load pdf in webbrowser control c# : Extract photos pdf application Library tool html .net windows online E82EV__8200%20vector%200.25-90kW__v3-0__EN33-part1607

Function library
Free interconnection of analog signals  
Free configuration of analog input signals
10
331
EDS82EV903   EN   3.0
Examples
ƒ
C0412/1 = 2   The frequency input is the signal source for setpoint 1 (NSET1−N1)
ƒ
C0412/5 = 23   CAN−IN1/word 4 is the signal source for the actual process
controller value (PCTRL−ACT)
Note!
The process data input words CAN−IN1.W1, CAN−IN1.W2, CAN−IN2.W1 and
CAN−IN2.W2 can be defined as analog word or as digital word (16 bit). If you
link them with internal analog signals (C0412/x = 20, 21 or 30, 31), they must
be defined as analog input words. Otherwise the controller cannot interpret
the signal correctly.
Extract photos pdf - Select, copy, paste PDF images in C#.net, ASP.NET, MVC, Ajax, WinForms, WPF
Support PDF Image Extraction from a Page, a Region on a Page, and PDF Document
some pdf image extractor; pdf image extractor
Extract photos pdf - VB.NET PDF Image Extract Library: Select, copy, paste PDF images in vb.net, ASP.NET, MVC, Ajax, WinForms, WPF
Support PDF Image Extraction from a Page, a Region on a Page, and PDF Document
extract pictures from pdf; extract images pdf
Function library
Free interconnection of analog signals  
Free configuration of analog outputs
10
332
EDS82EV903  EN  3.0
10.11.2
Free configuration of analog outputs 
Description
ƒ
The analog outputs (X3/62, X3/63) and the frequency output (X3/A4) can be freely
assigned to internal analog process signals or monitoring signals. The controller
outputs a voltage proportional to the internal signal at the analog outputs.
ƒ
Currents can also be output when using the application I/O.
–Range: 0 ... 20 mA, as of software version 1.1 also 4 ... 20 mA
–Setting via jumper at module and C0424
ƒ
A signal source can be assigned to several targets.
Note!
Use C0111 to permanently assign the analog output X3/62 to some internal
signal sources. C0419/1 is automatically adapted.
Codes for parameter setting
Code
Possible settings
IMPORTANT
No.
Name
Lenze
Selection
C0419
Free
configuration
of analog
outputs
Output of analog signals to terminal
  332
1
X3/62
(AOUT1−IN)
0
Output frequency
(MCTRL1−NOUT+SLIP)
A selection in C0111 is copied into
C0419/1. Change of C0419/1 sets
C0111 = 255!
2
(A)
X3/63
(AOUT2−IN)
2
Apparent motor current
(MCTRL1−IMOT)
3
(A)
X3/A4
(DFOUT1−IN)
3
DC−bus voltage (MCTRL1−DCVOLT)
Frequency output: 50 Hz ... 10 kHz
VB Imaging - VB ISSN Barcode Generating
help VB.NET developers draw and add standard ISSN barcode on photos, images and BMP image formats, our users can even create ISSN barcode on PDF, TIFF, Excel
extract image from pdf in; extract text from image pdf file
C# Image: How to Add Antique & Vintage Effect to Image, Photo
Among those antique things, old photos, which can be seen everywhere, can are dedicated to provide powerful & profession imaging controls, PDF document, tiff
how to extract images from pdf files; how to extract images from pdf
Function library
Free interconnection of analog signals  
Free configuration of analog outputs
10
333
EDS82EV903   EN   3.0
IMPORTANT
Possible settings
Code
Selection
Lenze
Name
No.
C0419
(Cont.)
