Safety Manual 
9116 UniverSal converter
 assumptions and restrictions for use of the product
4.1 
Basic safety specifications
Operational temperature range................ -20...+60°C
Storage temperature range...................... -20...+85°C
Power supply type, min. .......................... Double or reinforced
Supply voltage ......................................... 19.2...31.2 VDC
Relay output pulse length, min. ............... 70 ms
Loop supply  ............................................ >16.5 V @ 20 mA
External loop supply voltage ................... 5...26 VDC + external drop
(Passive output)
Mounting area .......................................... Zone 2 / Division 2 or safe area
Mounting environment ............................. Pollution degree 2 or better
4.2 
Safety accuracy
The analogue output and relay output corresponds to the applied input within the 
safety accuracy.
Safety accuracy ....................................... ±2%
4.2.1  minimum span
For temperature measurements, the selected range (OUT.HI - OUT.LO), and for 
linear resistance measurements the selected range (R 100% - R 0%), shall be 
larger or equal to the values below:
4.2.2  Range limitations
TC type B shall not be used below +400°C
4.3 
associated equipment
4.3.1  RtD or linear resistance sensor wiring
If a 2-wire or a 3-wire connection for RTD or linear resistance is selected, 
Input 
type
minimum span for safety 
accuracy
Pt100, Pt200, Pt1000
28°C
Pt500, Ni100, Ni120, Ni1000
43°C
Pt50, Pt400, Ni50
57°C
Pt250, Pt300
85°C
Pt20
142°C
Pt10
283°C
TC: E, J, K, L, N, T, U
91°C
TC: B, R, S, W3, W5, LR
153°C
Linear resistance, R 100% ≤ 800 W
53 W
Linear resistance, R 100% > 800 W
667 W
How to add text to pdf file - insert text into PDF content in C#.net, ASP.NET, MVC, Ajax, WinForms, WPF
XDoc.PDF for .NET, providing C# demo code for inserting text to PDF file
adding text to a pdf in reader; adding text to pdf online
How to add text to pdf file - VB.NET PDF insert text library: insert text into PDF content in vb.net, ASP.NET, MVC, Ajax, WinForms, WPF
Providing Demo Code for Adding and Inserting Text to PDF File Page in VB.NET Program
add text pdf reader; add text to pdf document in preview
Version No. V3R0
5
9116 Universal converter 
safety Manual
the end user must ensure that the applied sensor wiring does not introduce 
failures exceeding the requirements for the safety application.
4.3.2  Sensor errors
If the loop supply is used to supply a current input signal, the sensor error 
indication shall be enabled on the safety output(s).
If sensor error detection is disabled, or if any of the conficurations below 
are used, the user must ensure that the applied sensor, including wiring, 
has a failure rate that qualifies it for the safety application without sensor 
error detection enabled:
•  Input is current, 0-20 mA
•  Input is voltage
•  Input is linear resistance and R_0% < 18 W (no short circuit detection)
•  Input it Pt10, Pt20 or Pt50 (no short circuit detection)
•  Input is potentiometer (no short circuit detection on arm)
4.3.3  Process calibration
If a process calibration is taken into SIL-mode operation, it is mandatory 
that the accuracy of the device (and sensor, if applicable) are tested by the 
end user after SIL-mode is entered, in addition to the normal functional 
test. Refer to section 14 - Safe parameterisation - user responsibility.
4.3.4  analogue output
The connected safety PLC shall be able to detect and handle the fault 
indications on the analogue output of the 9116 converter by having a 
NAMUR NE43-compliant current input.
4.3.5  Relay output
The relay output shall only be connected to equiment which has a current 
limiting function of 2 A.
4.4 
failure rates
The basic failure rates from the Siemens standard SN 29500 are used as the failure 
rate database.
Failure rates are constant, wear-out mechanisms are not included.
External power supply failure rates are not included.
4.5 
Safe parameterisation
The  user  is  responsible  for  verifying  the  correctness  of  the  configuration 
parameters. (See section 14 Safe parameterisation - user responsibility).
Manual override may not be used for safety applications.
