Function library
External fault evaluation
External fault detection
10
361
EDS82EV903   EN   3.0
10.14
External fault evaluation 
10.14.1
External fault detection 
Description
Use the internal digital signal DCTRL1−TRIP−SET to evaluate external disturbances and
integrate them into the monitoring of the system. If an external disturbance is recognised,
the controller indicates the fault EEr and sets controller inhibit.
Note!
The function is LOW active.
Activation
ƒ
C0410/11 (DCTRL1−TRIP−SET) must be combined with digital signal source.
ƒ
LOW level at the signal source for DCTRL1−TRIP−SET sets fault message EEr and
activates the controller inhibit.
Note!
Use C0007 to carry out a fixed configuration of DCTRL1−TRIP−SET with the
digital inputs X3/E1 ... X3/E4. C0410/11 will be automatically adapted.
10.14.2
Reset of external faults 
Description
You can reset a fault message with the internal digital signal DCTRL1−TRIP−RESET, when the
cause of disturbance has been removed.
Note!
A LOW−HIGH signal resets the fault message.
Activation
ƒ
C0410/12 (DCTRL1−TRIP−RESET) must be combined with digital signal source.
ƒ
LOW−HIGH signal at the signal source for DCTRL1−TRIP−RESET resets the fault
message.
Note!
Further options to reset fault messages: (  459) 
Extract image from pdf using - Select, copy, paste PDF images in C#.net, ASP.NET, MVC, Ajax, WinForms, WPF
Support PDF Image Extraction from a Page, a Region on a Page, and PDF Document
pdf image extractor; extract jpg from pdf
Extract image from pdf using - VB.NET PDF Image Extract Library: Select, copy, paste PDF images in vb.net, ASP.NET, MVC, Ajax, WinForms, WPF
Support PDF Image Extraction from a Page, a Region on a Page, and PDF Document
extract vector image from pdf; extract images from pdf files
Function library
Display of operating data, diagnostics
Display of operating data
10
362
EDS82EV903  EN  3.0
10.15
Display of operating data, diagnostics 
10.15.1
Display of operating data 
Description
Important operating parameters are measured by the controller. They can be displayed
with the keypad or PC.
Some operating data can be calibrated to be displayed or selected directly with the unit of
the process quantity (e.g. pressure, temperature, speed).
Note!
The calibration always affects all specified codes simultaneously.
Codes for parameter setting
Code
Possible settings
IMPORTANT
No.
Name
Lenze
Selection
C0004
*
Bar graph
display
56
1
{Code
no.}
989
The bar graph display shows
the selected value in % after
mains connection
Range −180 % ... +180 %
56 = device utilisation (C0056)
C0044
*
Setpoint 2
(NSET1-N2)
−650.00
{0.02
Hz}
650.00
The set value will be lost during
mains switching!
Selection if C0412/2 =
FIXED−FREE (not assigned)
Display if C0412/2 is linked to
a signal source
  311
C0046
*
Setpoint 1
(NSET1-N1)
−650.00
{0.02
Hz}
650.00
The set value will be lost during
mains switching!
Selection if C0412/1 =
FIXED−FREE (not assigned)
Display if C0412/1 is linked to
a signal source
  311
C0047
*
Torque
setpoint or
torque limit
(MCTRL1−
MSET)
400
0
{1 %}
400
The set value will be lost during
mains switching!
  264
Reference: Rated motor torque determined
through motor parameter identification
In "Sensorless torque control"
operating mode (C0014 = 5):
Torque setpoint selection if
C0412/6 = FIXED−FREE (not
assigned)
Torque setpoint display if
C0412/6 is linked to a signal
source
In "V/f characteristic control" or
"Vector control" operating mode
(C0014 = 2, 3, 4):
Display of the torque limit
value if C0412/6 is linked to a
signal source
Display C0047 = 400 if
C0412/6 = FIXED−FREE (not
assigned)
C0049
*
Additional
setpoint
(PCTRL1−NADD)
−650.00
{0.02
Hz}
650.00
The set value will be lost during
mains switching!
