Function library
Optimising the operating behaviour
Inverter switching frequency
10
271
EDS82EV903   EN   3.0
IMPORTANT
Possible settings
Code
Selection
Lenze
Name
No.
C0144
Temperature−
dependent
reduction of
the switching
frequency
1
0
No temperature−dependent reduction
of the switching frequency
During operation at a switching
frequency of 16 kHz the frequency
is also reduced to 4 kHz. This
behaviour can be changed in
C0310.
  270
1
Automatic reduction of the switching
frequency to 4 kHz if  reaches max. − 5
°C
Automatic switching frequency reduction
C0144=0 (no temperature−dependent switching frequency reduction)
If  the  maximum  heatsink  temperature  (
max
is  exceeded  when  using  a  switching
frequency of 8 kHz or 16kHz) the inverter will be inhibited, TRIP "OH" (overtemperature)
will be set and the motor will coast to standstill.
C0144=1 (temperature−dependent switching frequency reduction is active):
ƒ
If the heatsink temperature 
max
− 5°C is reached when using a switching frequency
of 8 kHz or 16kHz the controller automatically reduces the switching frequency to
4kHz thus keeping the operation running.
ƒ
After cooling the heatsink the controller automatically changes to the switching
frequency set.
Note!
The switching frequency is automatically set to its optimum value depending
on the apparent motor current and output frequency to ensure trouble−free
operation.
ƒ
The noise emission changes.
ƒ
The user cannot influence this function.
Tip
Medium−frequency motors are only allowed to be operated on 8 kHz sin or 16 kHz sin.
Extract jpg from pdf - Select, copy, paste PDF images in C#.net, ASP.NET, MVC, Ajax, WinForms, WPF
Support PDF Image Extraction from a Page, a Region on a Page, and PDF Document
extract pictures from pdf; extract image from pdf in
Extract jpg from pdf - VB.NET PDF Image Extract Library: Select, copy, paste PDF images in vb.net, ASP.NET, MVC, Ajax, WinForms, WPF
Support PDF Image Extraction from a Page, a Region on a Page, and PDF Document
extract images from pdf; how to extract images from pdf
Function library
Optimising the operating behaviour
Oscillation damping
10
272
EDS82EV903  EN  3.0
10.3.3
Oscillation damping 
Description
Suppression of idling oscillations when:
ƒ
the rated power of controller and motor of a drive do not match, e.g. at operation
with high switching frequency and the related power derating
ƒ
Operation of higher−pole motors
ƒ
Operation of special motors
Compensation of resonances in the drive
ƒ
Some asynchronous motors can show this behaviour when being operated with an
output frequency of approx. 20...40Hz. As a result, operation can be instable
(current and speed fluctuations).
Codes for parameter setting
Code
Possible settings
IMPORTANT
No.
Name
Lenze
Selection
C0079
Oscillation
damping
2
0
{1}
140
  272
Adjustment
1. Approach with speed oscillations.
2. Reduce the speed oscillations by changing C0079 step by step. Additional indicators
for smooth running can be:
–uniform motor current
–reduction of mechanical vibrations in the bearing seat
Note!
Compensate the resonances in speed−controlled operation via the parameters
of the controller only.
C# PDF Convert to Jpeg SDK: Convert PDF to JPEG images in C#.net
NET library to batch convert PDF files to jpg image files. High Turn multiple pages PDF into single jpg files respectively online. Support
extract vector image from pdf; extract image from pdf file
VB.NET PDF Convert to Jpeg SDK: Convert PDF to JPEG images in vb.
PDF to images, C#.NET PDF file & pages edit, C#.NET PDF pages extract, copy, paste, C# NET components to batch convert adobe PDF files to jpg image files.
pdf image text extractor; how to extract pictures from pdf files
Function library
Optimising the operating behaviour
Skip frequencies
10
273
EDS82EV903   EN   3.0
10.3.4
Skip frequencies 
Description
With certain output frequencies, mechanical resonances might occur (e. g. fan).The skip
frequencies  suppress  these  unwanted  output  frequencies.  The  bandwidth  (f)
determines the skip frequency range.
The function is in the block NSET1 before the ramp function generator.
Codes for parameter setting
Code
Possible settings
IMPORTANT
No.
