load pdf in webbrowser control c# : Extract pdf images Library application component asp.net html web page mvc E82EV__8200%20vector%200.25-90kW__v3-0__EN29-part1602

Function library
Acceleration, deceleration, braking, stopping
Changing the direction of rotation
10
291
EDS82EV903   EN   3.0
10.6.3
Changing the direction of rotation  
Description
Change of direction of motor rotation via digital control signals. Only the main setpoint is
changed.
The direction of rotation can be changed in a fail−safe or non−fail−safe way. Depending on
the type of change−over, the controller brakes the motor to 0 Hz along the deceleration
ramp or quick stop ramp in order to accelerate the motor along the acceleration ramp in
the other direction of rotation.
The reversing time depends on the ramp times set for the main setpoint or quick stop.
Non−fail−safe change of the direction of rotation
Link C0410/3 to a digital signal source.
If the direction of rotation is changed, the drive brakes along the deceleration ramp
(C0013) and accelerates along the acceleration ramp (C0012) in the other direction or
rotation.
Direction of rotation with in−phase connection and HIGH active signal:
ƒ
LOW = CW rotation
ƒ
HIGH = CCW rotation
Note!
In case of open circuit or failure of the external control voltage, the drive may
reverse the direction of rotation.
Fail−safe change of the direction of rotation
Link C0410/22 and C0410/23 with one digital signal source each.
If the direction of rotation is changed, the drive brakes along the quick stop ramp (C0105)
and accelerates along the acceleration ramp (C0012) in the other direction or rotation.
Direction of rotation with in−phase connection and HIGH active signal:
Direction of rotation
Signal level at
Notes
C0410/22
(DCTRL1−CW/QSP)
C0410/23
(DCTRL1−CCW/QSP)
CCW rotation
LOW
HIGH
CW rotation
HIGH
LOW
Quick stop
LOW
LOW
Unchanged
HIGH
HIGH
During operation: The direction of
rotation results from the signal which
was active first.
When switching on the mains: The
controller activates quick stop (QSP).
Note!
In addition to the free configuration in C0410 you can also use the fixed
assignment in C0007 to link the "change direction of rotation" function with a
digital input.
Extract pdf images - Select, copy, paste PDF images in C#.net, ASP.NET, MVC, Ajax, WinForms, WPF
Support PDF Image Extraction from a Page, a Region on a Page, and PDF Document
extract pdf pages to jpg; extract image from pdf java
Extract pdf images - VB.NET PDF Image Extract Library: Select, copy, paste PDF images in vb.net, ASP.NET, MVC, Ajax, WinForms, WPF
Support PDF Image Extraction from a Page, a Region on a Page, and PDF Document
extract text from pdf image; extract images from pdf files without using copy and paste
Function library
Acceleration, deceleration, braking, stopping
DC braking (DCB)
10
292
EDS82EV903  EN  3.0
10.6.4
DC braking (DCB) 
Description
The DC−injection brake enables quick deceleration of the drive to standstill without using
an  external  brake  resistor.  The  DC−injection  brake  can  be activated via  terminal  or
automatically.
ƒ
The braking torque amounts to approx. 20...30% of the rated motor torque. It is
lower than for braking in generator mode with external brake resistor.
ƒ
A brake voltage or a brake current can be selected.
ƒ
Automatic DC braking improves the starting performance of the motor e.g. when
operating hoists.
Codes for parameter setting
Code
Possible settings
IMPORTANT
No.
Name
Lenze
Selection
C0019 Operating
threshold −
automatic DC
injection brake
(auto DCB)
0.10
0.00
= inactive
{0.02
Hz}
650.00 Hold time  C0106
Deactivate automatic DC injection
brake (auto DBC):
at active lower frequency
limitation (C0239)
at operating mode C0014 = 5
In the case of a max. output
frequency > 50 Hz (C0011), the
switching threshold of the auto
DCB in C0019 must be increased.