Possible analog signals for C0419
  332
0
Output frequency
(MCTRL1−NOUT+SLIP)
6 V/12 mA/5.85 kHz  C0011
1
Device utilisation (MCTRL1−MOUT) at
V/f characteristic control (C0014 = 2 or
3)
3 V/6 mA/2.925 kHz  rated active
inverter current (active
current/C0091)
Actual motor torque (MCTRL1−MACT)
with vector control (C0014 = 4) or
sensorless torque control (C0014 = 5)
3 V/6 mA/2.925 kHz  rated
motor torque
2
Apparent motor current
(MCTRL1−IMOT)
3 V/6 mA/2.925 kHz  rated
inverter current
3
DC−bus voltage (MCTRL1−DCVOLT)
6 V/12 mA/5.85 kHz  DC 1000 V
(400 V mains)
6 V/12 mA/5.85 kHz  DC 380 V
(230 V mains)
4
Motor power (MCTRL1−PMOT)
3 V/6 mA/2.925 kHz  rated
motor power
5
Motor voltage (MCTRL1−VOLT)
4.8 V/9.6 mA/4.68 kHz rated
motor voltage
6
1/output frequency (1/C0050)
(MCTRL1−1/NOUT)
2 V/4 mA/1.95 kHz  0.5  C0011
7
Output frequency within adjusted
limits (DCTRL1−C0010...C0011)
0 V/0 mA/4 mA/0 kHz  f = f
min
(C0010)
6 V/12 mA/5.85 kHz  f = f
max
(C0011)
8
Operation with process controller
(C0238 = 0, 1):
Actual process controller value
(PCTRL1−ACT)
6 V/12 mA/5.85 kHz  C0011
Operation without process controller
(C0238 = 2):
Output frequency without slip
(MCTRL1−NOUT)
VB.NET TWAIN: Scanning Multiple Pages into PDF & TIFF File Using
enterprises or institutions, there are often a large number of photos or documents be combined into one convenient multi-page document file, like PDF and TIFF.
extract images from pdf online; extract images from pdf files without using copy and paste
VB.NET Image: Program for Creating Thumbnail from Documents and
developers to create thumbnail from multiple document and image formats, such as PDF, TIFF, GIF As we all know, photos and graphics take up a lot of server space
extract vector image from pdf; extract jpg from pdf
Function library
Free interconnection of analog signals  
Free configuration of analog outputs
10
334
EDS82EV903  EN  3.0
IMPORTANT
Possible settings
Code
Selection
Lenze
Name
No.
C0419
(Cont.)
Possible analog signals for C0419
Selection 9 ... 25 corresponds to
the digital functions of the relay
output K1 or the digital switching
output K1 (C0008) or the digital
output A1 (C0117):
LOW = 0 V/0 mA/4 mA/ 0 kHz
HIGH = 10 V/20 mA/10 kHz
  332
9
Ready for operation (DCTRL1−RDY)
10
TRIP error message (DCTRL1−TRIP)
11
Motor is running (DCTRL1−RUN)
12
Motor is running / CW rotation
(DCTRL1−RUN−CW)
13
Motor is running / CCW rotation
(DCTRL1−RUN−CCW)
14
Output frequency = 0
(DCTRL1−NOUT=0)
15
Frequency setpoint reached
(DCTRL1−RFG1=NOUT)
16
Values have fallen below frequency
threshold Q
min
(f < C0017)
(PCTRL1−QMIN)
LOW active
17
I
max
limit reached (MCTRL1−IMAX)
C0014 = −5−: Torque setpoint reached
18
Overtemperature (
max
− 5 °C)
(DCTRL1-OH-WARN)
19
TRIP or Q
min
or pulse inhibit (IMP)
active (DCTRL1−TRIP−QMIN−IMP)
20
PTC warning (DCTRL1−PTC−WARN)
21
Apparent motor current < current
threshold (DCTRL1−IMOT<ILIM)
V−belt monitoring
Apparent motor current = C0054
Current threshold = C0156
Frequency threshold Q
min
= C0017
22
Apparent motor current < current
threshold and output frequency >
Frequency threshold Q
min
(DCTRL1−(IMOT<ILIM)−QMIN)
23
Apparent motor current < current
threshold and ramp function generator
1: input = output
(DCTRL1−(IMOT<ILIM)−RFG−I=0)
24
Motor phase failure warning
(DCTRL1−LP1−WARN)
25
Min. output frequency reached
(f  C0010) (PCTRL1−NMIN)
LOW active
VB.NET Image: Image and Doc Windows, Web & Mobile Viewers of
Users can directly browse and process images and photos on your computer. & image files of this mobile viewer are JPEG, PNG, BMP, GIF, TIFF, PDF, Word and DICOM
extract image from pdf online; extract pdf images
VB.NET Image: Barcode Reader SDK, Read Intelligent Mail from Image
and recognize Intelligent Mail barcode from scanned (or not) photos and documents in How to combine PDF Document Processing DLL with Barcode Reading control to
how to extract images from pdf file; extract images pdf acrobat
Function library
Free interconnection of analog signals  
Free configuration of analog outputs
10
335
EDS82EV903   EN   3.0
IMPORTANT
Possible settings
Code
Selection
Lenze
Name
No.
