Braking operation
Braking operation with external brake resistor
Rating for Lenze brake resistors
13
491
EDS82EV903   EN   3.0
13.2.4
Rating for Lenze brake resistors
Order no.
Resistor
R
B
Continuous
power 
2)
P
d
Heat
C
B
Switch−on cycle
Max. cable
cross−section 
RB1, RB2
Mass
[]
[kW]
[kWs]
[mm2]
AWG
[kg]
ERBM470R020W 1)
470
0.02
3.0 3)
1:10
Brake for a
maximum of 15
s, then apply a
recovery time of
at least 135 s
4
12
0.25
ERBM470R050W 
1)
470
0.05
7.5
6
10
0.60
ERBM470R100W
470
0.1
15
6
10
0.75
ERBM200R100W 
1)
200
0.1
15
6
10
0.60
ERBM370R150W
370
0.15
22.5
6
10
0.95
ERBM100R150W 1)
100
0.15
22.5
6
10
0.95
ERBM082R150W 1)
82
0.15
22.5
6
10
0.95
ERBM240R200W
240
0.2
30
6
10
1.25
ERBM082R200W 1)
82
0.2
30
6
10
1.25
ERBM052R200W 1)
52
0.2
30
6
10
1.25
ERBD180R300W
180
0.3
45
10
6
2.0
ERBD100R600W
100
0.6
83
10
6
3.1
ERBD082R600W
82
0.6
87
10
6
3.1
ERBD068R800W
68
0.8
120
10
6
4.3
ERBD047R01K2
47
1.2
174
10
6
4.9
ERBD033R02K0 4)
33
2.0
240
10
6
7.1
ERBD022R03K0 
4)
22
3.0
375
10
6
10.6
ERBD018R06K0 4)
18
6.0
900
10
6
10.6
ERBD018R03K0 4)
18
3.0
375
10
6
10.6
ERBD018R01K6 4)
18
1.6
240
10
6
10.6
1) Only for controllers with a rated mains voltage of 230 V
2) The continuous power is a reference value for the selection of brake resistors. Braking at peak braking power
(V
DC
2
/R).
3) Braking for max. 10 s
4) In conjunction with brake module EMB9352
Note!
If required, multiple brake resistors can be connected in parallel or in series:
Here, the value must not fall below the minimum permissible brake resistance
value of the controller.
13.2.5
Installation and wiring of the components for braking operation
Note!
Read the documentation for the accessories. Please observe the safety
instructions and operating conditions provided therein.
How to extract images from pdf - Select, copy, paste PDF images in C#.net, ASP.NET, MVC, Ajax, WinForms, WPF
Support PDF Image Extraction from a Page, a Region on a Page, and PDF Document
how to extract pictures from pdf files; extract images from pdf online
How to extract images from pdf - VB.NET PDF Image Extract Library: Select, copy, paste PDF images in vb.net, ASP.NET, MVC, Ajax, WinForms, WPF
Support PDF Image Extraction from a Page, a Region on a Page, and PDF Document
extract jpg pdf; extract images from pdf files without using copy and paste
Safety engineering
Important notes
14
492
EDS82EV903  EN  3.0
14
Safety engineering
14.1
Important notes
Controller version x4x supports the "Safe torque off" (STO) safety function according to IEC
61800−5−2  (formerly  "Safe  standstill"),  "Protection  against  unexpected  start−up"
according to the requirements of performance level "PL d" of EN ISO 13849−1. Depending
on the external wiring, up to "PL d" according to EN ISO 13849−1 is reached.
Note!
The two independent "Pulse inhibit via safety relay K
SR
" and "Controller
inhibit" methods must be used for the "PL d" performance level according to
EN ISO 13849−1 to be complied with.
ƒ
Only qualified personnel may install and commission the Safe torque off" function.
ƒ
All control components (switches, relays, PLC, ...) and the control cabinet must
comply with the requirements of EN ISO 13849−1 and EN ISO 13849−2. This includes
among other things:
–Control cabinet, switches, relays in enclosure IP54!
–All other requirements can be found in EN ISO 13849−1 and EN ISO 13849−2!
ƒ
Wiring with insulated wire end ferrules or rigid cables is absolutely required.
ƒ
All safety−relevant cables (e.g. control cable for the safety relay, feedback contact)
outside the control cabinet must be protected, e.g. by a cable duct. It must be
ensured that short circuits between the individual cables cannot occur!
