Connections                  Chapter 1 
If you are 
And you 
And 
Then 
Uninhibit a module (clear the check box)  No fault occurs 
A connection is made to the module and the module is dynamically reconfigured (if the 
controller is the owner-controller) with the configuration you created for that module. If the 
controller is configured for listen-only, it cannot reconfigure the module. 
Fault occurs 
A connection is not made to the module. The module status information changes to indicate 
the fault condition. 
Follow these steps to inhibit or uninhibit a module from logic. 
1.  Use a Get System Value (GSV) instruction to read the Mode attribute for 
the module. 
2.  To inhibit the module, set bit 2. To uninhibit the module, clear bit 2. 
3.  Use a Set System Value (SSV) instruction to write the Mode attribute back 
to the module. 
Example: 
Inhibit a Connection 
If Module_1_Inhibit = 1, then inhibit the operation of the I/O module named Module_1. 
1.  The GSV instruction sets Module_1_Mode = value of the Mode attribute for the module. 
2.  The OTE instruction sets bit 2 of Module_1_Mode = 1. This means inhibit the connection. 
3.  The SSV instruction sets the Mode attribute for the module = Module_1_Mode. 
Rockwell Automation Publication 1756-PM015F-EN-P – October 2014 
11 
Adding text to a pdf file - insert text into PDF content in C#.net, ASP.NET, MVC, Ajax, WinForms, WPF
XDoc.PDF for .NET, providing C# demo code for inserting text to PDF file
how to insert text box in pdf file; add text to pdf document in preview
Adding text to a pdf file - VB.NET PDF insert text library: insert text into PDF content in vb.net, ASP.NET, MVC, Ajax, WinForms, WPF
Providing Demo Code for Adding and Inserting Text to PDF File Page in VB.NET Program
how to insert text box in pdf document; how to add text to a pdf in preview
Chapter 1                  Connections 
If the controller loses communication with a module, data from that device does 
not update. When this occurs, the logic acts on the data in ways that may or may 
not be correct. You can program the controller to manage faults safely and 
efficiently. 
Outputs respond to the last, non-faulted state of the controlling inputs. To avoid potential injury and 
damage to machinery, make sure this does not create an unsafe operation. Configure critical I/O modules to 
generate a controller major fault when they lose their connections to the controller, or monitor the status of 
I/O modules. 
Example:  Loss of Communication 
Controller B requires data from controller A. If communication fails between the controllers, controller B 
continues to act on the last data that it received from controller A. 
If communication with a device in the I/O configuration of the controller does 
not occur for 100 ms, the communication times out. If this occurs, you have the 
following options. 
If you want the controller to 
Then 
Fault (major fault) 
Configure a major fault to occur on page 13
Continue operating 
Monitor the health of a module on page 13
Manage a connection 
on 
failure 
12 
Rockwell Automation Publication 1756-PM015F-EN-P – October 2014 
VB.NET PDF Library SDK to view, edit, convert, process PDF file
Feel free to define text or images on PDF document and extract accordingly. Capable of adding PDF file navigation features to your VB.NET program.
add text to pdf in acrobat; add text to a pdf document
VB.NET PDF Page Insert Library: insert pages into PDF file in vb.
If you want to read the tutorial of PDF page adding in C# class, we suggest you go to C# Imaging - how to insert a new empty page to PDF file.
adding text box to pdf; how to add text to a pdf file in acrobat
Connections                  Chapter 1 
Configure a major fault to occur 
You can configure modules to generate a major fault in the controller if they lose 
their connection with the controller. This interrupts the execution of logic and 
runs the Controller Fault Handler. If the Controller Fault Handler does not clear 
the fault, the controller shuts down. 
When you select Major Fault On Controller…Run Mode, the controller: 
•  Must be connected to the module during the Program transition to Run 
mode. During the Program to Run mode transition, there can be a 20-
second delay. 
During this delay, the controller makes one attempt to connect to a module. 
If you select Major Fault On Controller…Run Mode and you cannot 
connect during the 20-second delay, a fault occurs because at least one 
required connection is not established before going to Run mode. This is a 
3/23 type fault code. This fault can occur in large systems with networked 
I/O. 