Name
Lenze
Selection
C0625
*
Blocking
frequency 1
0.00
0.00
{0.02
Hz}
650.00
  273
C0626
*
Blocking
frequency 2
0.00
0.00
{0.02
Hz}
650.00
C0627
*
Blocking
frequency 3
0.00
0.00
{0.02
Hz}
650.00
C0628
*
Skipping
bandwidth −
blocking
frequencies
0.00
0.00
{0.01 %}
100.00
Applies to C0625, C0626, C0627
C# Image Convert: How to Convert Adobe PDF to Jpeg, Png, Bmp, &
String inputFilePath = @"C:\input.pdf"; String outputFilePath = @"C:\output.jpg"; // Convert PDF to jpg. C# sample code for PDF to jpg image conversion.
how to extract a picture from a pdf; extract images from pdf c#
C# Image Convert: How to Convert Tiff Image to Jpeg, Png, Bmp, &
RasterEdge.XDoc.PDF.dll. String inputFilePath = @"C:\input.tif"; String outputFilePath = @"C:\output.jpg"; // Convert tiff to jpg.
extract images from pdf file; pdf image extractor c#
Function library
Optimising the operating behaviour
Skip frequencies
10
274
EDS82EV903  EN  3.0
Adjustment
Note!
ƒ
Blocking frequencies act on the main setpoint only.
ƒ
C0625, C0626, C0627 and C0628 are equal in all parameter sets.
ƒ
Set the desired blocking frequencies in C0625, C0626 and C0627.
ƒ
C0628 defines the bandwidth of fading.
–Calculate the bandwidth (f) for the respective blocking frequency:
f[Hz]  2 f
s
[Hz] 
C0628[%]
100%
f
s
blocking frequency
C0627
C0626
C0625
f
in
f
out
f=2xC0625x
C0628
100%
f=2xC0626x
C0628
100%
f=2xC0627x
C0628
100%
8200vec525
Fig. 10−4
Effect of the skip frequencies
f
in
Input frequency of the function
f
out
Output frequency of the function
C# Create PDF from images Library to convert Jpeg, png images to
Batch convert PDF documents from multiple image formats, including Jpg, Png, Bmp, Gif, Tiff, Bitmap, .NET Graphics, and REImage.
extract pictures pdf; extract image from pdf using
VB.NET PDF - Convert PDF with VB.NET WPF PDF Viewer
read PDF, VB.NET convert PDF to text, VB.NET extract PDF pages, VB PDF to image file formats with high quality, support converting PDF to PNG, JPG, BMP and
extract text from image pdf file; extract pdf pages to jpg
Function library
Behaviour in the event of mains switching, mains failure or controller inhibit
Start conditions/flying−restart circuit
10
275
EDS82EV903   EN   3.0
10.4
Behaviour in the event of mains switching, mains failure or controller inhibit 
10.4.1
Start conditions/flying−restart circuit 
Description
Determines  the  controller  behaviour  after  a  restart  after  controller  inhibit,  mains
switching or a mains failure.
With  activated  flying−restart  circuit  the  controller  automatically  synchronises  to  a
coasting motor after mains disconnection or adds a setpoint signal.
Codes for parameter setting
Code
Possible settings
IMPORTANT
No.
Name
Lenze
Selection
C0142
Starting
condition
1
0
Automatic start is inhibited after
mains connection
Flying restart circuit inactive
Start after HIGH−LOW−HIGH level
change at X3/28
  275
1
Automatic start if X3/28 = HIGH
Flying restart circuit inactive
2
Automatic start is inhibited after
mains connection
Flying restart circuit active
Start after HIGH−LOW−HIGH level
change at X3/28
3
Automatic start if X3/28 = HIGH
Flying restart circuit active
C0143
*
Selection of
flying restart
mode
0
0
Max. output frequency (C0011) ... 0 Hz
Motor speed is searched for in the
stated range
  275
1
Last output frequency ... 0 Hz
2
Connect frequency setpoint
(NSET1−NOUT)
The respective value is connected
after the controller enable
3
Connect actual process controller value
(C0412/5) (PCTRL1−ACT)
Drive behaviour without flying−restart circuit
Manual start (C0142 = 0):
After mains interruption the drive only restarts after a LOW/HIGH level change at the
"Controller inhibit" terminal (X3/28).
Automatic start (C0142 = 1)
After mains interruption the drive only restarts if a HIGH level is applied to the "controller
inhibit"terminal (X3/28).
The controller sets all integrators to zero and releases them again.
Drive behaviour with flying−restart circuit
Manual start with flying−restart circuit (C0142 = 2)
After mains interruption the drive only restarts after a LOW/HIGH level change at the
"Controller inhibit" terminal (X3/28).
