Function library
Parameter set management
Saving and copying parameter sets
10
371
EDS82EV903   EN   3.0
Saving your own basic setting
1. Attach keypad.
2. Parameter set 1 must be active!
3. Inhibit controller with  or via terminal (X3/28 = LOW).
4. Set parameter in parameter set 1.
5. Set C0003 = 3 and confirm with 
.
6. Set C0002 = 9 and confirm with 
. The own basic setting is saved.
7. Set C0003 = 1 and confirm with 
.
Copying your own basic setting into the parameter sets
1. Attach keypad.
2. Inhibit controller with  or via terminal (X3/28 = LOW).
3. Set the correct selection number in C0002 from the "Loading/saving your own basic
setting" category and confirm with 
.
–E.g. C0002 = 5: Parameter set 1 is overwritten with your own basic setting.
–E.g. C0002 = 8: Parameter set 4 is overwritten with your own basic setting.
Extract pictures from pdf - Select, copy, paste PDF images in C#.net, ASP.NET, MVC, Ajax, WinForms, WPF
Support PDF Image Extraction from a Page, a Region on a Page, and PDF Document
extract pdf images; extract image from pdf c#
Extract pictures from pdf - VB.NET PDF Image Extract Library: Select, copy, paste PDF images in vb.net, ASP.NET, MVC, Ajax, WinForms, WPF
Support PDF Image Extraction from a Page, a Region on a Page, and PDF Document
extract jpg pdf; extract image from pdf in
Function library
Parameter set management
Parameter set changeover
10
372
EDS82EV903  EN  3.0
10.16.2
Parameter set changeover 
Description
During operation you can change between the four parameter sets of the controller via
digital signals. Thus 9 additional JOG values or additional acceleration and deceleration
times are available.
The  parameter  set  changeover  via  digital  signals  is  not  possible  if  the  automatic
changeover via DC−bus voltage is active!
Activation
Link C0410/13 (DCTRL1−PAR2/4) and C0410/14 (DCTRL1−PAR3/4) to a digital signal source.
After initialisation, the controller always operates with parameter set 1. The controller will
not perform a parameter set changeover before a parameter set changeover signal is
active.
Note!
ƒ
C0410/13 and C0410/14 must be linked to the same signals in all parameter
sets!
ƒ
Start the parameterisation with the highest parameter set. Carry out
parameterisation for parameter set 1 last. That way, undefined statuses are
avoided.
ƒ
If different operating modes (C0014) are set in the parameter sets, the
parameter sets should only be changed over when the controller is inhibited
(CINH).
Signal source
Active parameter set
Level at C0410/13
Level at C0410/14
LOW
LOW
Parameter set 1 (PAR1)
HIGH
LOW
Parameter set 2 (PAR2)
LOW
HIGH
Parameter set 3 (PAR3)
HIGH
HIGH
Parameter set 4 (PAR4)
Note!
In C0007, the changeover between parameter set 1 and parameter set 2 can be
linked to digital inputs X3/E2 or X3/E3.
VB Imaging - VB Code 93 Generator Tutorial
Visual VB examples here for developers to create and write Code 93 linear barcode pictures on PDF documents, multi-page TIFF, Microsoft Office Word, Excel and
extract pictures from pdf; pdf image extractor c#
VB.NET PDF Convert to Word SDK: Convert PDF to Word library in vb.
application. In addition, texts, pictures and font formatting of source PDF file are accurately retained in converted Word document file.
extract image from pdf java; extract image from pdf using
Function library
Individual summary of drive parameters in the user menu
10
373
EDS82EV903   EN   3.0
10.17
Individual summary of drive parameters in the user menu 
Description
ƒ
Quick access to ten selected codes via the user menu of the keypad
ƒ
With password protection, an individual code selection can be prepared which can
only be changed by e.g. your operating personnel.
Codes for parameter setting
Code
Possible settings
IMPORTANT
No.
Name
Lenze
Selection
C0517
*
User menu
After mains switching or in the
 function the code from
C0517/1 is displayed.
In the Lenze setting the user
menu contains the most
important codes for
commissioning the operating
mode "V/f characteristic control
with a linear characteristic"
If the password protection is
active, only the codes entered
in C0517 can be freely accessed
If less than 10 codes are
required, assign the value "0"
(zero) to the memory locations
not used. Please observe that
the software automatically
assigns code C0050 to a
memory location that is not
used, if it has not been
explicitly assigned to another
  373
1
Memory 1
50
C0050
Output frequency (MCTRL1−NOUT)
2
Memory 2
34
C0034
Range of analog setpoint selection
3
Memory 3
7
C0007
Fixed configuration of digital input
signals
4
Memory 4
10
C0010
Minimum output frequency
5
Memory 5
11
C0011
Maximum output frequency
6
Memory 6
12
C0012
Acceleration time main setpoint
7
Memory 7
13
C0013
Deceleration time main setpoint
8
Memory 8
15
C0015
V/f rated frequency
9
Memory 9
16
C0016
V
min
boost
10
Memory 10
2
C0002
Parameter set transfer
Possible entries for C0517
xxxx
All codes apart from the codes labelled
with "(A)".