Selection if C0412/3 =
FIXED−FREE (not assigned)
Display if C0412/3 is linked to
a signal source
VB.NET PDF Text Extract Library: extract text content from PDF
Extract highlighted text out of PDF document. Image text extraction control provides text extraction from PDF images and image files.
extract images from pdf acrobat; extract images pdf acrobat
C# PDF Text Extract Library: extract text content from PDF file in
Ability to extract highlighted text out of PDF document. Supports text extraction from scanned PDF by using XDoc.PDF for .NET Pro. Image text extraction control
extract images from pdf c#; extract color image from pdf in c#
Function library
Display of operating data, diagnostics
Display of operating data
10
363
EDS82EV903   EN   3.0
IMPORTANT
Possible settings
Code
Selection
Lenze
Name
No.
C0050
*
uSEr
Output freq.
(MCTRL1−
NOUT)
−650.00
{Hz}
650.00 Read only: Output frequency
without slip compensation
C0051
*
Output freq.
with slip
compensation
(MCTRL1−NOUT
+SLIP) or
Actual process
controller
value
(PCTRL1−ACT)
−650.00
{0.02
Hz}
650.00
The set value will be lost during
mains switching!
During operation without process
controller (C0238 = 2):
Read only: output frequency
with slip compensation
(MCTRL1−NOUT+SLIP)
During operation with process
controller (C0238 = 0, 1):
Selection if C0412/5 =
FIXED−FREE (not assigned)
Display if C0412/5 is linked to
a signal source
  324
C0052
*
Motor voltage
(MCTRL1−VOLT)
0
{V}
1000
Read only
C0053
*
DC−bus voltage
(MCTRL1−
DCVOLT)
0
{V}
1000
Read only
C0054
*
Apparent
motor current
(MCTRL1−
IMOT)
0.0
{A}
2000.0
Read only
C0056
*
Device
utilisation
(MCTRL1−
MOUT)
−255
{%}
255
Read only
The display value for the "Vector
control" or "Sensorless torque
control" operating mode can be
changed in C0311.
C0061
*
Heatsink
temperature
0
{°C}
255
Read only
If the heatsink temperature
> 
max
− 5 °C:
–Warning OH is provided
–Switching frequency is
reduced to 4 kHz if C0144 = 1
If the heatsink temperature
> 
max
:
–Controller sets TRIP OH
C0138
*
Process
controller
setpoint 1
(PCTRL1−SET1)
0.00
−650.00
{0.02
Hz}
650.00
The set value will be lost during
mains switching!
Selection if C0412/4 =
FIXED−FREE
Display if C0412/4 
FIXED−FREE
  322
C0189
*
(A)
Output signal −
follow−up
controller
(PCTRL1−FOLL1−
OUT)
−650.00
{0.02
Hz}
650.00
Read only
Follow−up controller =
PCTRL1−FOLL1
C0320
(A)
Actual process
controller value
(PCTRL1−ACT)
−650.00
{0.02
Hz}
650.00
Read only
C0321
(A)
Process
controller
setpoint
(PCTRL1−SET)
−650.00
{0.02
Hz}
650.00
Read only
C# PDF insert image Library: insert images into PDF in C#.net, ASP
C#.NET PDF SDK - Add Image to PDF Page in C#.NET. How to Insert & Add Image, Picture or Logo on PDF Page Using C#.NET. Add Image to PDF Page Using C#.NET.
some pdf image extractor; extract image from pdf online
VB.NET PDF insert image library: insert images into PDF in vb.net
Insert Image to PDF Page Using VB. Add necessary references: RasterEdge.Imaging. Basic.dll. RasterEdge.Imaging.Basic.Codec.dll. RasterEdge.Imaging.Drawing.dll.
extract photos from pdf; how to extract pictures from pdf files
Function library
Display of operating data, diagnostics
Display of operating data
10
364
EDS82EV903  EN  3.0
IMPORTANT
Possible settings
Code
Selection
Lenze
Name
No.