C0419
(Cont.)
Possible analog signals for C0419
  332
26
Output frequency normalised without
slip (MCTRL1−NOUT−NORM)
27
Output frequency without slip
(MCTRL1−NOUT)
6 V/12 mA/5.85 kHz  C0011
28
Actual process controller value
(PCTRL1−ACT)
29
Process controller setpoint
(PCTRL1−SET1)
6 V/12 mA/5.85 kHz  C0011
30
Process controller output without
feedforward control (PCTRL1−OUT)
31
Ramp function generator input
(NSET1−RFG1−IN)
32
Ramp function generator output
(NSET1−NOUT)
33 (A)
PID controller output
(PCTRL1−PID−OUT)
34 (A)
Process controller output
(PCTRL1−NOUT)
35
Input signal at X3/8 (standard I/O) or
X3/1U or X3/1I (application I/O),
assessed with gain (C0414/1 or C0027)
and offset (C0413/1 or C0026)
(AIN1−OUT)
6 V/12 mA/5.85 kHz  maximum
value of analog input signal (5 V,
10 V, 20 mA, 10 kHz)
Condition: The gain of the analog
input or frequency input is set to:
C0414/x, C0426 = 100 %
36
Input signal at frequency input X3/E1
and X3/E2, assessed with gain (C0426)
and offset (C0427) (DFIN1−OUT)
37
Motor potentiometer
output(MPOT1−OUT)
38 (A)
Input signal at X3/2U or X3/2I,
assessed with gain (C0414/2) and
offset (C0413/2) (AIN2−OUT)
40
AIF input word 1 (AIF−IN.W1)
Setpoints to the controller from
communication module on AIF
10 V/20 mA/10 kHz  1000
41
AIF input word 2 (AIF−IN.W2)
50
CAN−IN1.W1 or FIF−IN.W1
Setpoints to controller from
function module on FIF
10 V/20 mA/10 kHz  1000
51
CAN−IN1.W2 or FIF−IN.W2
52
CAN−IN1.W3 or FIF−IN.W3
53
CAN−IN1.W4 or FIF−IN.W4
60
CAN−IN2.W1
61
CAN−IN2.W2
62
CAN−IN2.W3
63
CAN−IN2.W4
255
Not assigned (FIXED−FREE)
C0108
*
Gain for analog
output X3/62
(AOUT1−GAIN)
128
0
{1}
255
Standard I/O: C0108 and C0420
are equal
Application I/O: C0108 and
C0420/1 are equal
  332
C0109
*
Offset for
analog output
X3/62 (AOUT1−
OFFSET)
0.00
−10.00
{0.01 V}
10.00
Standard I/O: C0109 and C0422
are equal
Application I/O: C0109 and
C0422/1 are equal
  332
C0420
*
Gain − analog
output X3/62
(AOUT1−GAIN)
Standard I/O
128
0
{1}
255
128  Gain 1
C0420 and C0108 are equal
  332
VB.NET Image: VB Code to Read Linear Identcode Within RasterEdge .
Support reading and scanning Identcode from scanned documents and photos in VB code; and recognize multiple Identcode barcodes form single or multiple PDF page(s
how to extract images from pdf in acrobat; extract images from pdf files without using copy and paste
VB.NET Image: VB Code to Download and Save Image from Web URL
view and store thousands of their favorite images and photos to Windows We are dedicated to provide powerful & profession imaging controls, PDF document, image
extract pdf pages to jpg; pdf image extractor online
Function library
Free interconnection of analog signals  
Free configuration of analog outputs
10
336
EDS82EV903  EN  3.0
IMPORTANT
Possible settings
Code
Selection
Lenze
Name
No.
C0422
*
Offset for
analog output
X3/62 (AOUT1−
OFFSET)
Standard I/O
0.00
−10.00
{0.01 V}
10.00 C0422 and C0109 are equal
  332
C0420
*
(A)
Gain − analog
outputs
Application I/O
128  Gain 1
  332
1
X3/62
(AOUT1−GAIN)
128
0
{1}
255
C0420/1 and C0108 are equal
2
X3/63
(AOUT2−GAIN)
C0422
*
(A)
Offset of
analog outputs
Application I/O
−10.00
{0.01 V}
10.00
  332
1
X3/62 (AOUT1−
OFFSET)
0.00
C0422/1 and C0109 are the same
2
X3/63 (AOUT2−
OFFSET)
C0424
*
(A)
Output signal
range − analog
outputs
Application I/O
0
1
0 ... 10 V / 0 ... 20 mA
4 ... 20 mA
Observe jumper position of the
function module!