ƒ
With the Safe torque off" function no emergency stop can be effected without
additional measures:
–There is neither an electrical isolation between motor and controller nor a service
or repair switch!
–An "Emergency stop" requires the electrical isolation of the conductor to the
motor, e.g. by means of a central mains contactor with emergency stop wiring.
ƒ
If in the case of the "Safe torque off" a force effect is to be expected from outside,
(e.g. sagging of hanging loads), additional measures are required (e.g. mechanical
brakes).
ƒ
After the installation the operator has to check the function of the "Safe torque off"
circuit.
–The functional test must be repeated at regular intervals.
–Basically, the inspection intervals depend on the application, the related risk
analysis, and the overall system. The inspection intervals must not be longer than
1 year.
VB.NET PDF Text Extract Library: extract text content from PDF
Extract highlighted text out of PDF document. Image text extraction control provides text extraction from PDF images and image files.
extract text from image pdf file; extract pdf images
C# PDF Text Extract Library: extract text content from PDF file in
Ability to extract highlighted text out of PDF document. Image text extraction control provides text extraction from PDF images and image files.
extract images from pdf file; extract images from pdf files
Safety engineering
Operating mode
14
493
EDS82EV903   EN   3.0
14.2
Operating mode
34
X3.1
33
K32
K31
CINH
5V
µC
PWM
PWM
-
~
U
V
W
Ax
K
SR
&
8200vec110
Fig. 14−1
Internal connection of the "Safe torque off" function with 3 electrically isolated circuits
Area :
Pulse inhibit via safety relay K
SR
; forcibly guided feedback for monitoring the safety
relay
Area :
Controller inhibit (CINH, e.g. standard I/O X3/28), optional feedback via a digital
output (Ax, e.g. standard I/O X3/A1)
Area :
Power output stage
Activating "Safe torque off"
The "Safe torque off" status is activated via two different disconnecting paths which are
independent of each other:
1st disconnecting path: pulse inhibit via safety relay K
SR
(terminal X3.1/33, X3.1/34)
ƒ
In the case of LOW level at terminals X3.1/33, X3.1/34, the safety relay K
SR
is
deactivated.The driver supply of the power section drivers is interrupted. The
inverter no longer receives pulses.
ƒ
The disconnection of the safety relay K
SR
has to be monitored externally, so that a
failure of this disconnecting path can be detected. X3.1/K31, X3.1/K32 is a forcibly
guided break contact, i.e. if the safety relay K
SR
has been deactivated ("Safe torque
off" activated), the contact is closed.
2nd disconnecting path: controller  inhibit via input signal at  terminal  CINH  (e.g. at
standard I/O terminal X3/28)
ƒ
The input signal CINH is fed to the microcontroller system and the PWM unit. In the
case of LOW level at terminal CINH, the output of pulses to the inverter is inhibited
in the microcontroller system.
ƒ
The disconnecting path "Controller inhibit" can be evaluated optionally via a digital
output. Further information can be gathered from the chapter "Functional test"
(  498).
"Safe  torque  off"  is  activated  if there is a  LOW  level  at  both  disconnecting  paths.
Independent of the other channels, every single channel suppresses the output of pulses
to the inverter (single−fault−safety).
VB.NET PDF Page Extract Library: copy, paste, cut PDF pages in vb.
VB.NET: Extract All Images from PDF Document. This is an example that you can use it to extract all images from PDF document. ' Get page 3 from the document.
how to extract text from pdf image file; extract pdf pages to jpg
C# Create PDF from images Library to convert Jpeg, png images to
C#.NET Project DLLs for Conversion from Images to PDF in C#.NET Program. C# Example: Convert More than Two Type Images to PDF in C#.NET Application.
extract image from pdf; how to extract images from pdf file
Safety engineering
Operating mode
14
494
EDS82EV903  EN  3.0
Deactivating "Safe torque off"
An AND operation of the disconnecting paths prevents the drive from restarting if only one
disconnecting path is enabled.
"Safe torque off" is deactivated (output of pulses to the inverter is enabled) if there is a
HIGH level at both disconnecting paths.
Note!
8200 vector E82xV...x4x with application I/O − can only be used with one
disconnecting path:
Always switch the controller inhibit (terminal x3.3/28) together with safety
relay Ksr.