C0322
(A)
Process
controller
output without
feedforward
control
(PCTRL1−OUT)
−650.00
{0.02
Hz}
650.00 Read only
C0323
(A)
Ramp function
generator
input
(NSET1−RFG1−
IN)
−650.00
{0.02
Hz}
650.00
Read only
C0324
(A)
Ramp function
generator
output
(NSET1−NOUT)
−650.00
{0.02
Hz}
650.00
Read only
C0325
(A)
PID controller
output
(PCTRL1−PID−
OUT)
−650.00
{0.02
Hz}
650.00
Read only
C0326
(A)
Process
controller
output
(PCTRL1−NOUT)
−650.00
{0.02
Hz}
650.00
Read only
C0500
*
Calibration of
process
variable −
numerator
2000
1
{1}
25000
Codes C0010, C0011, C0017,
C0019, C0037, C0038, C0039,
C0044, C0046, C0049, C0050,
C0051, C0138, C0140, C0181,
C0239, C0625, C0626, C0627
can be calibrated in a way to
make the keypad display a
process variable
If C0500/C0501 are changed,
the "Hz" unit is not shown in
the display anymore
  362
C0501
*
Calibration of
process
variable −
denominator
10
1
{1}
25000
C0500
*
(A)
Calibration of
process
variable −
numerator
2000
1
{1}
25000
Codes C0037, C0038, C0039,
C0044, C0046, C0049, C0051,
C0138, C0140, C0181 can be
calibrated in a way to make the
keypad display a process
variable in the unit selected in
C0502
Frequency−dependent codes
such as C0010, C0011, C0017,
C0019, C0050, C0239, C0625,
C0626, C0627 are always
provided in "Hz"
Changes in codes C0500 and
C0501 affect codes C0010 and
C0011; their values are scaled
correspondingly in the process
  362
C0501
*
(A)
Calibration of
process
variable −
denominator
10
1
{1}
25000
C0502
*
(A)
Unit − process
variable
0
0: 
1: ms
2: s
4: A
5: V
6: rpm
9: °C
10: Hz
11: kVA
12: Nm
13: %
14: kW
15: N
16: mV
17: m
18: 
19: hex
34: m
35: h
42: mH
C# PDF Page Extract Library: copy, paste, cut PDF pages in C#.net
Able to extract single or multiple pages from adobe portable document format, known as PDF document, is a documents even though they are using different types
how to extract a picture from a pdf; extract text from image pdf file
C# Create PDF from images Library to convert Jpeg, png images to
Free library is access to downloading and using in .NET framework. If you want to turn PDF file into image file format in C# application, then RasterEdge XDoc
extract text from pdf image; extract image from pdf acrobat
Function library
Display of operating data, diagnostics
Display of operating data
10
365
EDS82EV903   EN   3.0
Calibration
The calibrated value can be calculated from:
C0xxx
C0011
200
C0500
C0501
Example of calibration
The pressure setpoint is selected in bar.
The maximum pressure of 5 bar (100 %) is reached if C0011 = 50 Hz.
Relative calibration in %
100% 
50
200

C0500
C0501

50
200

4000
10
Solution with e.g. C0500 = 4000, C0501 = 10
Absolute calibration in bar
5.00bar 
50
200
C0500
C0501

50
200
200
10
Solution with e.g. C0500 = 200, C0501 = 10
Note!
During operation with standard I/O, frequency−related codes such as C0010,
C0011, C0017, C0019, C0050, C0239, C0625, C0626 and C0627 are also
displayed in the unit defined through calibration.
C# PDF - Extract Text from Scanned PDF Using OCR SDK
VB.NET Write: Add Image to PDF; VB.NET Protect: Add Password to PDF; VB.NET Form: extract value from VB.NET Annotate: PDF Markup & Drawing. XDoc.Word for C#;
pdf image extractor online; pdf extract images
C# PDF Form Data Read Library: extract form data from PDF in C#.
PDF software, it should have functions for processing text, image as well as C#.NET Project DLLs: Read and Extract Field Data in C#. using RasterEdge.XDoc.PDF;
how to extract images from pdf; online pdf image extractor
Function library
Display of operating data, diagnostics
Diagnostics
10
366
EDS82EV903  EN  3.0
10.15.2
Diagnostics
Description
Display codes for diagnostics
Codes for parameter setting
Code
Possible settings
IMPORTANT
No.