  292
C0035
*
Operation
mode − DC
injection brake
(DCB)
0
0
Brake voltage selection under C0036
Hold time  C0107
  292
1
Brake current selection under C0036
C0036
Voltage/
current DC
injection brake
(DCB)
0.00
{0.01 %}
150.00 %
Device−dependent
Based on V
rated
, I
rated
Setting applies to all permitted
mains voltages
  292
C0106
Hold time −
automatic DC
injection brake
(auto DCB)
0.50
0.00
= auto DCB
inactive
{0.01 s}
999.00
= 
Hold time if DC injection braking
is triggered because the value falls
below C0019
  292
C0107
Hold time − DC
injection brake
(DCB)
999.0
0
1.00
{0.01 s}
999.00
= 
Hold time if DC injection braking
is externally triggered via terminal
or control word
  292
C0196
*
Activation auto
DCB
0
0
Auto DCB active if PCTRL1−SET3 <
C0019
  292
1
Auto DCB active if PCTRL1−SET3 <
C0019 and NSET1−RFG1−IN < C0019
C# PDF Text Extract Library: extract text content from PDF file in
Ability to extract highlighted text out of PDF document. Image text extraction control provides text extraction from PDF images and image files.
how to extract images from pdf files; extract images from pdf acrobat
VB.NET PDF Text Extract Library: extract text content from PDF
Extract highlighted text out of PDF document. Image text extraction control provides text extraction from PDF images and image files.
extract image from pdf file; extract jpeg from pdf
Function library
Acceleration, deceleration, braking, stopping
DC braking (DCB)
10
293
EDS82EV903   EN   3.0
Adjustment
1. Use C0035 to select whether a brake voltage or a brake current shall be selected.
2. Enter the brake voltage or brake current under C0036 in percent.
–If C0035=0, the data refers to the rated voltage of the controller.
–If C0035=1, the data refers to the rated current of the controller.
3. Select how to activate the DC injection brake:
–Via digital input signal (configuration with C0410/15)
–Automatically when the values are fallen below the operating threshold C0019
(condition: C0106 > 0.00 s)
Activate DC−injection braking via input signal (DCB)
Link C0410/15 with a digital signal source.
In case of HIGH−active inputs, the DC−injection braking (DCB) remains active as long as the
signal is on HIGH level.
After the hold time (C0107) has elapsed, the controller sets pulse inhibit (keypad display:
).
Note!
In addition to the free configuration in C0410 you can also use the fixed
assignment in C0007 to link the function with a digital input.
Activate automatic DC−injection braking (auto DCB)
1. Select the hold time >0.00 s under C0106:
–The automatic DC−injection braking (auto DCB) is active for the set time.
–Afterwards, the controller sets pulse inhibit (keypad display: ).
2. Select the condition for activating the automatic DC−injection braking under C0196:
–C0196=0: auto DCB active if the output frequency is lower than the operating
threshold (C0050<C0019)
–C0196=1: auto DCB is active if the output frequency is lower than the operating
threshold (C0050<C0019) and the setpoint is lower than the operating threshold
(setpoint<C0019)
3. Set the operating threshold under C0019.
Note!
If DC−injection braking is operated too long with high brake current or brake
voltage, the connected motor can be overheated!
Setting tips
ƒ
Use C0019 to set a dead band in the setpoint. If DC−injection braking is not to be
active here, set C0106 = 0.00 s.
ƒ
C0019 can be referred to a process variable.
VB.NET PDF Page Extract Library: copy, paste, cut PDF pages in vb.
VB.NET: Extract All Images from PDF Document. This is an example that you can use it to extract all images from PDF document. ' Get page 3 from the document.
extract images pdf acrobat; pdf extract images
C# Create PDF from images Library to convert Jpeg, png images to
Create PDF from Images. |. Home ›› XDoc.PDF ›› C# PDF: Create PDF from Images. C#.NET PDF - Create PDF from Images in C# with XDoc.NET PDF Control.
extract vector image from pdf; extract images from pdf c#
Function library
Acceleration, deceleration, braking, stopping
AC motor braking
10
294
EDS82EV903  EN  3.0
10.6.5
AC motor braking 
Description
With the parameter set changeover in dependence of the DC−bus voltage, the AC motor
braking can be used as alternative for DC braking (DCB). The AC motor braking is a braking
method without external brake resistor for the control mode V/f characteristic control
with linear characteristic".
Note!
The AC motor braking can only be used with the control mode V/f
characteristic control with linear characteristic" (C0014 = 2).
ƒ
With mains voltages up to approx. AC 400 V shorter braking times can be reached
than with the DC injection braking.
ƒ
The braking times for braking via an external brake resistor are approx. 33 % shorter
than for AC motor braking.
Codes for parameter setting
Code
Possible settings
IMPORTANT
No.