Otherwise the motor will start without acceleration ramp or with a shorter
acceleration ramp.
C# PDF Page Extract Library: copy, paste, cut PDF pages in C#.net
Page: Extract, Copy and Paste PDF Pages. Easy to Use C# Code to Extract PDF Pages, Copy Pages from One PDF File and Paste into Others in C#.NET Program.
how to extract a picture from a pdf; how to extract images from pdf files
C# PDF insert image Library: insert images into PDF in C#.net, ASP
Powerful .NET PDF image edit control, enable users to insert vector images to PDF file. Merge several images into PDF. Insert images into PDF form field.
how to extract images from pdf files; extract image from pdf
Safety engineering
Safety relay K
SR
14
495
EDS82EV903   EN   3.0
14.3
Safety relay K
SR
Technical data
Terminal
Description
Range
Values
X3.1/K32
X3.1/K31
X3.1/33
X3.1/34
Safety relay K
SR
1st disconnecting path
Coil voltage at +20 °C
DC 24 V (20 ... 30 V)
Coil resistance at +20 °C
823  ±10 %
Rated coil power
Approx. 700 mW
Max. switching voltage
AC 250 V, DC 250 V (0.45 A)
Max. switching capacity, AC
1500 VA
Max. switching current (ohmic load)
AC 6 A (250 V), DC 6 A (50 V)
Recommended minimum load
> 50 mW
Max. operating frequency
6 switching operations per minute
Mechanical service life
107 switching cycles
Electrical service life
at AC 250 V
(ohmic load)
105 switching cycles at 6 A
106 switching cycles at 1 A
107 switching cycles at 0.25 A
at DC 24 V
(ohmic load)
6 × 103 switching cycles at 6 A
106 switching cycles at 3 A
1.5 × 106 switching cycles at 1 A
107 switching cycles at 0.1 A
Terminal data
Cable type
Wire end ferrule
Cable cross−section
Tightening torque
Stripping length
Directly
coupled
to the
mains
2.5 mm2
(AWG 14)
0.5 ... 0.6 Nm
(4.4 ... 5.3 lb−in)
5 mm
Flexible
With plastic sleeve
2.5 mm2
(AWG 14)
C# PDF Convert to Images SDK: Convert PDF to png, gif images in C#
Professional .NET library and Visual C# source code for creating high resolution images from PDF in C#.NET class. Cut and paste any areas in PDF pages to images.
extract photos from pdf; extract jpeg from pdf
VB.NET Create PDF from images Library to convert Jpeg, png images
VB.NET Guide for Converting Raster Images to PDF File Using VB.NET Sample Code. VB.NET Example of More than Two Images to PDF Conversion. This VB.
pdf extract images; extract vector image from pdf
Safety engineering
Safety relay K
SR
14
496
EDS82EV903  EN  3.0
Wiring
Danger!
Faulty operation in case of earth faults possible
The correct functioning of the safety function is not ensured if an earth fault
occurs.
Possible consequences:
ƒ
A failure of the safety function can lead to death, severe injuries or damage
to material.
Protective measures:
The electrical reference point for the coil of the safety relay K
SR
must be
connected to the PE conductor system (EN 60204−1, paragraph 9.4.3)!
Danger!
Danger to life through improper installation
Improper installation of the safety engineering systems may cause an
uncontrolled starting action of the drives.
Possible consequences:
ƒ
Death, severe injuries, or damage to material assets during an uncontrolled
starting action of the drives.
Protective measures:
ƒ
Shielded installation of all control cables connected to the FIF module is
essential to reduce interference injection.
ƒ
Apply the shield to a large surface of the EMC sheet.
Safety engineering
Safety relay K
SR
14
497
EDS82EV903   EN   3.0
8200 vector 3 ... 11 kW
X3.1
KSR
IGBT
+5V
+
34
28
33
Ax
X3.1
CINH
Z1
8200vector
K32K31
DC+24V
&
µC
...
...
...
8200vec266
Fig. 14−2
Connection of safety relay K
SR
Z1
Standard I/O or application I/O
CINH
Controller inhibit
IGBT
Power output stage
Function
Relay position switched
X3.1/34
Control for safety relay K
SR
X3.1/33
X3.1/K32
Feedback contact K
SR
opened
X3.1/K31
28
Controller inhibit input (CINH)
Ax
Digital output for optional "Controller
inhibit" feedback
8200 vector 15 ... 90 kW
K
SR
K32
K31
33
34
K
SR
IGBT
+5V
+
34
28
33
Ax
X3.1
Z1
8200vector
K32
K31
DC+24V
&
µC
...