•  Registers a fault if the connection is dropped while in Run mode. A required 
I/O module connection failed, creating a 3/16 type fault. 
For fault codes, see the Logix5000 Controllers Major and Minor Faults 
Programming Manual, publication 1756-PM014 
Monitor the health of a module 
If you do not configure the major fault to occur, you should monitor the module 
status. If a module loses its connection to the controller, outputs go to their 
configured faulted state. The controller and other I/O modules continue to 
operate based on old data from the module. 
Rockwell Automation Publication 1756-PM015F-EN-P – October 2014 
13 
VB.NET PDF Text Box Edit Library: add, delete, update PDF text box
code below to your VB.NET class program for adding text box on Dim outputFilePath As String = Program.RootPath + "\\" Annot_9.pdf" ' open a PDF file Dim doc
add text to pdf document online; adding text to a pdf form
C# PDF Text Box Edit Library: add, delete, update PDF text box in
for adding text box to PDF document in .NET WinForms application. A web based PDF annotation application able to add text box comments to adobe PDF file online
add text boxes to pdf document; how to insert text box on pdf
Chapter 1                  Connections 
If communication with a module times out, the controller produces the following 
warnings. 
•  The I/O status indicator on the front of the controller flashes green. 
•  A Warning ( ) icon shows over the I/O configuration folder and over the 
device that has timed out. 
•  A module fault code is produced, which you can access through: 
•  Module Properties window for the module. 
•  GSV instruction. 
To monitor the health of your connections, use a Get System Value (GSV) 
instruction to monitor the Module object for either the controller or a specific 
module. 
If you want to 
Get this attribute 
Data Type 
Description 
Determine if communication 
has timed out with any 
device 
LEDStatus 
INT 
For efficiency, use a 
DINT as the 
destination data type. 
Current state of the I/O status indicator on the front of the controller. 
You do not enter an instance name with this attribute. This attribute applies to the entire 
collection of modules. 
Value 
Meaning 
Status Indicator off. No Module objects are configured for the controller 
(there are no modules in the I/O Configuration section of the controller 
organizer). 
Flashing red. None of the Module objects are Running. 
Flashing green. At least one Module object is not Running. 
Solid green. All the Module objects are Running. 
Determine if communication 
has timed out with a specific 
device 
FaultCode 
INT 
For efficiency, use a 
DINT as the 
destination data type. 
A number that identifies a module fault, if one occurs. 
In the Instance Name, choose the device whose connection you want to monitor. Make sure 
to assign a name to the device in the I/O Configuration folder of the project. 
If Module_Status is any value other than 4, the controller is not communicating 
with the module. See the following example. 
14 
Rockwell Automation Publication 1756-PM015F-EN-P – October 2014 
C# PDF Annotate Library: Draw, edit PDF annotation, markups in C#.
Provide users with examples for adding text box to PDF and edit font size and color in text box field in C#.NET program. C#.NET: Draw Markups on PDF File.
add text to pdf; adding text to pdf
VB.NET PDF Text Add Library: add, delete, edit PDF text in vb.net
convert PDF to text, C#.NET convert PDF to images, C#.NET PDF file & pages Professional VB.NET Solution for Adding Text Annotation to PDF Page in VB
how to insert text box in pdf; how to enter text in pdf form
Connections                  Chapter 1 
Example: 
This rung checks the status of an I/O connection. The controller checks the entry status of the connection; any value other than 4 indicates that the connection is 
not functioning correctly. When the controller detects an error, the error code and information is trapped, and the controller tries to re-establish the connection. 
Rockwell Automation Publication 1756-PM015F-EN-P – October 2014 
15 
C# PDF Page Insert Library: insert pages into PDF file in C#.net
By using reliable APIs, C# programmers are capable of adding and inserting (empty) PDF page or pages from various file formats, such as PDF, Tiff, Word, Excel
adding text field to pdf; adding text pdf files
C# PDF File & Page Process Library SDK for C#.net, ASP.NET, MVC
VB.NET read PDF, VB.NET convert PDF to text, VB.NET an (empty) page to a PDF and adding empty pages Certainly, random pages can be deleted from PDF file as well
adding text pdf file; how to add text to a pdf file in reader
Chapter 2 
Determine controller memory information 
Depending on your type of controller, the memory of the controller may be 
divided into several areas. 