4.6 
Installation in hazardous areas
The  IECEx  Installation  drawing,  ATEX Installation  drawing  and FM Installation 
drawing shall be followed if the products are installed in hazardous areas.
 functional specification of the safety function
Conversion of current signals (0...20 mA or 4...20 mA), voltage signals, potentiometer, linear 
resistance, RTD sensor signals or thermocouple sensor signals from hazardous areas to a 
4...20 mA current output signal, and/or an output relay, within specified accuracy.
VB.NET PDF Password Library: add, remove, edit PDF file password
This VB.NET example shows how to add PDF file password with access permission setting. passwordSetting.IsAssemble = True ' Add password to PDF file.
adding text to a pdf in preview; how to insert text into a pdf using reader
C# PDF Password Library: add, remove, edit PDF file password in C#
This example shows how to add PDF file password with access permission setting. passwordSetting.IsAssemble = true; // Add password to PDF file.
adding text field to pdf; how to add text to pdf file
Version No. V3R0
Safety Manual 
9116 UniverSal converter
For RTD and linear resistance input  sensors, cable resistances of up to 50 W per wire can be 
compensated if 3- or 4-wire connection is configured.
For thermocouple sensors, cold junction temperature errors can be compensated, either by an 
internally mounted temperature sensor, or by an accessory connector with a built-in temperature 
sensor. The selection of CJC measurement must be done and verified by the end user.
 functional specification of the non-safety functions
The status relay (terminal 33 and 34), error signal on power rail (terminal 91) and LED outputs 
are not suitable for use in any Safety Instrumented Function.
 Safety parameters
RTD, TC, LinR and Potentiometer input, Current output
Probability of dangerous Failure per Hour (PFH)
4.30E-08
Note
1
Probability of failure on demand (PFD) -  
1 year proof test interval
2.82E-04
Proof test interval (10% of loop PFD)
4 years
Safe Failure Fraction 
93%
RTD, TC, LinR and Potentiometer input, Relay output
Probability of dangerous Failure per Hour (PFH)
6.20E-08
Note1
Probability of failure on demand (PFD) -  
1 year proof test interval
4.03E-04
Proof test interval (10% of loop PFD)
3 years
Safe Failure Fraction 
90%
Voltage input, Current output
Probability of dangerous Failure per Hour (PFH)
5.60E-08
Note1
Probability of failure on demand (PFD) -  
1 year proof test interval
3.66E-04
Proof test interval (10% of loop PFD)
3 years
Safe Failure Fraction 
93%
Voltage input, Relay output
Probability of dangerous Failure per Hour (PFH)
7.60E-08
Note1
Probability of failure on demand (PFD) -  
1 year proof test interval
4.89E-04
Proof test interval (10% of loop PFD)
2 years
Safe Failure Fraction 
91%
C# PDF File & Page Process Library SDK for C#.net, ASP.NET, MVC
Read: PDF Text Extract; C# Read: PDF Image Extract; C# Write: Insert text into PDF; C# Write: Add Image to PDF; C# Protect: Add Password
how to enter text into a pdf; add text boxes to pdf
VB.NET PDF Text Extract Library: extract text content from PDF
this advanced PDF Add-On, developers are able to extract target text content from source PDF document and save extracted text to other file formats through VB
add text field pdf; how to add text to pdf document
Version No. V3R0
7
9116 Universal converter 
safety Manual
Current input, Current output
Probability of dangerous Failure per Hour (PFH)
4.20E-08
Note1
Probability of failure on demand (PFD) -  
1 year proof test interval
2.77E-04
Proof test interval (10% of loop PFD)
5 years
Safe Failure Fraction 
95%
Current input, Relay output
Probability of dangerous Failure per Hour (PFH)
6.20E-08
Note1
Probability of failure on demand (PFD) -  
1 year proof test interval
4.00E-04
Proof test interval (10% of loop PFD)
3 years
Safe Failure Fraction 
93%
Common Safety Parameters
Demand response time
Signal input: < 0.5 seconds 
Potentiometer and linear resistance  
input < 0.65 seconds 
Temperature input: < 1.1 seconds
Demand mode
High
Demand rate
3000 seconds
Mean Time To Repair (MTTR)
24 hours
Diagnostic test interval 
30 seconds
Hardware Fault Tolerance (HFT)
0
Component Type
B
SIL capability
SIL 2
Description of the “Safe State”, analogue output
Output ≤ 3.6 mA or 
Output ≥ 21 mA 
Description of the “Safe State”, relay output
Contact open (relay de-energized)
Relay lifetime (Note
2
)
100 000 times
Note
1
: The 9116 contains no lifetime limiting components, therefore the PFH figures are valid 
for up to 12 years, according to IEC 61508.
