Function library
Configuration of analog and digital setpoints and actual values
Setpoints via keypad
10
311
EDS82EV903   EN   3.0
10.7.6
Setpoints via keypad 
Description
The setpoint can be selected via the keypad.
The keypad setpoint is added to the main setpoint.
Note!
ƒ
Setpoints selected by means of the keypad are stored when the controller is
disconnected from the mains or operation is interrupted.
ƒ
The drive can start again after controller enable!
Codes for parameter setting
Code
Possible settings
IMPORTANT
No.
Name
Lenze
Selection
C0044
*
Setpoint 2
(NSET1-N2)
−650.00
{0.02
Hz}
650.00 The set value will be lost during
mains switching!
Selection if C0412/2 =
FIXED−FREE (not assigned)
Display if C0412/2 is linked to
a signal source
  311
C0046
*
Setpoint 1
(NSET1-N1)
−650.00
{0.02
Hz}
650.00
The set value will be lost during
mains switching!
Selection if C0412/1 =
FIXED−FREE (not assigned)
Display if C0412/1 is linked to
a signal source
  311
C0140
*
Additive
frequency
setpoint
(NSET1−NADD)
0.00
−650.00
{0.02
Hz}
650.00
Selection via  function of
the keypad or parameter
channel
Acts additively on the main
setpoint
Value will be stored when
switching the mains or
removing the keypad
C0140 is only transferred
during parameter set transfer
with GDC (not with keypad)
  311
Select setpoint with E82ZBC keypad 
You can simply select the setpoint by using the  function:
1. Use  or  to select the  function.
2. Set setpoint with  or .
–If the controller is enabled, the changed setpoint has a direct effect on the drive.
–If the controller is inhibited, the setpoint is saved. After the controller has been
enabled, the drive accelerates to the setpoint set last with the adjusted
acceleration or deceleration time.
Note!
 writes the setpoint into C0140. You can directly select the setpoint in
C0140.
Some pdf image extract - Select, copy, paste PDF images in C#.net, ASP.NET, MVC, Ajax, WinForms, WPF
Support PDF Image Extraction from a Page, a Region on a Page, and PDF Document
extract images from pdf c#; extract pictures from pdf
Some pdf image extract - VB.NET PDF Image Extract Library: Select, copy, paste PDF images in vb.net, ASP.NET, MVC, Ajax, WinForms, WPF
Support PDF Image Extraction from a Page, a Region on a Page, and PDF Document
pdf image extractor c#; extract vector image from pdf
Function library
Configuration of analog and digital setpoints and actual values
Setpoints via a bus system
10
312
EDS82EV903  EN  3.0
Select setpoint with XT EMZ9371BC keypad 
You select the setpoint directly in C0140:
1. Select C0140 in the menus.
2. Set setpoint with  or .
Drive behaviour when selecting setpoints via keypad
ƒ
If the controller is enabled, the changed setpoint has a direct effect on the drive.
ƒ
If the controller is inhibited, the setpoint is saved. After the controller has been
enabled, the drive accelerates to the value saved last with the adjusted acceleration
or deceleration time.
Setting tips
ƒ
The setpoint via keypad has an effect on setpoint 1 (NSET1−N1) and setpoint 2
(NSET1−N2). If you want to select different setpoints via keypad:
–Separate the linkage of NSET1−N1 and NSET1−N2 with analog input signals
(C0412/1 = 0 and C0412/2 = 0).
–Now you can set NSET1−N1 in C0046 and NSET−N2 in C0044.
ƒ
Set C0140 = 0 if the setpoint is not selected via C0140, otherwise the drive may start
immediately when the controller is enabled.
10.7.7
Setpoints via a bus system 
Setpoints or actual values can be preselected for FIF by means of a bus function module or
AIF by means of a bus module.
A detailed description can be found in the documentation for the modules.
VB.NET PDF Password Library: add, remove, edit PDF file password
RasterEdge XDoc.PDF SDK provides some PDF security settings about password to help protect your PDF document in VB.NET project.
pdf image extractor; extract photos pdf
C# HTML5 PDF Viewer SDK to view, annotate, create and convert PDF
Here explains some usages about HTML5 PDF Viewer annotation functionalities. C#.NET: Create PDF Online in ASP.NET. C#.NET: Edit PDF Image in ASP.NET.
extract images from pdf files without using copy and paste; extract image from pdf file
Function library
Configuration of analog and digital setpoints and actual values
Setpoint changeover (hand/remote changeover)
10
313
EDS82EV903   EN   3.0
10.7.8
Setpoint changeover (hand/remote changeover) 
Description
Changeover between the setpoints NSET1−N1 and NSET1−N2.