Automatic start with flying−restart circuit (C0142 = 3)
After mains interruption the drive only restarts if a HIGH level is applied to the "controller
inhibit"terminal (X3/28).
C# WPF PDF Viewer SDK to convert and export PDF document to other
C#.NET PDF file & pages edit, C#.NET PDF pages extract, copy, paste PDF to image file formats with high quality, support converting PDF to PNG, JPG, BMP and
how to extract images from pdf file; extract image from pdf c#
VB.NET Create PDF from images Library to convert Jpeg, png images
Support create PDF from multiple image formats in VB.NET, including Jpg, Png, Bmp, Gif, Tiff, Bitmap, .NET Graphics, and REImage.
extract photos pdf; extract jpg from pdf
Function library
Behaviour in the event of mains switching, mains failure or controller inhibit
Start conditions/flying−restart circuit
10
276
EDS82EV903  EN  3.0
Flying restart
With the selection of the flying restart(C0143) you define whether the controller searches
for the motor speed after the restart or adds a signal.
Searching for the motor speed (C0143 = 0, C0143 = 1)
The drive starts if the momentary motor speed has been found. The acceleration is steady
and smooth
Note!
ƒ
The flying−restart circuit must not be used if several motors with different
rotating masses are connected to a controller.
ƒ
The flying restart method is safe and reliable for drives with great rotating
masses.
ƒ
With machines with low moments of inertia and small friction, the motor
can restart for a short time or reverse after controller enable.
ƒ
The controller only searches the given direction of rotation.
ƒ
The controller calculates the output frequency required for the current speed of the
idling motor, is connected and accelerates the motor until it reaches its setpoint.
Adding a signal (C0143 = 2, C0143 = 3)
The controller adds the output frequency corresponding to the frequency setpoint or the
actual process controller value.
Note!
The actual process controller value must only be set if a speed−proportional
signal is available in C0412/5!
Tip
If the flying−restart circuit  is not required  for every drive start, but only after mains
reconnection:
ƒ
Bridge X3/28 with HIGH level and start the controller with the function QSP"
(C0142=3 and C0106=0s).
ƒ
The flying−restart circuit is now only activated for for the first mains connection.
Function library
Behaviour in the event of mains switching, mains failure or controller inhibit
Controller inhibit
10
277
EDS82EV903   EN   3.0
10.4.2
Controller inhibit 
Description
If the controller inhibit is active, the power outputs are inhibited.
ƒ
The drive idles to standstill without torque.
ƒ
Keypad status display: Pulse inhibit 
ƒ
Status display of the controller: The green LED is blinking.
Danger!
Do not use controller inhibit (DCTRL1−CINH) as emergency off. The controller
inhibit only inhibits the power outputs and does  not  disconnect the controller
from the mains!
The drive could restart any time.
Codes for parameter setting
Code
Possible settings
IMPORTANT
No.
Name
Lenze
Selection
C0040
*
Controller
inhibit (CINH)
−0−
Controller inhibited (CINH)
Controller can only be enabled if
X3/28 = HIGH
  277
−1−
Controller enabled (CINH
)
Activation
ƒ
Via terminal X3/28:
–LOW level at the terminal activates the controller inhibit (cannot be inverted)
–HIGH level enables the controller again
ƒ
Via digital signal (linking C0410/10 with a signal source):
–LOW level at the signal source activates the controller inhibit (level inversion is
possible with C0411)
–HIGH level releases the controller again
ƒ
Via keypad (condition: C0469 = 1):
– activates the controller inhibit
– enables the controller again
ƒ
Via code C0040:
–C0040 = 0 activates the controller inhibit
–C0040 = 1 enables the controller again
Note!
ƒ
The sources for controller inhibit are ANDed, i. e. the drive only restarts
when the controller inhibit is cancelled at all signal sources.
ƒ
The restart begins with an output frequency of 0 Hz, i.e. if the flying−restart
circuit is not activated, still rotating masses can lead to generative overload.
Function library
Behaviour in the event of mains switching, mains failure or controller inhibit
Controlled deceleration after mains failure/mains disconnection
10
278
EDS82EV903  EN  3.0
10.4.3
Controlled deceleration after mains failure/mains disconnection 
Description
Note!
ƒ
The function described below can be used for max. 1.5 kW rated controller
power. If this function is to be used for greater controller powers, Lenze
must be consulted first.
