CREADREG
33002515 07/2012
121
Mode of Functioning
Function mode of CREADREG blocks
Although a large number of CREADREG function blocks can be programmed, only 
four read operations may be active at the same time. It makes no difference whether 
these operations are performed using this function block or others (e.g. MBP_MSTR, 
READREG). All function blocks use one data transaction path and require multiple 
cycles to complete a task. 
The complete routing information must be separated into two parts:
z
in the NODEADDR of the destination node (regardless of whether it is located in the 
local segment or in another segment) and 
z
the routing path, in case there is a link via network bridges.
The resulting destination address consists of these two information components.
The routing path is a DINT data type, which is interpreted as a sequence of two-digit 
information units. It is not necessary to use "00" extensions (e.g. both routing paths 
4711 and 47110000 are valid, for NODEADDR 34 the result is destination address 
47.11.34.00.00).
NOTE: This function block puts a heavy load on the network. The network load must 
therefore be carefully monitored. If the network load is too high, the program logic 
should be reorganized to work with the READREG function block, which is a variant 
of this function block that does not operate in continuous mode, but is command 
driven.
Add text pdf reader - insert text into PDF content in C#.net, ASP.NET, MVC, Ajax, WinForms, WPF
XDoc.PDF for .NET, providing C# demo code for inserting text to PDF file
how to add text to a pdf file in reader; adding text to pdf in preview
Add text pdf reader - VB.NET PDF insert text library: insert text into PDF content in vb.net, ASP.NET, MVC, Ajax, WinForms, WPF
Providing Demo Code for Adding and Inserting Text to PDF File Page in VB.NET Program
add text box in pdf; add text in pdf file online
CREADREG
122
33002515 07/2012
Parameter description
NODEADDR
Identifies the node address within the target segment.
The parameter can be entered as an address, located variable, unlocated variable 
or literal.
ROUTPATH
Identifies the routing path to the target segment. The two-digit information units run 
from 01 64 (see Mode of Functioning, page 121). If the slave resides in the local 
network segment, ROUTPATH must be set to "0" or must be left unconnected.
The parameter can be entered as an address, located variable, unlocated variable 
or literal.
SLAVEREG
Start of the area in the addressed slave from which the source data are read. The 
source area always resides within the 4x register area. SLAVEREG expects the 
source reference as offset within the 4x area. The leading "4" must be omitted (e.g. 
59 (contents of the variables or value of the literal) = 40059).
The parameter can be entered as an address, located variable, unlocated variable 
or literal.
NO_REG
Number of registers to be read from slave processor (1 ... 100).
The parameter can be entered as an address, located variable, unlocated variable 
or literal.
STATUS
Error code, see Modbus Plus Error Codes, page 123
The parameter can be specified as an address, located variable or unlocated 
variable.
REG_READ
An ANY_ARRAY_WORD that is the same size as the requested transmission must be 
agreed upon (≥ NO_REG) for this parameter. The name of this array is defined as a 
parameter. If the array is defined too small, then only the amount of data is 
transmitted that is present in the array.
The parameter must be defined as a located variable.
C# PDF insert image Library: insert images into PDF in C#.net, ASP
inserting image to PDF in preview without adobe PDF reader installed. Insert images into PDF form field. How to insert and add image, picture, digital photo
adding text to a pdf document acrobat; how to add text fields to a pdf
VB.NET PDF Text Extract Library: extract text content from PDF
With this advanced PDF Add-On, developers are able to extract target text content from source PDF document and save extracted text to other file formats
how to add text to a pdf document using acrobat; add text block to pdf
CREADREG
33002515 07/2012
123
Modbus Plus Error Codes
Form of the function error code
The form of the function error code for Modbus Plus is Mmss, which includes:
z
M is the high code
z
m is the low code
z
ss is a subcode
Hexadecimal error code
Hexadecimal error code for Modbus Plus:
Hex. Error 
Code
Meaning
1001
Abort by user
2001
An operation type that is not supported was specified in the control block
2002
One or more control block parameters were modified while the MSTR element 
was active (this only applies to operations which require several cycles for 
completion). Control block parameters my only be modified in inactive MSTR 
components.