Note
2
: The user must calculate the product lifetime with regard to the relay lifetime.
 Hardware and software configuration
All configurations of software and hardware versions are fixed from factory, and cannot be 
changed by end-user or reseller.
This manual only covers products labelled with the product version (or range of versions) 
specified on the front page.
C# PDF Text Extract Library: extract text content from PDF file in
How to C#: Extract Text Content from PDF File. Add necessary references: RasterEdge.Imaging.Basic.dll. RasterEdge.Imaging.Basic.Codec.dll.
adding text pdf file; add text box in pdf
C# PDF insert image Library: insert images into PDF in C#.net, ASP
using RasterEdge.Imaging.Basic; using RasterEdge.XDoc.PDF; Have a try with this sample C#.NET code to add an image to the first page of PDF file.
adding text to pdf form; adding text to pdf in acrobat
Version No. V3R0
Safety Manual 
9116 UniverSal converter
 failure category
failure rates (1/h) for RTD, TC, LinR and Potentiometer input, Current output
Fail Safe Detected
0.000E-0
Fail Safe Undetected
2.78E-07
Fail Dangerous Detected
3.52E-07
Fail Dangerous Undetected
4.30E-08
failure rates (1/h) for RTD, TC, LinR and Potentiometer input, Relay output 
Fail Safe Detected
0.000E-0
Fail Safe Undetected
3.59E-07
Fail Dangerous Detected
2.30E-07
Fail Dangerous Undetected
6.20E-08
failure rates (1/h) for Voltage input, Current output
Fail Safe Detected
0.000E-0
Fail Safe Undetected
3.95E-07
Fail Dangerous Detected
4.79E-07
Fail Dangerous Undetected
5.60E-08
failure rates (1/h) for Voltage input, Relay output 
Fail Safe Detected
0.000E-0
Fail Safe Undetected
4.80E-07
Fail Dangerous Detected
3.53E-07
Fail Dangerous Undetected
7.60E-08
failure rates (1/h) for Current input, Current output
Fail Safe Detected
0.000E-0
Fail Safe Undetected
4.44E-07
Fail Dangerous Detected
5.54E-07
Fail Dangerous Undetected
4.20E-08
failure rates (1/h) for Current input, Relay output
Fail Safe Detected
0.000E-0
Fail Safe Undetected
6.36E-07
Fail Dangerous Detected
3.20E-07
Fail Dangerous Undetected
6.20E-08
VB.NET PDF File Compress Library: Compress reduce PDF size in vb.
Also able to uncompress PDF file in VB.NET programs. Offer flexible and royalty-free developing library license for VB.NET programmers to compress PDF file.
add text boxes to pdf document; how to add text to a pdf document using reader
VB.NET PDF insert image library: insert images into PDF in vb.net
try with this sample VB.NET code to add an image As String = Program.RootPath + "\\" 1.pdf" Dim doc New PDFDocument(inputFilePath) ' Get a text manager from
how to add text box in pdf file; how to insert text in pdf using preview
Version No. V3R0
9
9116 Universal converter 
safety Manual
10  Periodic proof test procedure
This test will detect approximately 95% of possible “du” (dangerous undetected) failures in the 
device. The proof test is equivalent to the functional test.
11  Procedures to repair or replace the product
Any failures that are detected and that compromise functional safety should be reported to the 
sales department at PR electronics A/S.
Repair of the device and replacement of circuit breakers must be done by PR electronics A/S only.