Name
Lenze
Selection
C0988
*
DC−bus voltage
threshold for
DC−bus voltage
control
0
0
= changeover of
the parameter set
via DC−bus
voltage
deactivated
{1 %}
200
It is always changed over
between PAR1 and PAR2
Changeover of the parameter
set via terminal, bus or PC is
not possible if C988 > 0!
  278
  294
C# PDF Page Extract Library: copy, paste, cut PDF pages in C#.net
Page: Extract, Copy and Paste PDF Pages. Easy to Use C# Code to Extract PDF Pages, Copy Pages from One PDF File and Paste into Others in C#.NET Program.
how to extract pictures from pdf files; extract photos from pdf
C# PDF Convert to Images SDK: Convert PDF to png, gif images in C#
C#.NET PDF SDK - Convert & Render PDF to Images in C#.NET. Free .NET DLLs for converting PDF to images in both .NET WinForms and ASP.NET application.
pdf image extractor c#; pdf image extractor
Function library
Acceleration, deceleration, braking, stopping
AC motor braking
10
295
EDS82EV903   EN   3.0
Adjustment
Parameter
Code
Setting parameter set 1
(active during normal operation)
Setting parameter set 2
(active during braking operation)
Switching threshold
C0988
Set C0988 depending on the mains voltage:
AC 230 V  C0988 = 112 %
AC 400 V  C0988 = 112 %
AC 440 V  C0988 = 123 %
AC 460 V  C0988 = 129 %
AC 480 V  C0988 = 134 %
AC 500 V  C0988 = 140 %
V/f rated frequency
C0015
Value adapted to the drive, e.g. 50 Hz
Depending on the drive power, up to a
minimum of 25 % of the value of C0015
in parameter set 1:
General rule: 2.2 kW  50 %
Reduce value in case of smaller drive
powers. Increase value in case of
higher drive powers.
That way, the energy in the motor is
reduced due to overexcitation during
operation with parameter set 2.
V
min
boost
C0016
Value adapted to the drive, e.g. 5 %
Depending on the drive power, up to
five times the value of C0016 in
parameter set 1:
General rule: 2.2 kW  factor 3
Reduce factor in case of smaller drive
powers. Increase factor in case of
higher drive powers.
That way, the energy in the motor is
also reduced in the lower speed range
due to overexcitation during operation
with parameter set 2.
Deceleration time for quick stop
during braking along the quick stop
ramp:
C0105
Required braking time for AC braking
Deceleration time of the drive with
max. centrifugal load.
The OU message (overvoltage) must not
be provided during the deceleration.
Deceleration time during the
braking process at the main setpoint
ramp:
C0013
Setting tips
The higher the mains voltage the longer the deceleration time must be set in parameter
set 1 in order to be able to carry out AC motor braking. Hence, braking times with DC
injection brakes are shorter at mains voltages > 400 V.
Note!
ƒ
Changeover of the parameter set via terminal, bus or PC is not possible if
C0988 > 0!
ƒ
C0988 is always the same for all parameter sets.
C# PDF Convert to Jpeg SDK: Convert PDF to JPEG images in C#.net
Following demo code will show how to convert all PDF pages to Jpeg images with C# .NET. // Load a PDF file. String inputFilePath
extract photos pdf; extract text from image pdf file
C# PDF insert image Library: insert images into PDF in C#.net, ASP
Powerful .NET PDF image edit control, enable users to insert vector images to PDF file. Merge several images into PDF. Insert images into PDF form field.
extract images pdf; extract pdf images
Function library
Configuration of analog and digital setpoints and actual values
Setpoint source selection
10
296
EDS82EV903  EN  3.0
10.7
Configuration of analog and digital setpoints and actual values  
10.7.1
Setpoint source selection 
Description
Fixed setpoint source selection.
ƒ
C0001 = 0, 2: Setpoint source as described in the following. Link the setpoint source
with the internal analog signal under C0412.
ƒ
C0001 = 1: Setpoint source is the parameter channel of AIF. The freely configurable
signals are switched off" (C0412/x = 0 or 255). The setpoint must be written to the
codes which are assigned to the signals (see signal flow charts or description of
C0412).
ƒ
C0001 = 3: Setpoint source is the process data channel of AIF. The setpoint is written
to an AIF input word (AIF−IN.W1 or AIF−IN.W2). Link the AIF input word with the
internal analog signal under C0412.
Function library
Configuration of analog and digital setpoints and actual values
Setpoint source selection
10
297
EDS82EV903   EN   3.0
Codes for parameter setting
Code
Possible settings
IMPORTANT
No.