2003
Illegal value in the length field of the control block
2004
Illegal value in the offset field of the control block
2005
Illegal value in the length and offset fields of the control block
2006
Unauthorized data field on slave
2007
Unauthorized network field on slave
2008
Unauthorized network routing path on slave
2009
Routing path equivalent to own address
200A
Attempting to retrieve more global data words than available
30ss
Unusual response by Modbus slave (see page124)
4001
Inconsistent response by Modbus slave
5001
Inconsistent response by network
6mss
Routing path error (see page124)
Subfield m shows where the error occurred (a 0 value means local node, 2 
means 2nd device in route, etc) .
VB.NET PDF insert image library: insert images into PDF in vb.net
try with this sample VB.NET code to add an image As String = Program.RootPath + "\\" 1.pdf" Dim doc New PDFDocument(inputFilePath) ' Get a text manager from
add text to pdf in acrobat; adding text pdf file
VB.NET PDF Password Library: add, remove, edit PDF file password
VB: Add Password to PDF with Permission Settings Applied. This VB.NET example shows how to add PDF file password with access permission setting.
adding text field to pdf; adding text pdf files
CREADREG
124
33002515 07/2012
ss hexadecimal value in 30ss error code
ss hexadecimal value in 30ss error code:
ss hexadecimal value in 6mss error code
NOTE: Subfield m in error code 6mss is an Index in the routing information that 
shows where an error has been detected (a 0 value indicates the local node, 2 
means the second device in the route, etc.). 
The ss subfield in error code 6mss is as follows:
ss hex. Value Meaning
01
Slave does not support requested operation
02
Non-existent slave registers were requested
03
An unauthorized data value was requested
05
Slave has accepted a lengthy program command
06
Function cannot currently be carried out: lengthy command running
07
Slave has rejected lengthy program command
ss hexadecimal value
Meaning
01
No response receipt
02
Access to program denied
03
Node out of service and unable to communicate
04
Unusual response received
05
Router-node data path busy
06
Slave out of order
07
Wrong destination address
08
Unauthorized node type in routing path
10
Slave has rejected the command
20
Slave has lost an activated transaction
40
Unexpected master output path received
80
Unexpected response received
F001
Wrong destination node specified for MSTR operation
C# PDF Text Extract Library: extract text content from PDF file in
How to C#: Extract Text Content from PDF File. Add necessary references: RasterEdge.Imaging.Basic.dll. RasterEdge.Imaging.Basic.Codec.dll.
how to add a text box in a pdf file; add text to pdf acrobat
C# PDF Password Library: add, remove, edit PDF file password in C#
C# Sample Code: Add Password to PDF with Permission Settings Applied in C#.NET. This example shows how to add PDF file password with access permission setting.
how to add text to pdf file with reader; adding text to pdf file
33002515 07/2012
125
9
Unity Pro
CWRITEREG
33002515 07/2012
CWRITREG: Continuous register 
writing
Introduction
This chapter describes the CWRITREG block.
What Is in This Chapter?
This chapter contains the following topics:
Topic
Page
Description
126
Mode of Functioning
129
Parameter description
130
VB.NET PDF Text Add Library: add, delete, edit PDF text in vb.net
Read: PDF Image Extract; VB.NET Write: Insert text into PDF; Add Image to PDF; VB.NET Protect: Add Password to VB.NET Annotate: PDF Markup & Drawing. XDoc.Word
how to enter text in pdf form; adding text to pdf online
C# PDF Text Add Library: add, delete, edit PDF text in C#.net, ASP
Read: PDF Image Extract; VB.NET Write: Insert text into PDF; Add Image to PDF; VB.NET Protect: Add Password to VB.NET Annotate: PDF Markup & Drawing. XDoc.Word
add editable text box to pdf; adding text to pdf
CWRITEREG
126
33002515 07/2012
Description
Function description
This derived function block writes continuously to the register area. It transfers data 
from the PLC via Modbus Plus to a specified slave destination processor.
EN and ENO can be configured as additional parameters.
NOTE: When programming a CWRITREG function, you must be familiar with the 
routing procedures used by your network. Modbus Plus routing path structures will 
be described in detail in "Modbus Plus Network Planning and Installation Guide".
NOTE: This function block only supports the local Modbus Plus interface (no NOM).
If using a NOM please work with the CWRITE_REG block from the communication 
block library.
NOTE: This function block does not support TCP/IP- or SY/MAX-Ethernet. 
If TCP/IP- or SY/MAX-Ethernet is needed, please use the CWRITE_REG block from 
the communication block library.
NOTE: Several copies of this function block can be used in the program. However, 
multiple instancing of these copies is not possible.