(from version: application I/O
E82ZAFA ... Vx11)
  332
1
X3/62 (AOUT1)
0
2
X3/63 (AOUT2)
0
Signal linkage
The analog outputs are linked with internal analog signals by entering the selection figure
of the internal signal into the corresponding subcode of C0419. C0419 can be different for
the parameter sets.
Examples
ƒ
C0419/1   51: The process data word CAN−IN2/word 2 is the signal source for
X3/62.
ƒ
C0419/2   5: The monitoring signal Motor voltage" is the signal source for X3/63.
Note!
The process data input words CAN−IN1.W1/FIF−IN.W1, CAN−IN1.W2/FIF−IN.W2,
CAN−IN2.W1 and CAN−IN2.W2 can be defined as analog word or digital word
(16 bit). If you link them with analog outputs (C0419/x = 50, 51 or 60, 61), they
must be defined as analog input words. Otherwise the output signal would be
incorrect.
Adjustment
Set gain (C0420) and offset (C0422) to adapt the output signal to the application.
The scalings stated in C0419 relate to gain 1 (C0420 = 128).
C# Imaging - Scan RM4SCC Barcode in C#.NET
PDF, Word, Excel and PPT) and extract barcode value Load an image or a document(PDF, TIFF, Word, Excel barcode from (scanned) images, pictures & photos that are
extract pictures from pdf; extract pictures pdf
VB.NET Image: Image Resizer Control SDK to Resize Picture & Photo
daily life, if you want to send some image files or photos to someone We are dedicated to provide powerful & profession imaging controls, PDF document, image
extract images from pdf acrobat; how to extract text from pdf image file
Function library
Free interconnection of analog signals  
Free configuration of analog outputs
10
337
EDS82EV903   EN   3.0
Output signal for selection 7
The  output  signal for selection  7  is  proportional  to the output  frequency with slip
compensation.
U
out
[V] 6,00V
fC0011
C0011C0010
U
out
Output signal
f
Output frequency
C0010
Minimum output frequency
C0011
Maximum output frequency
Output signal for selection 8
During  operation  without  process  controller,  the  output  signal  for  selection  8  is
proportional to the output frequency without slip compensation.
Application example for selection 6
The output signal acts reciprocally with the output frequency. This signal can be used for
the display of processing times (e.g. for continuous furnace products).
Example: output signal = 0 ... 10 V
U
out
[V] 1.00V
C0011
f

C0420
128
U
out
Output signal
f
Output frequency
C0011
Maximum output frequency
C0420
Analog output gain
6.00
5.00
4.00
3.00
2.00
1.00
0.00
0
10
20
30
40
50
60
Uout[V]
f[Hz]
C0420 =128
8200vec536
Fig. 10−15
Output signal of the function "1/output frequency"
Function library
Free interconnection of analog signals  
Free configuration of analog process data output words
10
338
EDS82EV903  EN  3.0
10.11.3
Free configuration of analog process data output words
Description
ƒ
The analog process data output words can be freely assigned to internal analog
process signals or monitoring signals. The controller outputs a value proportional to
the internal signal on the bus. The normalisation is indicated under C0421.
ƒ
A signal source can be assigned to several targets.
Codes for parameter setting
Code
Possible settings
IMPORTANT
No.
Name
Lenze
Selection
C0421
*
Free
configuration
of analog
process data
output words
Output of analog signals to bus
  338
1
AIF−OUT.W1
8
Operation with process controller
(C0238 = 0, 1):
Actual process controller value
(PCTRL1−ACT)
Operation without process controller
(C0238 = 2):
Output frequency without slip
(MCTRL1−NOUT)
2
AIF−OUT.W2
0
Output frequency
(MCTRL1−NOUT+SLIP)
3
CAN−OUT1.W1
/ FIF−OUT.W1
255
Not assigned (FIXED−FREE)
CAN−OUT1.W1 and
FIF−OUT.W1 are digitally
defined in the Lenze setting
and assigned to the 16 bits of
the controller status word 1
(C0417)
Before assigning an analog
signal source (C0421/3  255),
first delete the digital
assignment (C0417/x = 255)!