Name
Lenze
Selection
C0093
*
Device type
xxxy
Read only
xxx = performance data from
the type code (e.g. 551 = 550
W)
y = voltage class (2 = 240 V,
4 = 400 V)
C0099
*
Software
version
x.y
Read only
x = major version, y = index
C0161
*
Active fault
Display of history buffer contents
Keypad: three−digit
alphanumeric fault
identification
Operating module 9371BB:
LECOM error number
  453
C0162
*
Last fault
C0163
*
Last fault but
one
C0164
*
Last fault but
two
C0168
*
Pending error
Display of history buffer "Active
fault"
Keypad: three−digit
alphanumeric fault
identification
Operating module 9371BB:
LECOM error number
  453
C0179
*
Power−on time
{h}
Read only
Total time of mains "ON"
C0183
*
Diagnostics
0
No fault
Read only
102
TRIP active
104
Message "Overvoltage (OU)" or
"Undervoltage (LU)" active
142
Pulse inhibit
151
Quick stop is active
161
DC injection brake active
250
Warning active
C0200
*
Software ID
Read only on PC
x = main version, y = subversion
82S8212V_xy000
8200 vector 0.25 ... 11 kW
82S8212V_xy010
8200 vector 15 ... 90 kW
C0201
*
Software
creation date
Read only on PC
C0202
*
Software ID
Output in keypad as string in four parts at four
characters each
Read only in keypad
1
82S8
2
212 V
3
_xy0
x = main version, y = subversion
4
zz
00 = 8200 vector 0.25 ... 11 kW
10 = 8200 vector 15 ... 90 kW
Function library
Display of operating data, diagnostics
Diagnostics
10
367
EDS82EV903   EN   3.0
IMPORTANT
Possible settings
Code
Selection
Lenze
Name
No.
C0304
Service codes
Alterations by Lenze service only!
...
C0309
C0372
*
Identification
function
module
0
No function module
Display only
1
Standard I/O or AS−i
2
System bus (CAN)
6
Other function module on FIF
e.g. Application I/O, INTERBUS, ...
10
No valid identification
C0518
Service codes
Alterations by Lenze service only!
C0519
C0520
C1500
*
(A)
Software ID
application I/O
82SAFA0B_xy000
Read only on PC
x = main version
y = subversion
C1501
*
(A)
Software
creation date −
application I/O
Read only on PC
C1502
*
(A)
Software ID
application I/O
Output in keypad as string in four parts at four
characters each
Read only in keypad
x = main version
y = subversion
1
82SA
2
FA0B
3
_xy0
4
00
C1504
(A)
Service codes −
application I/O
Alterations by Lenze service only!
...
C1507
(A)
C1550
(A)
Service code −
application I/O
Alterations by Lenze service only!
Function library
Parameter set management
Saving and copying parameter sets
10
368
EDS82EV903  EN  3.0
10.16
Parameter set management 
10.16.1
Saving and copying parameter sets 
Description
Management of the controller parameter sets. It is possible to
ƒ
restore the Lenze setting and put the controller into the delivery state again.
ƒ
save your own basic setting, e.g. the delivery state of the machine.
ƒ
transfer parameter sets from the keypad to the controller or vice versa. The settings
can thus be easily copied between controllers.
Codes for parameter setting
Code
Possible settings
IMPORTANT
No.
Name
Lenze
Selection
C0002
*
uSEr
Parameter set
management
0
0
Ready
PAR1 ... PAR4:
Parameter sets of the controller
PAR1 ... PAR4 also contain the
parameters for the function
modules standard I/O,
application I/O, AS interface,
system bus (CAN)
FPAR1:
Module−specific parameter set
of the fieldbus function
modules INTERBUS,
PROFIBUS−DP, LECOM−B,
DeviceNet/CANopen
FPAR1 is saved in the function
module
  368
Restoring the
delivery status
1
Lenze setting  PAR1
Restore the delivery status in the
parameter set selected
2
Lenze setting  PAR2
3
Lenze setting  PAR3
4
Lenze setting  PAR4
31
Lenze setting  FPAR1
Restore the delivery status in the
fieldbus function module
61
Lenze setting  PAR1 + FPAR1
Restore the delivery status in the
selected parameter set of the
controller and in the fieldbus
function module
62
Lenze setting  PAR2 + FPAR1
63
Lenze setting  PAR3 + FPAR1
64
Lenze setting  PAR4 + FPAR1
C0002
*
uSEr
(Continu
ation)
Transferring
parameter sets
with the
keypad
By means of the keypad you can
transfer the parameter sets to
other controllers.
During the transmission the access
to the parameters via other
channels is inhibited!
Keypad  controller
Overwrite all available parameter
sets (PAR1 ... PAR4, if required
FPAR1) with the corresponding
data of the keypad
70
with function module application I/O,
INTERBUS, PROFIBUS−DP, LECOM−B,
DeviceNet, CANopen
10
with all other function modules
Function library
Parameter set management
Saving and copying parameter sets
10
369
EDS82EV903   EN   3.0
IMPORTANT
Possible settings
Code
Selection
Lenze
Name
No.