ƒ
With manual/remote changeover it is possible to e.g. change from remote operation
to manual operation in the event of setting or service at the drive.
–For manual operation the setpoint source for remote operation must not be
changed.
–In manual operation the setpoint is selected via potentiometer, motor
potentiometer or keypad/PC.
ƒ
Examples for setpoint changeovers:
–Bus operation  Keypad or PC
–Bus operation  analog setpoint via analog input
–Keypad or PC   analog setpoint via analog input
–Function Motor potentiometer"   analog setpoint via analog input
–Analog setpoint via analog input   setpoint via frequency input
–Analog input 1   analog input 2 (application I/O only)
Note!
The safety functions controller inhibit and quick stop (QSP) set in remote
operation will be reset when manual operation is being activated. Check
whether the master system reactivates these functions after a changeover.
Activation
Analog setpoint changeover via analog input
ƒ
The setpoint source for remote operation must be linked with NSET1−N1 under
C0412/1.
ƒ
The setpoint source for manual operation must be linked with NSET1−N2 under
C0412/2.
ƒ
A digital input signal must be linked with the manual/remote changeover
(DCTRL1−H/Re) under C0410/17.
ƒ
HIGH active inputs:
–Manual operation active if signal source for DCTRL1−H/Re = HIGH
Activation of "bus operation  keypad or PC"
1. Internally invert a digital input (X3/E5 or X3/E6) not used in the Lenze setting under
C0411.
2. Assign this input C0410/17 (DCTRL1−H/Re) to activate manual operation.
3. If the inversion of the digital input reset (C0411 = 0), remote operation will be active
again.
C# PDF Password Library: add, remove, edit PDF file password in C#
Able to change password on adobe PDF document in C#.NET. To help protect your PDF document in C# project, XDoc.PDF provides some PDF security settings.
extract photos from pdf; extract image from pdf c#
C# Create PDF Library SDK to convert PDF from other file formats
Load PDF from existing documents and image in SQL server. creating toolkit, if you need to add some text and draw some graphics on created PDF document file
extract images from pdf online; extract images from pdf acrobat
Function library
Configuration of analog and digital setpoints and actual values
Setpoint changeover (hand/remote changeover)
10
314
EDS82EV903  EN  3.0
Example
ƒ
Invert X3/E6 with C0411 = 32.
ƒ
Assign X3/E6 to the subcode C0410/17 with C0410/17 = 6.
ƒ
The setpoint can be selected under C0044 using the keypad or PC.
ƒ
If C0411 = 0 is set, the remote operation is active again.
Influence on other setpoints
ƒ
JOG frequency are not effected by a manual/remote changeover.
ƒ
Function   of the keypad E82ZBC simultaneously acts on NSET1−N1 and NSET−N2.
–Use C0046 (NSET1−N1) and C0044 (NSET1−N2) for separated setpoint selection.
Note!
The keypad key   is not active in manual operation!
VB.NET PDF Annotate Library: Draw, edit PDF annotation, markups in
mark the source PDF file by adding some comments, notes on, which integrates advanced VB.NET PDF editing functions and VB.NET image annotating features
how to extract images from pdf files; extract image from pdf acrobat
VB.NET Image: How to Process & Edit Image Using VB.NET Image
Besides, if you want to apply some popular image effects to target image file, like image sharpening, image vintage effect creating, image color adjusting and
extract image from pdf c#; extract photos from pdf
Function library
Automatic detection of motor data
10
315
EDS82EV903   EN   3.0
10.8
Automatic detection of motor data 
Description
This function serves to determine the required motor data and influences of the motor
cable.
Must be carried out prior to initial commissioning of the vector control (C0014 = 4) or the
sensorless torque control (C0014 = 5). Otherwise commissioning will not be possible.
Note!
The motor data identification also influences the smooth running
performance in the "V/f characteristic control with constant V
min
boost"
operating mode (C0014 = 2 or 3). If motor data identification is carried out in
this operating mode, the smooth running performance can be optimised for
lower speeds.
Codes for parameter setting
Code
Possible settings
IMPORTANT
No.
Name
Lenze
Selection
C0084 Motor stator
resistance
0.000
0.000
{0.001
}
64.000
  315
0.0
0.0
{0.1
m}
6500.0
Only 8200 vector 15 ... 90 kW
C0087
Rated motor
speed
300
{1 rpm}
16000
Device−dependent
  315
C0088
Rated motor
current
0.0
0.1 (A)
650.0
Device−dependent
0.0 ... 2.0 x rated output current of
the controller
  315
C0089
Rated motor
frequency
50
10
{1 Hz}
960
  315
C0090
Rated motor
voltage
50
{1 V}
500
230 V for 230 V controllers,
400 V for 400 V controllers
  315
C0091
Motor cos ϕ
0.40
{0.1}
1.0
Device−dependent
  315
C0092
Motor stator
inductance
0.0
0.000
{0.1 mH}
Device−dependent
  315
0.00
0.00
{0.01
mH}
Device−dependent
Only 8200 vector 15 ... 90 kW
C0148
*
Identifying
motor data
0
0
Ready
Only when the motor is cold!