Syntax:
Codes: C0517/x = cccc
Subcodes: C0517/x = cccc.ss
Adapt the user menu
Enter the desired code numbers or subcode numbers into the subcodes of C0517.
C# Imaging - C# Code 93 Generator Tutorial
Visual C# examples here for developers to create and write Code 93 linear barcode pictures on PDF documents, multi-page TIFF, Microsoft Office Word, Excel and
how to extract images from pdf in acrobat; how to extract text from pdf image file
VB.NET Image: VB.NET Codes to Load Images from File / Stream in .
When evaluating this VB.NET imaging library with pictures of your own We are dedicated to provide powerful & profession imaging controls, PDF document, image to
extract pictures pdf; extract pdf pages to jpg
Function library
Individual summary of drive parameters in the user menu
10
374
EDS82EV903  EN  3.0
Example: select the speed via keypad
The operating personnel of a conveyor is supposed to only read the output frequency
(actual speed) of the drive on the keypad and be able to change the additive frequency
setpoint (setpoint speed). The speeds are selected and displayed in "rpm":
Prepare the user menu
1. Assign memory 1 of the user menu to the display code for actual speed C0050:
–C0517/1 = 50
2. Assign memory 2 of the user menu to the code for setpoint speed C0140:
–C0517/2 = 140
3. Assign the value from memory 2 to all other memory units 3 to 10:
–C0517/3 ... C0517/10 = 140
4. Use C0500/C0501 for conversion of the display value from C0050 and C0140 in
"rpm" (  362)
5. Activate password protection:
–C0094 > 0
6. Change to the user menu.
The user menu is now prepared.
Change the setpoint speed
1. After the keypad has been plugged in or after mains switching, C0050 (actual drive
speed) is displayed ().
2.  press (, C0050)
3.  press (, C0140)
4.  press ()
–The current setpoint speed is displayed.
5. Change the setpoint speed:
– = reduce setpoint speed
– = increase setpoint speed
6.  press (, C0140)
 press (, C0050)
The setpoint speed selected last is saved when the mains is disconnected.
C#: Use OCR SDK Library to Get Image and Document Text
a digital camera, scanned document or image-only PDF using C# color image recognition for scanned documents and pictures in C#. Steps to Extract Text from Image.
extract images from pdf; extract photos pdf
VB.NET Image: Sharpen Images with DocImage SDK for .NET
VB.NET Coding. When you have made certain corrections in your VB.NET project photo or image files, you might want to sharpen your pictures before saving them
extract jpeg from pdf; extract images from pdf online
Function library
Networking
Interconnection with function module system bus (CAN) E82ZAFCCxxx
10
375
EDS82EV903   EN   3.0
10.18
Networking 
For networking with bus systems the controller has two interfaces:
ƒ
the automation interface (AIF) for communication modules
ƒ
the function interface (FIF) for function modules
A detailed description for networking with different bus system can be found in the
corresponding communication manuals.
10.18.1
Interconnection with function module system bus (CAN) E82ZAFCCxxx
Description
Codes  which  are  required  for  the  configuration  of  a  system  bus  network  with  an
E82ZAFCCxxx function module are integrated in the controller.
A detailed description can be found in the CAN communication manual.
Codes for parameter setting
Code
Possible settings
IMPORTANT
No.
Name
Lenze
Selection
C0350
*
System bus
node address
1
1
{1}
63
Only for system bus function
module E82ZAFCC on the FIF
interface.
Change becomes effective after
"Reset−Node" command
Set the node address in C0009 for
operation with communication
modules 217x.
  375
C0351
*
System bus
baud rate
0
0
500 kbps
Only for system bus function
module E82ZAFCC on the FIF
interface.
Change becomes effective after
"Reset−Node" command
Set the baud rate in C0125 for
operation with communication
modules 217x.
  375
1
250 kbps
2
125 kbps
3
50 kbps
4
1000 kbps (function module
E82ZAFCC100 only)
5
20 kbps
C0352
*
Configuration
of system bus
node
0
0
Slave
Only for system bus function
module E82ZAFCC on the FIF
interface.
