1
Slip compensation 
Description
Under load, the speed of an asynchronous machine is reduced. This load dependent speed
drop is called slip. The slip can be partly compensated by setting C0021 accordingly. The slip
compensation is effective for all control modes (C0014).
Codes for parameter setting
Code
Possible settings
IMPORTANT
No.
Name
Lenze
Selection
C0021
Slip
compensation
0.0
−50.0
{0.1 %}
50.0
C0021 is calculated and saved
during the motor parameter
identification with C0148.
  268
Automatic adjustment
The  slip  compensation  is  calculated  during  the motor  parameter  identification  and
entered under C0021.
Preparing motor parameter identification
You must enter the motor data of the motor nameplate:
ƒ
Rated motor speed (C0087)
ƒ
Rated motor current (C0088)
ƒ
Rated motor frequency (C0089)
ƒ
Rated motor voltage (C0090)
ƒ
Motor cos  (C0091)
Motor parameter identification
Carry out the motor parameter identification. ( 
  315 
)
Automatically detected parameters
V/f−rated frequency (C0015), slip compensation (C0021) and motor stator inductivity
(C0092) are  calculated and  saved. The  total resistance of motor cable and  motor is
measured and saved as motor stator resistance (C0084).
Function library
Optimising the operating behaviour
Slip compensation
10
269
EDS82EV903   EN   3.0
Manual adjustment
Manual adjustment of the slip compensation is only required if the motor parameter
identification is not carried out. For this purpose, a first coarse adjustment of the slip
compensation can be carried out on the basis of the motor data. Fine adjustment will be
carried out empirically when the drive is running:
Coarse adjustment
1. Roughly determine the slip compensation on the basis of the motor data and enter
it into C0021:
s
n
rsyn
n
r
n
rsyn
100%
n
rsyn
f
r
60
p
s
Slip constant (C0021) [%]
n
rsyn
Synchronous motor speed [min−1]
n
r
Rated motor speed according to motor nameplate [min−1]
f
r
Rated motor frequency according to motor nameplate
[Hz]
p
Number of motor pole pairs (1, 2, 3, ...)
s
1500min11435min1
1500min1
100% 4.33%
n
rsyn
50Hz60
2
1500min
1
Example of a 4−pole motor / 1435rpm / 50Hz:
Preset C0021=4.3%
Fine adjustment
2. Correct C0021 with the drive running until load−dependent speed drops do not occur
anymore in the desired speed range between idling and maximum motor load. The
following holds true as a guide value for correct slip compensation:
–Deviation from the rated speed  0.5% for output frequency 5 ... 50Hz (87Hz)
–Higher deviations are possible during field weakening operation
Note!
If C0021 is set too high, the drive may get unstable.
Setting tips
ƒ
With speed control, set C0021 = 0.0 with the internal process controller.
ƒ
A negative slip (C0021<0) in the "V/f characteristic control" operating mode results
in a "smoother" drive behaviour in case of high load impulses or applications
including multiple motors.
Function library
Optimising the operating behaviour
Inverter switching frequency
10
270
EDS82EV903  EN  3.0
10.3.2
Inverter switching frequency
Description
The switching frequency of the inverter influences the smooth running performance, the
power loss inside the controller, and the noise generation in the connected motor. The
Lenze setting of 8 kHz is the optimum value for standard applications. The following
general rule applies:
The lower the switching frequency the
ƒ
lower the power loss.
ƒ
higher the noise generation.
Moreover you can determine whether the switching frequency is changed over to 4 kHz if
the heatsink temperature only amounts to approx. 5 °C below the permissible maximum
temperature.  This  serves  to  prevent  the  drive  from  being  inhibited  by  the
"overtemperature" error and the motor from coasting without torque.
Note!
Note that when operating with a switching frequency of 16 kHz the output
current must be reduced to prevent the controller from being overheated
(derating).
The current limit values (C0022 and C0023) must be adapted so that the
currents given in the technical data will not be exceeded.
Codes for parameter setting
Code
Possible settings
IMPORTANT
No.
Name
Lenze
Selection
C0018
Switching
frequency
2
0
2 kHz sin
General rule:
The lower the switching frequency
the
lower the power loss
higher the noise generation
Only operate mid−frequency
motors at 8 kHz sin or 16 kHz sin
(C0018 = 2 or 3)!
  270
1
4 kHz sin
2
8 kHz sin
low noise
generation
3
16 kHz sin
C0018
Switching
frequency
(only 8200 vect
or 15 ... 90 kW)
6
0
2 kHz sin
General rule:
The lower the switching frequency
the
lower the power loss
higher the noise generation
Only operate mid−frequency
motors at 8 kHz sin or 16 kHz sin
(C0018 = 2 or 3)!
  270
1
4 kHz sin
2
8 kHz sin
low noise
generation
3
16 kHz sin
4
2 kHz
low power loss
5
4 kHz
6
8 kHz
7
16 kHz
8
1 kHz sin
9 ... 11
Reserved
12
1 kHz
low power loss