1. Inhibit controller, wait until
drive is at standstill
2. Enter the correct values from
the motor nameplate in C0087,
C0088, C0089, C0090, C0091
3. Set C0148 = 1, confirm with
4. Enable controller:
The identification
–starts,  goes out
–the motor "whistles" faintly
but it does not rotate!
–takes approx. 30 s
–is completed when  is lit
again
5. Inhibit controller
  315
1
Start identification
V/f rated frequency (C0015), slip
compensation (C0021) and motor
stator inductance (C0092) are
calculated and saved
The motor stator resistance (C0084)
= total resistance of the motor cable
and motor is measured and saved
C# PDF: C# Code to Process PDF Document Page Using C#.NET PDF
and manage those PDF files, especially when they are processing some PDF document files C# PDF: Add Image to PDF Page Using C#.NET, C# PDF: Extract Page(s
extract images from pdf files; extract photos pdf
C# Create PDF from images Library to convert Jpeg, png images to
It enables you to build a PDF file with one or Various image forms are supported which include Png, Jpeg, Bmp Some C# programming demos are illustrated below.
extract image from pdf acrobat; extract images from pdf c#
Function library
Automatic detection of motor data
10
316
EDS82EV903  EN  3.0
C0092 − device−dependent upper selection limit
8200 vector type
Max. adjustable motor stator inductance
[mH]
E82xV251K2C
2000.0
E82xV371K2C
2000.0
E82xV551K2C
1620.0
E82xV751K2C
1330.0
E82xV152K2C
760.0
E82xV222K2C
560.0
E82xV302K2C
440.0
E82xV402K2C
320.0
E82xV552K2C
230.0
E82xV752K2C
180.0
E82xV551K4C
2000.0
E82xV751K4C
2000.0
E82xV152K4C
2000.0
E82xV222K4C
1690.0
E82xV302K4C
1240.0
E82xV402K4C
970.0
E82xV552K4C
710.0
E82xV752K4C
560.0
E82xV113K4C
390.0
E82xV153K4B
290.0
E82xV223K4B
197.0
E82xV303K4B
150.0
E82xV453K4B
103.0
E82xV553K4B
84.6
E82xV753K4B
62.0
E82xV903K4B
51.6
How to C#: Basic SDK Concept of XImage.Raster
VB.NET How-to, VB.NET PDF, VB.NET Word classes to convert, process, edit, and annotate image from local can load convert and save define some specified options
extract image from pdf using; extract image from pdf file
C#: How to Add HTML5 Document Viewer Control to Your Web Page
Note: some versions of Visual Studio use addCommand(new CommandAnnotation("image", new AnnoStyle _userCmdDemoPdf = new UserCommand("pdf"); _userCmdDemoPdf.addCSS
how to extract text from pdf image file; extract image from pdf
Function library
Automatic detection of motor data
10
317
EDS82EV903   EN   3.0
Activation
Note!
Ensure that the motor is cold when the identification is started!
ƒ
During identification current flow via the controller outputs U, V.
ƒ
The load machine can remain connected. Holding brakes can remain in their
braking position.
ƒ
With idling motors a small angle shift can occur at the motor shaft.
1. Inhibit the controller. And wait until the drive is in standstill.
2. Enter C0087, C0088, C0089, C0090 and C0091 of your motor (see nameplate):
–It is absolutely necessary to enter correct data since important parameters such as
slip compensation, idle running current and I 
2
t monitoring are based on these
values.
–Enter rated motor current (C0088) and rated motor voltage (C0090) according to
the connection type (star or delta).
3. Select C0148 = 1, confirm with 
.
4. Enable controller. Identification starts (green controller LED blinking quickly).
–The motor stator resistance is measured and stored under C0084.
–The motor stator inductance is calculated from the data entered and stored under
C0092.
–The V/f rated frequency is calculated and stored under C0015.
–The slip is calculated and stored under C0021.
–The identification takes approx. 30 s.
–Identification is completed when the green controller LED comes on (keypad, GDC:
 is active).
5. Inhibit the controller.
Note!
Only the parameter set activated via the digital input signals will be identified.