Change becomes effective after
"Reset−Node" command
  375
1
Master
C0353
*
System bus
address source
Only for system bus function
module E82ZAFCC on the FIF
interface.
Source of address for system
bus process data channels
  375
1 CAN1 (Sync)
0
0
C0350 is the source
Effective with sync control (C0360
= 1)
2
CAN2
0
1
C0354 is the source
3
CAN1 (time)
0
Effective with event or time
control (C0360 = 0)
VB.NET Image: VB.NET Code to Create Watermark on Images in .NET
image one onto it, and whether to burn it to the pictures to make We are dedicated to provide powerful & profession imaging controls, PDF document, tiff files
extract images pdf; extract images from pdf files without using copy and paste
VB.NET Image: Codings for Image Filter Processing with .NET Image
RasterEdge .NET Image SDK provides many different and interesting filters for your pictures / photos with simple and a few Visual Basic .NET programming codings
some pdf image extract; extract photo from pdf
Function library
Networking
Interconnection with function module system bus (CAN) E82ZAFCCxxx
10
376
EDS82EV903  EN  3.0
IMPORTANT
Possible settings
Code
Selection
Lenze
Name
No.
C0354
*
Selective
system bus
address
0
{1}
513
Only for system bus function
module E82ZAFCC on the FIF
interface.
Single addressing of system bus
process data objects
  375
1
CAN−IN1 (sync)
129
Effective with sync control (C0360
= 1)
2
CAN−OUT1
(sync)
1
3
CAN−IN2
257
4
CAN−OUT2
258
5
CAN−IN1 (time)
385
Effective with event or time
control (C0360 = 0)
6
CAN−OUT1
(time)
386
C0355
*
System bus
identifier
0
{1}
2047
Only for system bus function
module E82ZAFCC on the FIF
interface.
Display only
  375
1
CAN−IN1
Identifier of CAN1 with sync
control (C0360 = 1)
2
CAN−OUT1
3
CAN−IN2
4
CAN−OUT2
5
CAN−IN1
Identifier of CAN1 with event or
time control (C0360 = 0)
6
CAN−OUT1
C0356
*
System bus
time settings
Only for system bus function
module E82ZAFCC on the FIF
interface.
  375
1
Boot−up
3000
0
{1 ms}
65000
Required for CAN interconnection
without master
2
CAN−OUT2
cycle time
0
0 = event−controlled process data
transfer
> 0 = cyclical process data transfer
3
CAN−OUT1
cycle time
0
0 and C0360 = 0: event−controlled
process data transfer
> 0 and C0360 = 1: cyclical process
data transfer
4
CAN delay
20
Waiting time until start of cyclical
transmission after boot−up
C0357
*
System bus
monitoring
times
Only for system bus function
module E82ZAFCC on the FIF
interface.
  375
1
CAN−IN1 (sync)
0
0
= monitoring
inactive
{1 ms}
65000
Active if C0360 = 1
TRIP CE1 with communication
fault
2
CAN−IN2
0
TRIP CE2 with communication
fault
3
CAN−IN1 (time)
0
Active if C0360 = 0
TRIP CE3 with communication
fault
C0358
*
Reset node
0
0
without function
Only for system bus function
module E82ZAFCC on the FIF
interface.
Configure system bus reset
nodal point
  375
1
System bus reset
C0359
*
System bus
status
0
Operational
Only for system bus function
module E82ZAFCC on the FIF
interface.
Display only
  375
1
Preoperational
2
Warning
3
Bus−off
C# Imaging - Scan RM4SCC Barcode in C#.NET
& decode RM4SCC barcode from scanned documents and pictures in your Decode RM4SCC from documents (PDF, Word, Excel and PPT) and extract barcode value as
pdf image text extractor; extract image from pdf
VB.NET TIFF: How to Draw Picture & Write Text on TIFF Document in
Many users concern about the issue of how to draw pictures or write text We are dedicated to provide powerful & profession imaging controls, PDF document, tiff
how to extract images from pdf files; extract images from pdf file
Function library
Networking
Interconnection with function module system bus (CAN) E82ZAFCCxxx
10
377
EDS82EV903   EN   3.0
IMPORTANT
Possible settings
Code
Selection
Lenze
Name
No.
C0360
*
Control process
data channel
CAN1
1
0
Event or time control
Only for system bus function
module E82ZAFCC on the FIF
interface.