Otherwise, the output signal
would be wrong
4
CAN−OUT1.W2
/ FIF−OUT.W2
255
Not assigned (FIXED−FREE)
5
CAN−OUT1.W3
/ FIF−OUT.W3
255
Not assigned (FIXED−FREE)
6
CAN−OUT1.W4
/ FIF−OUT.W4
255
Not assigned (FIXED−FREE)
7
CAN−OUT2.W1
255
Not assigned (FIXED−FREE)
8
CAN−OUT2.W2
255
Not assigned (FIXED−FREE)
9
CAN−OUT2.W3
255
Not assigned (FIXED−FREE)
10
CAN−OUT2.W4
255
Not assigned (FIXED−FREE)
Function library
Free interconnection of analog signals  
Free configuration of analog process data output words
10
339
EDS82EV903   EN   3.0
IMPORTANT
Possible settings
Code
Selection
Lenze
Name
No.
C0421
*
(Cont.)
Possible analog signals for C0421
  338
0
Output frequency
(MCTRL1−NOUT+SLIP)
24000  480 Hz
1
Device utilisation (MCTRL1−MOUT) at
V/f characteristic control (C0014 = 2 or
3)
16383  Rated active inverter
current (active current/C0091)
Actual motor torque (MCTRL1−MACT)
with vector control (C0014 = 4) or
sensorless torque control (C0014 = 5)
16383  Rated motor torque
2
Apparent motor current
(MCTRL1−IMOT)
16383  Rated inverter current
3
DC−bus voltage (MCTRL1−DCVOLT)
16383  565 V DC at 400 V mains
16383  325 V DC at 230 V mains
4
Motor power
285  Rated motor power
5
Motor voltage (MCTRL1−VOLT)
16383  Rated motor voltage
6
1/output frequency (1/C0050)
(MCTRL1−1/NOUT)
195  0.5  C0011
7
Output frequency within adjusted
limits (DCTRL1−C0010...C0011)
24000  480 Hz
0 f C0010
24000(fC0010)
480Hz
 f C0010
8
Operation with process controller
(C0238 = 0, 1):
Actual process controller value
(PCTRL1−ACT)
24000  480 Hz
Operation without process controller
(C0238 = 2):
Output frequency without slip
(MCTRL1−NOUT)
Function library
Free interconnection of analog signals  
Free configuration of analog process data output words
10
340
EDS82EV903  EN  3.0
IMPORTANT
Possible settings
Code
Selection
Lenze
Name
No.
C0421
*
(Cont.)
Possible analog signals for C0421
Selection 9 ... 25 corresponds to
the digital functions of relay
output K1 (C0008) or digital
output A1 (C0117):
LOW = 0
HIGH = 1023
  338
9
Ready for operation (DCTRL1−RDY)
10
TRIP error message (DCTRL1−TRIP)
11
Motor is running (DCTRL1−RUN)
12
Motor is running / CW rotation
(DCTRL1−RUN−CW)
13
Motor is running / CCW rotation
(DCTRL1−RUN−CCW)
14
Output frequency = 0
(DCTRL1−NOUT=0)
15
Frequency setpoint reached
(DCTRL1−RFG1=NOUT)
16
Values have fallen below frequency
threshold Q
min
(f < C0017)
(PCTRL1−QMIN)
17
I
max
limit reached (MCTRL1−IMAX)
C0014 = −5−: Torque setpoint reached
18
Overtemperature (
max
−5 °C)
(DCTRL1-OH-WARN)
19
TRIP or Q
min
or pulse inhibit (IMP)
(DCTRL1−IMP)
20
PTC warning (DCTRL1−PTC−WARN)
21
Apparent motor current < current
threshold (DCTRL1−IMOT<ILIM)
V−belt monitoring
Apparent motor current = C0054
Current threshold = C0156
Frequency threshold Q
min
= C0017
22
Apparent motor current < current
threshold and output frequency >
Frequency threshold Q
min
(DCTRL1−(IMOT<ILIM)−QMIN)
23
Apparent motor current < current
threshold and ramp function generator
1: input = output
(DCTRL1−(IMOT<ILIM)−RFG−I=0)
24
Motor phase failure warning
(DCTRL1−LP1−WARN)
25
Min. output frequency reached
(f  C0010) (PCTRL1−NMIN)