If you want to detect motor data for any other parameter set, this parameter
set must be activated via digital input signals before it can be identified.
Motor data correction during operation
ƒ
The motor data are corrected automatically during operation (max. ±25 %) to
compensate for temperature fluctuations.
–The values under C0084 and C0092 calculated by C0148 become active after
mains switching.
ƒ
The values under C0084 and C0092 can be manually entered or corrected.
Function library
Process controller
Set control loop properties
10
318
EDS82EV903  EN  3.0
10.9
Process controller
10.9.1
Set control loop properties
Description
The process controller serves to put up control loops for controlling e.g. speed, pressure,
temperature, flow rate, humidity, level or dancer position.
The process controller requires a setpoint and an actual value (e.g. from a sensor). If
setpoint and actual value are selected as analog values (potentiometer, PLC), the controller
must be equipped with an application I/O to build up a control circuit.
Codes for parameter setting
Code
Possible settings
IMPORTANT
No.
Name
Lenze
Selection
C0070 Process
controller gain
1.00
0.00
= P component
inactive
{0.01}
300.00
  318
C0071
Process
controller reset
time
100
10
{1}
9999
= I component
inactive
  318
C0072
Differential
component −
process
controller
0.0
0.0
= D component
inactive
{0.1}
5.0
  318
C0074
Influence of
the process
controller
0.0
0.0
{0.1 %}
100.0
  318
C0238
Frequency
precontrol
2
0
No feedforward control (only process
controller)
Process controller has full
influence
  318
  322
1
Feedforward control (overall setpoint +
process controller)
Process controller has restricted
influence
2
No feedforward control (overall
setpoint only)
Process controller does not have
any influence (inactive)
Overall setpoint (PCTRL1−SET3) =
main setpoint + additional
setpoint
Adjustment
1. Roughly adjust the control features in the following tables based on the guide
values.
2. Fine adjustment:
–Adjust C0070, C0071 and C0072 so that the target value is reached quickly and
with minimum overshoots in case of setpoint and actual value changes.
Scaling C0071
Value in C0071
Resulting reset time  T
N
10 ... 5000
10 ms ... 5000 ms
5000 ... 6000
5 s ... 10 s
6000 ... 7000
10 s ... 100 s
7000 ... 8000
100 s ... 1000 s
8000 ... 9998
1000 s ... 9998 s
Function library
Process controller
Set control loop properties
10
319
EDS82EV903   EN   3.0
Pressure control and flow control
ƒ
The differential component K
D
(C0072) is generally not required for pressure and
flow control.
ƒ
Set the influence (C0074) to 100 %.
ƒ
Deactivate the frequency feedforward control (C0238 = 0).
Code
Setting for
Gases
Fluids
C0070 (K
P
)
0.1
0.02 ... 0.1
C0071 (T
N
)
5000 (T
N
= 5s)
200 ... 1000 (T
N
= 0.2s ... 1s)
C0072 (K
D
)
0
0
Speed control
Code
Setting
C0070 (K
P
)
5
C0071 (T
N
)
100 (T
N
= 0.1s)
C0072 (K
D
)
0
Set the influence of the process controller
ƒ
Activate frequency feedforward control (C0238=1). Now the process controller has
only limited influence:
–The control factor determines the influence of the process controller (C0074).
–Control factor = C0050 (output frequency) − C0051 (actual process controller value)
ƒ
C0074 refers to the maximum output frequency C0011.
ƒ
C0074 influences the stability of the control loop:
–Set C0074 as low as possible.
–If C0074 is set too high, the control loop can become unstable.
Calculate the influence of the process controller
Calculate C0074
Example
C0074[%]
C0050C0051
C0011
100%
C0011=50Hz, C0050=53Hz, C0051=50Hz:
C0074[%]
53Hz50Hz
50Hz
100%6%
Set the influence so that the process controller output covers the calculated value in every
working point.
Set C0074=10% as guide value for the example (C0074=6%). The guide value contains
tolerances which must always be observed.
Function library
Process controller
Set control loop properties
10
320
EDS82EV903  EN  3.0
Example of additive influence
The effective direction of the process controller output to the main setpoint is additive.
Settings
ƒ
C0051=positive actual value
ƒ
C0181=select positive setpoint
ƒ
C0238=1 (with frequency feedforward control)
ƒ
Potentiometer terminals of the dancer
–End (E)=+10V
–Start (A)=GND
Function
1. The dancer deflects to the bottom. The dancer control (V
T
) decreases.
2. V2 increases.
M
3~
8200
3
E
A
U
T
+10 V
0 V ... 10 V
~ V1
V1
V2
S
8200vec534
Fig. 10−13
Example: Dancer control with adding influence of the process controller