...
...
CINH
8200vec266
Fig. 14−3
Connection of safety relay K
SR
Z1
Standard I/O or application I/O
CINH
Controller inhibit
IGBT
Power output stage
Function
Relay position switched
X3.1/34
Control for safety relay K
SR
X3.1/33
X3.1/K32
Feedback contact K
SR
opened
X3.1/K31
28
Controller inhibit input (CINH)
Ax
Digital output for optional "Controller
inhibit" feedback
Safety engineering
Functional test
Important notes
14
498
EDS82EV903  EN  3.0
14.4
Functional test
14.4.1
Important notes
Danger!
Unexpected start−up of the machine possible
The "Safe torque off" safety function provides protection against an
unexpected start−up of the drive and therefore is an important item within the
safety concept for a machine. It has to be ensured that this function works
correctly.
Possible consequences:
ƒ
Death, severe injury, or damage to material assets, when the safety function
fails.
Protective measures:
After the installation and at regular intervals, the operator has to check the
function of the "Safe torque off" circuit.
ƒ
When doing this, check both disconnecting paths separately with regard to
their disconnection capability.
ƒ
The functional test can be carried out manually or automatically via the PLC.
ƒ
Basically the inspection interval depends on the application and the
corresponding risk analysis, as well as on the system as a whole. It should
not exceed 1 year.
ƒ
If the functional test shows impermissible states,
–the drive or the machine has to be shut down immediately.
–commissioning is not permitted until the safety function operates
correctly.
Safety engineering
Functional test
Manual safety function check
14
499
EDS82EV903   EN   3.0
14.4.2
Manual safety function check
For the functional test, check both disconnecting paths separately.
1st disconnecting path: pulse inhibit via safety relay K
SR
How to proceed during the test:
1. Alternately apply LOW and HIGH level to input X3.1/34 and check the states given in
the table below.
Individual test
Specification
Correct status
Relay control input (X3.1/34)
Feedback output (X3.1/K31)
Pulse inhibit
LOW
HIGH
Pulse enable
HIGH
LOW
The individual tests are passed if the correct states given in the table result.
2nd disconnecting path: controller inihibit
Requirement for the test:
ƒ
"Quick stop" function (QSP) deactivated
ƒ
"Automatic DC injection brake" function deactivated (C0019 = 0.00)
ƒ
Pulses enabled by safety relay K
SR
(X3.1/34 = HIGH)
How to proceed during the test:
1. Set controller inhibit (X3/28 = LOW).
2. Define a setpoint n
set
> 0.
3. Check that the motor is not rotating.
The individual test is passed if the motor does not rotate.
Functional test not passed
If an individual test results in an impermissible status, the functional test is not passed.
ƒ
The drive or machine has to be shut down immediately.
ƒ
Commissioning is not permitted until the safety function operates correctly.
Safety engineering
Functional test
Monitoring the safety function with a PLC
14
500
EDS82EV903  EN  3.0
14.4.3
Monitoring the safety function with a PLC
K
SR
µC
PWM
PWM
CINH
DIGOUT
DC 24V
Z2
Z1
8200vector
S1
S2
IN 1
IN2
IN3
IN4
34
X3.1
33
K32
K31
28
Ax
&
8200vec111
Fig. 14−4
Circuit diagram for monitoring the safety function with a PLC
S1, S2
Separate options for disconnecting the two disconnecting paths
K
SR
Safety relay
X3.1/34
Control of safety relay
X3.1/33
Control of safety relay (GND)
X3.1/K32 Positively driven feedback contact (24 V)
X3.2/K31 Positively driven feedback contact
Z1
Standard I/O or application I/O
Ax
Digital output for motor current evaluation
CINH
Controller inhibit
Z2
Programmable logic controller (PLC)
IN 1 − 4
Digital inputs
Requirements
The following conditions must be met:
ƒ
The PLC must be programmed such that the complete system is set to a safe state
immediately when the function check leads to an impermissible state.
ƒ
The parameter setting of a digital output must be such that you can conclude to the
output current I
motor
of the drive (see parameterisation example).