Representation in FBD
Representation:
VB.NET PDF Text Box Edit Library: add, delete, update PDF text box
Read: PDF Image Extract; VB.NET Write: Insert text into PDF; Add Image to PDF; VB.NET Protect: Add Password to VB.NET Annotate: PDF Markup & Drawing. XDoc.Word
how to insert text into a pdf using reader; how to insert text in pdf using preview
CWRITEREG
33002515 07/2012
127
Representation in LD
Representation:
Representation in IL
Representation:
CAL CWRITREG_Instance (NODEADDR:=DeviceAddress,
ROUTPATH:=RoutingPath, SLAVEREG:=OffsetAddress,
NO_REG:=NumberOfRegisters, 
REG_WRIT:=SourceDataArea,
STATUS=>ErrorCode)
Representation in ST
Representation:
CWRITREG_Instance (NODEADDR:=DeviceAddress,
ROUTPATH:=RoutingPath, SLAVEREG:=OffsetAddress,
NO_REG:=NumberOfRegisters, 
REG_WRIT:=SourceDataArea,
STATUS=>ErrorCode) ;
CWRITEREG
128
33002515 07/2012
Parameter description
Description of the input parameters:
Description of input / output parameters:
Description of the output parameters:
Parameters
Data type
Meaning
NODEADDR
INT
Device address within the target segment
ROUTPATH
DINT
Routing path to target segment
SLAVEREG
DINT
Offset address of the first 4x register in the slave to 
be written to
NO_REG
INT
Number of registers to be written from slave
Parameters
Data type
Meaning
REG_WRIT
ANY_ARRAY_WORD
Source data field
(A data structure must be declared as a located 
variable for the source file.)
Parameters
Data type
Meaning
STATUS
WORD
Error Code
CWRITEREG
33002515 07/2012
129
Mode of Functioning
Function mode of CWRITREG blocks
Although an unlimited number of CWRITREG function blocks can be programmed, 
only four write operations may be active at the same time. It makes no difference 
whether these operations are performed using this function block or others (e.g. 
MBP_MSTR, WRITEREG). All function blocks use one data transaction path and 
require multiple cycles to complete a task.
If several CWRITREG function blocks are used within an application, they must at 
least differ in the values of their NO_REG or REG_WRIT parameters.
The complete routing information must be separated into two parts:
z
in the NODEADDR of the destination node (regardless of whether it is located in the 
local segment or in another segment) and 
z
the routing path, in case there is a link via network bridges.
The resulting destination address consists of these two information components.
The routing path is a DINT data type, which is interpreted as a sequence of two-digit 
information units. It is not necessary to use "00" extensions (e.g. both routing paths 
4711 and 47110000 are valid, for NODEADDR 34 the result is destination address 
47.11.34.00.00).
NOTE: This function block puts a heavy load on the network. The network load must 
therefore be carefully monitored. If the network load is too high, the program logic 
should be reorganized to work with the WRITEREG function block, which is a variant 
of this function block that does not operate in continuous mode, but is command 
driven.
CWRITEREG
130
33002515 07/2012
Parameter description
NODEADDR
Identifies the node address within the target segment.
The parameter can be specified as an address, located variable, unlocated variable 
or literal.
ROUTPATH
Identifies the routing path to the target segment. The two-digit information units run 
from 01 64 (see Mode of Functioning, page 129). If the slave resides in the local 
network segment, ROUTPATH must be set to "0" or must be left unconnected.
The parameter can be specified as an address, located variable, unlocated variable 
or literal.
SLAVEREG
Start of the destination area in the addressed slave to which the source data are 
written. The destination area always resides within the 4x register area. SLAVEREG 
expects the destination address as an offset within the 4x area. The leading "4" must 
be omitted (e.g. 59 (contents of the variables or value of the literal) = 40059).
The parameter can be entered as an address, located variable, unlocated variable 
or literal.
NO_REG
Number of registers to be written to slave processor (1 ... 100).
The parameter can be specified as an address, located variable, unlocated variable 
or literal.
REG_WRIT
An ANY_ARRAY_WORD that is the same size as the planned transmission must be 
agreed upon (≥ NO_REG) for this parameter. The name of this array is defined as a 
parameter. If the array is defined too small, then only the amount of data is 
transmitted that is present in the array.
The parameter must be defined as a located variable.
STATUS
If MSTR error code is returned, see Modbus Plus Error Codes, page 123
The parameter can be specified as an address, located variable or unlocated 
variable.