1
Sync control
Function library
Code table
10
378
EDS82EV903  EN  3.0
10.19
Code table
How to read the code table
Column
Abbreviation
Meaning
Code
Cxxxx
Code Cxxxx
The parameter value of the code can be defined
differently within each parameter set
The parameter value is accepted immediately
(ONLINE)
1
Subcode 1 of Cxxxx
2
Subcode 2 of Cxxxx
*
Parameter value of the code is the same for all parameter sets and can be
changed in parameter set 1
Keypad E82ZBC
Changed parameter of the code or subcode will be
accepted after pressing 
Keypad XT EMZ9371BC
Changed parameter of the code or subcode will be
accepted after pressing 

Keypad E82ZBC
Changed parameter of the code or subcode will be
accepted after pressing 
if the controller is
inhibited
Keypad XT EMZ9371BC
Changed parameter of the code or subcode will be
accepted after pressing 

if the controller is
inhibited
(A)
Code, subcode or selection only available for operation with application I/O
uSEr
Code is contained in the Lenze setting in the USER menu
Designation
Name of the code
Lenze
Lenze setting (value at delivery or after restoring the delivery status with C0002)
Further information can be obtained from the "IMPORTANT" column
Selection
1
{%}
99
Min. value
{unit}max. value
IMPORTANT
Brief, important explanations
Function library
Code table
10
379
EDS82EV903   EN   3.0
Code
Possible settings
IMPORTANT
No.
Name
Lenze
Selection
C0001
Setpoint
selection
(operating
mode)
0
A change in C0001 triggers the
below−mentioned changes in
C0412 and C0410 if C0412 has
not been configured freely
before.
If C0412 has been configured
freely before (check: C0005 =
255), C0001 does not affect
C0412 and C0410. You must
link the signals manually.
Free configuration in C0412 or
C0410 does not affect C0001!
Control can be carried out via
terminals as well as via
PC/keypad.
  296
0
Setpoint selection via AIN1 (X3/8 or
X3/1U, X3/1I)
C0412/1 and C0412/2 are
linked to analog input 1
(C0412/1 = 1, C0412/2 = 1).
C0410 remains unchanged.
1
Setpoint selection via keypad or
parameter channel of an AIF bus
module
In C0412, the link to the analog
input is disconnected
(C0412/1 = 255,
C0412/2 = 255).
Setpoint selection via C0044 or
C0046.
C0410 remains unchanged.
2
Setpoint selection via AIN1 (X3/8 or
X3/1U, X3/1I)
C0412/1 and C0412/2 are
linked to analog input 1
(C0412/1 = 1, C0412/2 = 1).
C0410 remains unchanged.
3
Setpoint selection via process data
channel of an AIF bus module
C0001 = 3 must be set for the
setpoint selection via process
data channel of an AIF bus
module (types 210x, 211x,
213x, 217x)! Otherwise the
process data will not be
evaluated.
C0412/1 and C0412/2 are
linked to analog input words
AIF−IN.W1 and AIF−IN.W2
(C0412/1 = 10, C0412/2 = 11).
C0410/1 ... C0410/16 are
linked to the individual bits of
the AIF control word (AIF−CTRL)
(C0410/1 = 10 ... C0410/16 = 2
5).
Function library
Code table
10
380
EDS82EV903  EN  3.0
IMPORTANT
Possible settings
Code
Selection
Lenze
Name
No.
C0002
*
uSEr
Parameter set
management
0
0
Ready
PAR1 ... PAR4:
Parameter sets of the
controller
PAR1 ... PAR4 also contain the
parameters for the function
modules standard I/O,
application I/O, AS interface,
system bus (CAN)
FPAR1:
Module−specific parameter set
of the fieldbus function
modules INTERBUS,
PROFIBUS−DP, LECOM−B,
DeviceNet/CANopen
FPAR1 is saved in the function
module
  368
Restoring the
delivery status
1
Lenze setting  PAR1
Restore the delivery status in the
parameter set selected
2
Lenze setting  PAR2
3
Lenze setting  PAR3
4
Lenze setting  PAR4
31
Lenze setting  FPAR1
Restore the delivery status in the
fieldbus function module
61
Lenze setting  PAR1 + FPAR1
Restore the delivery status in the
selected parameter set of the
controller and in the fieldbus
function module
62
Lenze setting  PAR2 + FPAR1
63
Lenze setting  PAR3 + FPAR1
64
Lenze setting  PAR4 + FPAR1
C0002
*
uSEr
(Cont.)
Transferring
parameter sets
with the
keypad
By means of the keypad you can
transfer the parameter sets to
other controllers.
During the transmission the
access to the parameters via other
channels is inhibited!
Keypad  controller
Overwrite all available parameter
sets (PAR1 ... PAR4, if required
FPAR1) with the corresponding
data of the keypad
70
with function module application I/O,
INTERBUS, PROFIBUS−DP, LECOM−B,
DeviceNet, CANopen
10
with all other function modules