12  maintenance
No maintenance required.
13  Documentation for routing diagram
The routing diagram is shown in section 16.2.
13.1  In general
When configuring the 9116, you will be guided through all parameters and you can 
choose the settings which fit the application. For each menu there is a scrolling help 
text which is automatically shown in line 3 on the display.
Configuration is carried out by use of the 3 function keys:
1 will increase the numerical value or choose the next parameter
2 will decrease the numerical value or choose the previous parameter
3 will accept the chosen value and proceed to the next menu
When configuration is completed, the display will return to the default state 1.0.
Pressing and holding 3 will return to the previous menu or return to the default 
state (1.0) without saving the changed values or parameters.
If no key is activated for 1 minute, the display will return to the default state (1.0) 
without saving the changed values or parameters.
13.2  further explanations
13.2.1  Password protection
Access to the configuration can be blocked by assigning a password. 
The password is saved in the device in order to ensure a high degree of 
protection against unauthorised modifications to the configuration. Default 
password 2008 allows access to all configuration menus.
Password protection is mandatory in SIL applications.
Step
action
1
Bypass the safety PLC or take other appropriate action to avoid a false trip
2
Connect a simulator identical to the input setup
3
Apply input value corresponding to 0/100% output range 
4
Observe whether the outputs acts as expected
5
Restore the input terminals to full operation
6
Remove the bypass from the safety PLC or otherwise restore normal operation
C# PDF File Split Library: Split, seperate PDF into multiple files
page of your defined page number which starts from 0. For example, your original PDF file contains 4 pages. C# DLLs: Split PDF Document. Add necessary references
add text pdf acrobat professional; how to add text field to pdf
VB.NET PDF File Merge Library: Merge, append PDF files in vb.net
by directly tagging the second PDF file to the target one, this PDF file merge function VB.NET Project: DLLs for Merging PDF Documents. Add necessary references
adding text to a pdf; add text field to pdf acrobat
10 
Version No. V3R0
Safety Manual 
9116 UniverSal converter
13.2.2  Sensor/cable fault information via display front 4501
When  the  function  is enabled and supported by  selected input  type, 
sensor or cable faults are displayed as SE.BR (sensor break) or SE.SH 
(cable short-circuited). 
In case of sensor or cable fault the backlight flashes. This can be reset by 
pressing the 3 key. When the sensor or cable fault has been remedied, the 
device will return to normal operation.
13.3  advanced functions (aDV.Set)
The device gives access to a number of advanced functions which can be reached 
by answering “Yes” to the point “ADV.SET”.
13.3.1  memory (mem)
In the memory menu a non-SIL configuration can be either saved or loaded 
from the local memory of the 4501 display unit. Choose SAVE to store the 
current configuration in the 4501 memory. Press LOAD to read a previously 
stored configuration in the 4501 memory and store it in the device. It is only 
possible to load a configuration stored from the same type of device and 
from the same version, or earlier.
13.3.2  Display setup (DISP)
The brightness contrast and the backlight can be adjusted.
Tag number with 5 alphanumerics can be entered.
Functional  readout  in  line  3 of  the  display can  be  selected:  choose 
between readout of output current or tag no. When selecting ”ALT” the 
readout alternates between output current and tag no.
13.3.3  Password (PaSS)
Here you can choose a password between 0000 and 9999 in order to protect 
the device against unauthorised modifications to the configuration. The device 
is delivered default without password.
13.3.4  language (lanG)
In this menu you can choose between 7 different language versions of 
help texts that will appear in the menu. You can choose between UK, DE, 
FR, IT, ES, SE and DK.
13.3.5  Process calibration (Cal)
A process calibration can be made by the end user. A known process 
signal must be applied for both low and high end of the input measurement 
range. The known input of the applied low end signal must be entered 
in the CAL.LO menu and confirmed by pressing OK before removing or 
changing the applied signal to the high end signal. The known input of 
the applied high end signal must be entered in the CAL.HI menu and 
confirmed by pressing OK before removing. It is possible to enable or 
disable the use of the latest process calibration.