C0002
*
uSEr
(Cont.)
Transferring
parameter sets
with the
keypad
Keypad  PAR1 (+ FPAR1)
Overwrite selected parameter set
and, if required FPAR1, with the
corresponding data of the keypad
71
with function module application I/O,
INTERBUS, PROFIBUS−DP, LECOM−B,
DeviceNet/CANopen
11
with all other function modules
Keypad  PAR2 (+ FPAR1)
72
with function module application I/O,
INTERBUS, PROFIBUS−DP, LECOM−B,
DeviceNet/CANopen
12
with all other function modules
Keypad  PAR3 (+ FPAR1)
73
with function module application I/O,
INTERBUS, PROFIBUS−DP, LECOM−B,
DeviceNet/CANopen
13
with all other function modules
Keypad  PAR4 (+ FPAR1)
74
with function module application I/O,
INTERBUS, PROFIBUS−DP, LECOM−B,
DeviceNet/CANopen
14
with all other function modules
Controller  keypad
Copy all available parameter sets
(PAR1 ... PAR4, if required FPAR1)
into the keypad
80
with function module application I/O,
INTERBUS, PROFIBUS−DP, LECOM−B,
DeviceNet/CANopen
20
with all other function modules
Keypad  function module
Only overwrite the
module−specific parameter set
FPAR1 with the data of the keypad
40
only with function module INTERBUS,
PROFIBUS−DP, LECOM−B,
DeviceNet/CANopen
Function module  keypad
Only copy the module−specific
parameter set FPAR1 into the
keypad
50
only with function module INTERBUS,
PROFIBUS−DP, LECOM−B,
DeviceNet/CANopen
C0002
*
uSEr
(Cont.)
Saving your
own basic
setting
9
PAR1  own basic setting
For the parameters of the
controller you can save an own
basic setting (e.g. the delivery
status of your machine):
1. Ensure that parameter set 1 is
active
2. Inhibit controller
3. Set C0003 = 3, confirm with
4. Set C0002 = 9, confirm with
, the own basic setting is
saved
5. Set C0003 = 1, confirm with
6. Enable the controller
C0002
*
uSEr
(Cont.)
Loading/copyin
g the own basic
setting
By using this function you can also
just copy PAR1 into the parameter
sets PAR2 ... PAR4
5
own basic setting  PAR1
Restore own basic setting in the
parameter set selected
6
own basic setting  PAR2
7
own basic setting  PAR3
8
own basic setting  PAR4
Function library
Parameter set management
Saving and copying parameter sets
10
370
EDS82EV903  EN  3.0
IMPORTANT
Possible settings
Code
Selection
Lenze
Name
No.
C0003
*
Saving
parameters
non−volatilely
1
0
Do not save parameters in the EEPROM Data loss after mains switch−off
1
Always save parameters in the EEPROM
Active after every mains
connection
Cyclic alteration of parameters
via bus module is not
permissible
3
Save your own basic setting in the
EEPROM
Afterwards save parameter set 1
as own basic setting with
C0002 = 9
Note!
ƒ
Do not remove keypad as long as the parameters are being transmitted! If
the keypad is removed during transmission, the controller indicates the
errors "Prx" or "PT5".
ƒ
A detailed description of the keypads can be found in the "Parameter
setting" chapter.
Restoring the delivery status
1. Attach keypad.
2. Inhibit controller with  or via terminal (X3/28 = LOW).
3. Set the correct selection number in C0002 from the "Restore delivery status"
category and confirm with 
.
–E.g. C0002 = 1: Parameter set 1 of the controller is overwritten with Lenze setting.
Parameter set transfer from the controller to the keypad
1. Attach keypad.
2. Inhibit controller with  or via terminal (X3/28 = LOW).
3. Set C0002 = 20 or 50 or 80, confirm with 
.
Parameter set transfer from the keypad to the controller
1. Attach keypad.
2. Inhibit controller with  or via terminal (X3/28 = LOW).
3. Set the correct selection number In C0002 from the "Parameter set transfer with
keypad" category and confirm with 
.
–E.g. C0002 = 10: All parameter sets of the controller are overwritten with the
settings in the keypad.
–E.g. C0002 = 11: Parameter set 1 of the controller is overwritten with the settings
in the keypad.