Name
Lenze
Selection
C0001
Setpoint
selection
(operating
mode)
0
A change in C0001 triggers the
below−mentioned changes in
C0412 and C0410 if C0412 has
not been configured freely
before.
If C0412 has been configured
freely before (check: C0005 =
255), C0001 does not affect
C0412 and C0410. You must
link the signals manually.
Free configuration in C0412 or
C0410 does not affect C0001!
Control can be carried out via
terminals as well as via
PC/keypad.
  296
0
Setpoint selection via AIN1 (X3/8 or
X3/1U, X3/1I)
C0412/1 and C0412/2 are
linked to analog input 1
(C0412/1 = 1, C0412/2 = 1).
C0410 remains unchanged.
1
Setpoint selection via keypad or
parameter channel of an AIF bus
module
In C0412, the link to the analog
input is disconnected
(C0412/1 = 255,
C0412/2 = 255).
Setpoint selection via C0044 or
C0046.
C0410 remains unchanged.
2
Setpoint selection via AIN1 (X3/8 or
X3/1U, X3/1I)
C0412/1 and C0412/2 are
linked to analog input 1
(C0412/1 = 1, C0412/2 = 1).
C0410 remains unchanged.
3
Setpoint selection via process data
channel of an AIF bus module
C0001 = 3 must be set for the
setpoint selection via process
data channel of an AIF bus
module (types 210x, 211x,
213x, 217x)! Otherwise the
process data will not be
evaluated.
C0412/1 and C0412/2 are
linked to analog input words
AIF−IN.W1 and AIF−IN.W2
(C0412/1 = 10, C0412/2 = 11).
C0410/1 ... C0410/16 are
linked to the individual bits of
the AIF control word (AIF−CTRL)
(C0410/1 = 10 ... C0410/16 = 2
5).
Note!
ƒ
With C0001 = 0, 1 or 2 the operation can start after the controller has been
released.
ƒ
C0001 = 3 must be set to select a setpoint via a process data channel of an
AIF bus module! Otherwise the process data will not be evaluated.
ƒ
With C0001 = 3 quick stop (QSP) is set after mains switch−on !
–PC: Deactivate QSP using the control word C0135, bit 3 = 0.
–Keypad: Set C0469 = −2−. Press .
Function library
Configuration of analog and digital setpoints and actual values
Analog setpoints via terminal
10
298
EDS82EV903  EN  3.0
10.7.2
Analog setpoints via terminal 
Description
Selection and adjustment of analog signals via terminal as setpoint or actual value.
Codes for parameter setting
Code
Possible settings
IMPORTANT
No.
Name
Lenze
Selection
C0034
*
uSEr
Range of
setpoint
selection
Standard I/O
(X3/8)
Observe switch position of the
function module!
  298
0
0
Unipolar voltage 0 ... 5 V / 0 ... 10 V
Current 0 ... 20 mA
1
Current 4 ... 20 mA
Reversal of rotation direction only
possible with a digital signal.
2
Bipolar voltage −10 V ... +10 V
Minimum output frequency
(C0010) not effective
Individually adjust offset and
gain
3
Current 4 ... 20 mA open−circuit
monitored
TRIP Sd5 if I < 4 mA
Reversal of rotation direction only
possible with a digital signal.
C0034
*
(A)
uSEr
Range of
setpoint
selection
Application I/O
Observe jumper position of the
function module!
  298
1
X3/1U, X3/1I
0
0
Unipolar voltage 0 ... 5 V / 0 ... 10 V
2
X3/2U, X3/2I
1
Bipolar voltage −10 V ... +10 V
Minimum output frequency
(C0010) not effective
2
Current 0 ... 20 mA
3
Current 4 ... 20 mA
Reversal of rotation direction only
possible with a digital signal.
4
Current 4 ... 20 mA open−circuit
monitored
Reversal of rotation direction only
possible with a digital signal.
TRIP Sd5 at I < 4 mA
C0026
*
Offset for
analog input 1
(AIN1–OFFSET)
0.0
−200.0
{0.1 %}
200.0
Setting for X3/8 or X3/1U,
X3/1I
The upper limit of the setpoint
range from C0034 corresponds
to 100 %
C0026 and C0413/1 are equal
  298
C0027
*
Gain for analog
input 1
(AIN1−GAIN)
100.0
−1500.0
{0.1 %}
1500.0
Setting for X3/8 or X3/1U,
X3/1I
100.0 % = gain 1
Inverted setpoint selection
through negative gain and
negative offset
C0027 and C0414/1 are equal
  298
Function library
Configuration of analog and digital setpoints and actual values
Analog setpoints via terminal
10
299
EDS82EV903   EN   3.0
IMPORTANT
Possible settings
Code
Selection
Lenze
Name
No.