13.3.6  Power rail (RaIl)
In this menu it can be chosen if sensor errors  are transmitted to the central 
surveillance in the PR 9410 power control device.
Version No. V3R0
11
9116 Universal converter 
safety Manual
13.3.7  Simulation (SIm)
It is possible to override the actual measured input signal by a simulated 
value. In the REL.SIM menu it is posible to simulate the relay state with out 
affecting the analogue output, by pressing 
1
. Leaving the simulation menus, 
or disconnecting the 4501 device, will disable the simulation mode and bring 
the output back to correspond to the actual measured value. Simulation is 
not possible in SIL-mode.
13.3.8  Safety integrity level (SIl)
See section 14 - Safe parameterisation - user responsibility
14  Safe parameterisation - user responsibility
14.1  Safety-related configuration parameters
14.1.1  Common parameters
Name
Function
IN.TYPE
Selected input type:
TEMP = Temperature
CURR = Current
VOLT = Voltage
LIN.R = Linear resistance 
POTM = Potentiometer
I.RANGE
Selected  fixed  input  range  for  current  measurements  (for 
IN.TYPE = CURR):
0_20 = 0...20 mA (no sensor error detection!)
4_20 = 4...20 mA
V.RANGE
Selected fixed input range for voltage measurements 
(for IN.TYPE = VOLT)
SENSOR
Selected temperature sensor type (for IN.TYPE = TEMP):
TC = Thermocouple
Ni = Ni RTD sensor
Pt = Pt RTD sensor
12 
Version No. V3R0
Safety Manual 
9116 UniverSal converter
Pt.TYPE
Pt sensor type (for SENSOR = Pt):
10 = Pt10
20 = Pt20          (No short circuit detection!)
50 = Pt50
100 = Pt100
200 = Pt200
250 = Pt250
300 = Pt300
400 = Pt400
500 = Pt500
1000 = Pt1000
Ni.TYPE
Ni sensor type (for SENSOR = Ni):
50 = Ni50
100 = Ni100
120 = Ni120
1000 = Ni1000
TC.TYPE
Thermocouple type (for SENSOR = TC):
TC.B = Thermocuple type B
TC.E = Thermocuple type E
TC.J = Thermocuple type J
TC.K = Thermocuple type K
TC.L = Thermocuple type L
TC.N = Thermocuple type N
TC.R = Thermocuple type R
TC.S = Thermocuple type S
TC.T = Thermocuple type T
TC.U = Thermocuple type U
TC.W3 = Thermocuple type W3
TC.W5 = Thermocuple type W5
TC.Lr = Thermocuple type Lr
CJC
CJC type for SENSOR = TC:
INT = Internal CJC sensor measurement
CONN = CJC connector measurement (accessory)
}
Version No. V3R0
13
9116 Universal converter 
safety Manual
CONNEC
Selected sensor connection type for RTD or linear resistance 
measurements (for SENSOR = Ni or Pt or IN.TYPE = LIN.R):
2W = 2-wire 
3W = 3-wire
4W = 4-wire
If 2W or 3W is selected, the end user must ensure that the 
applied sensor wiring does not introduce failures exceeding the 
requirements for the safety application.
R 0%
0% input range for linear resistance measurements 
(for IN.TYPE = LIN.R). 
This value must be < (R 100% - minimum span), refer to 4.2.1
R 100%
100% input range for linear resistance measurements 
(for IN.TYPE = LIN.R)
This value must be > (R 0% + minimum span), refer to 4.2.1
UNIT
Selected temperature unit for IN.TYPE = TEMP
°C = degrees Celsius
°F = degrees Fahrenheit
For IN.TYPE ≠  TEMP  selectable units refer to routing diagram
DISP.LO
0% display value on 4501. Can be used as base for relay 
setpoints (for IN.TYPE ≠ TEMP)
DISP.HI
100% display value on 4501. Can be used as base for relay 
setpoints (for IN.TYPE ≠ TEMP)
NEW.PAS
Password  for  protection  of  the  device  configuration  from 
unauthorized access. Range from 0 to 9999.