ƒ
The deceleration time until standstill cannot be defined exactly. It depends
on the machine/system components (mass inertia, friction, ...).
Controlled deceleration of the motor to a standstill (f = 0) in case of mains switch−off or
mains failure.
The function can be implemented with or without external brake resistor:
This function serves to prevent the drive from coasting in case of an emergency switching
off (controller is activated via mains).
Without external brake resistor
ƒ
Controlled deceleration of the motor to a standstill (f = 0) if the controller is active.
ƒ
The braking energy stems from the system losses (controller and motor).
With external brake resistor
ƒ
Automatic, quick deceleration of the motor to a standstill (f = 0).
ƒ
The deceleration time is shorter than it is without external brake resistor.
Functional sequence
1. The mains voltage is interrupted.
2. The DC−bus voltage (V
DC
) falls below the value in C0988  the controller switches
over to parameter set 1.
3. The drive brakes along the quick stop ramp (C0105 in parameter set 1).
4. Due to operation in generator mode, V
DC
exceeds the value in C0988  the
controller switches over to parameter set 2.
5. The motor accelerates along the acceleration ramp (C0012 in parameter set 2).
6. If the DC−bus voltage falls below the value in C0988 again, the process starts all over
again with step 2.
Steps 2. to 6. are carried out until a motor speed of approx. zero is reached because the
rotational energy in the motor conserves V
DC
.
If the motor is not at a standstill at the time when the mains recovers, the drive will
accelerate to the selected setpoint along the acceleration ramp (C0012). The drive will then
start immediately which results in a rough restart, compared to the flying restart circuit.
Function library
Behaviour in the event of mains switching, mains failure or controller inhibit
Controlled deceleration after mains failure/mains disconnection
10
279
EDS82EV903   EN   3.0
Codes for parameter setting
Code
Possible settings
IMPORTANT
No.
Name
Lenze
Selection
C0988
*
DC−bus voltage
threshold for
DC−bus voltage
control
0
0
= changeover of
the parameter set
via DC−bus
voltage
deactivated
{1 %}
200
It is always changed over
between PAR1 and PAR2
Changeover of the parameter
set via terminal, bus or PC is
not possible if C988 > 0!
  278
  294
Adjustment
Parameter
Code
Setting parameter set 1
(active in case of mains failure)
Setting parameter set 2
(active during normal operation)
Switching threshold
C0988
Set C0988 to approx. 10 % undervoltage:
AC 230 V  C0988 = 75 ... 85 %
AC 400 V  C0988 = 75 ... 85 %
AC 460 V  C0988 = 75 ... 98 %
Terminal configuration
C0410
Link C0410/4 (DCTRL1−QSP) to a digital
input (X3/E1 ... X3/E6).
Set the terminal configuration for
normal operation.
Quick stop (QSP) active during
normal operation
Invert this input via C0411.
(Lenze setting = LOW−active)
The digital input linked to DCTRL1−QSP
in parameter set 1 must also be linked
to DCTRL1−QSP (not inverted).
Interconnect the digital input.
No quick stop (QSP) during
normal operation
Do not interconnect this input.
The digital input linked to DCTRL1−QSP
in parameter set 1 must not be used.
Deceleration time for quick stop
(QSP)
C0105
Without external brake resistor
Select a value which ensures a
controlled deceleration of the motor to
a standstill after mains disconnection:
1. Set the same value as in parameter
set 2.
2. Switch off mains voltage.
–Parameter set 1 is activated.
–Observe whether the controller
reports an "Overvoltage OU"
during the controlled deceleration.
3. Repeat the controlled deceleration
and reduce C0105 until the
controller reports an "OU" in the
process.
4. Increase this value by approx. 20 %
as a final setting.
Set the deceleration time for QSP
required for the application.
With external brake resistor
Select an external brake resistor with
sufficient dimensioning.
1. Set C0105 as in parameter set 2.
2. Reduce C0105 until the desired
deceleration time is reached after
mains disconnection.
Function library
Behaviour in the event of mains switching, mains failure or controller inhibit
Controlled deceleration after mains failure/mains disconnection
10
280
EDS82EV903  EN  3.0
Setting tips
Keep the deceleration as smooth as possible by setting the upper limit of the specified
bandwidth in C0988.
Do not exceed the current limit (generator mode) during the controlled deceleration.
Note!
ƒ
Changeover of the parameter set via terminal, bus or PC is not possible if
C0988 > 0!
ƒ
C0988 is always the same for all parameter sets.