C0413
*
Offset − analog
inputs
−200.0
{0.1 %}
200.0 The upper limit of the setpoint
range from C0034 corresponds to
100 %
  298
1
AIN1−OFFSET
0.0
Setting for X3/8 or X3/1U, X3/1I
C0413/1 and C0026 are the same
2
AIN2−OFFSET
0.0
Setting for X3/2U, X3/2I
(only application I/O)
C0414
*
Gain − analog
inputs
−1500.0
{0.1 %}
1500.0
100.0 % = gain 1
Inverted setpoint selection
through negative gain and
negative offset
1
AIN1−GAIN
100.0
Setting for X3/8 or X3/1U, X3/1I
C0414/1 and C0027 are the same
2
AIN2−GAIN
100.0
Setting for X3/2U, X3/2I
(only application I/O)
C0430
*
(A)
Automatic
adjustment of
analog inputs
0
0
Inactive
The gain and offset are calculated
by entering two points of the
setpoint characteristic. Enter
points that are as far away from
each other as possible for high
accuracy of calculation:
1. In C0430, select the input the
gain and the offset are to be
calculated for
2. In C0431, enter the X value
(setpoint) and the Y value
(output frequency) of point 1
3. In C0432, enter the X value
(setpoint) and the Y value
(output frequency) of point 2
4. Calculated values are
automatically entered in C0413
(offset) and C0414 (gain)
  298
1
Entry of points for X3/1U, X3/1I
2
Entry of points for X3/2U, X3/2I
C0431
*
(A)
Coordinates of
point 1
−100.0
{0.1 %}
100.0
1
X (P1)
−100.0
Analog setpoint of P1
100 % = max. input value (5 V, 10 V or 20 mA)
2
Y (P1)
−100.0
Output frequency of P1
100 % = C0011
C0432
*
(A)
Coordinates of
point 2
−100.0
{0.1 %}
100.0
1
X (P2)
100.0
Analog setpoint of P2
100 % = max. input value (5 V, 10 V or 20 mA)
2
Y (P2)
100.0
Output frequency of P2
100 % = C0011
Function library
Configuration of analog and digital setpoints and actual values
Analog setpoints via terminal
10
300
EDS82EV903  EN  3.0
Adjustment
1. In C0412, link the desired setpoint or actual value to one of the analog inputs
(C0412/x = 1 or 4).
Note!
Besides the free configuration in C0412, a fixed configuration can be selected
in C0005.
2. Select the setpoint range in C0034.
3. Set the switch/jumper position on the function module to the same range!
Otherwise the setpoint signal will not be interpreted correctly.
–Independent of the set gain, the setpoint signal will only be evaluated within the
setpoint range (C0034) that has been set.
–The minimum output frequency (C0010) corresponds to 0 % setpoint signal.
–If offset0% and/or if inverted setpoint selection has been selected, the value
may fall below the value set in C0010.
4. Set gain if required (C0414)
–The gain always acts both on the setpoint signal and the offset.
–100 % corresponds to a gain factor = 1.
–Calculate the gain by means of two points on the setpoint characteristic. Observe
the signs of the coordinates:
Gain[%] 
f(P
2
)f(P
1
)
U(P
2
)U(P
1
)
100%
5. Set offset if required (C0413).
–An offset will shift the characteristic.
–A dead band can be set up by means of the offset and C0239 (lower frequency
limitation) if required.
–Calculate the offset by means of the calculated gain and a point on the setpoint
characteristic. Observe the signs of the coordinates:
Offset(P
2
)[%] 
f(P
2
)[%]
Gain[%]
100%U(P
2
)[%]
Note!
ƒ
C0026, C0027, C0413 and C0414 are equal in all parameter sets.
ƒ
During operation with application I/O, automatic adjustment of the
setpoint inputs is possible via C0430, C0431 and C0432:
–Select the setpoint input in C0430.
–Enter the coordinates of two points on the setpoint characteristic in C0431
and C0432.
–Calculated values are automatically entered in C0413 (offset) and C0414
(gain)