If you have this controller 
Then it stores this 
In this memory 
1756 ControlLogix 
1756 GuardLogix 
1768 CompactLogix 
1768 Compact GuardLogix 
I/O tags 
I/O memory 
Produced / Consumed tags 
Communication via Message (MSG) instructions 
Communication with workstations 
Communication with polled (OPC/DDE) tags that 
use RSLinx software1 
Tags other than I/O, produced, or consumed tags  Data and logic memory2 
Logic routines 
Communication with polled (OPC/DDE) tags that 
use RSLinx software1 
1769-L2x CompactLogix 
1769-L3x CompactLogix 
FlexLogix 
DriveLogix 
SoftLogix5800 
These controllers do not divide their memory. They store all elements in one 
common memory area. 
(1) To communicate with polled tags, the controller uses both I/O data and logic 
memory. 
(2) 1756-L55M16 controllers have an additional memory section for logic. 
To estimate how much controller memory your project requires, use the Memory 
tab of the Controller Properties dialog box. For each of the memory areas of your 
controller, the dialog box lets you estimate number of bytes of: 
•  Free (unused) memory. 
•  Used memory. 
•  Largest free contiguous block of memory. 
Use the following steps to estimate the controller memory. 
1.  Start the Logix Designer application and open a controller project. 
Introduction 
Estimate memory 
ry 
information offline 
Rockwell Automation Publication 1756-PM015F-EN-P – October 2014 
17 
Chapter 2                  Determine controller memory information 
2.  On the Online toolbar (above the Controller Organizer), click the 
Controller Properties icon. 
3.  On the Controller Properties dialog box, click the Memory tab. 
4.  In the Estimated Data and Logic Memory area, view the memory 
information since the last estimate. 
5.  Click Estimate to re-estimate the amount of controller memory. 
6.  Click OK. 
18 
Rockwell Automation Publication 1756-PM015F-EN-P – October 2014 
Determine controller memory information                  Chapter 2 
When you are online with a controller, the Memory tab shows the actual memory 
usage of the controller. While the controller is running, it uses additional memory 
for communication. The amount of memory the controller needs varies 
depending on the state of the communication. 
The Memory tab of the controller includes a Max Used entry for each type of 
memory. The Max Used values show the peak of memory usage as communication 
occurs. 
Use the following steps to reset memory usage. 
1.  Start the Logix Designer application and open a controller project. 
2.  On the Online toolbar (above the Controller Organizer), click the 
Controller Properties icon. 
3.  On the Controller Properties dialog box, click the Memory tab. 
4.  Click Reset All Max to reset values. 
5.  Click OK. 
View run-time memory 
emory 
information 
Rockwell Automation Publication 1756-PM015F-EN-P – October 2014 
19 
Chapter 2                  Determine controller memory information 
There are several ways to use logic to get memory information. 
• Get memory information from the controller on page 20. 
• Choose the memory information on page 21. 
• Convert INTs to a DINT on page 22. 
Get memory information from the controller 
To get memory information from the controller, execute a Message (MSG) 
instruction. The following table lists configuration information for the 
instruction. 
On this tab 
For this item 
Type or select 
Which means 
Configuration 
Message Type 
CIP Generic 
Execute a Control and Information Protocol command. 
Service Type 
Custom 
Create a CIP Generic message that is not available in the list. 
Service Code 
Read specific information about the controller (GetAttributeList service). 
Class 
72 
Get information from the user memory object. 
Instance 
This object contains one instance. 
Attribute 
Null value. 
Source Element 
source_array of type SINT[12] 
In this element 
Enter 
Which means 
source_array[0] 
Get 5 attributes. 
source_array[1] 
Null value. 
source_array[2] 
Get free memory. 
source_array[3] 
Null value. 
source_array[4] 
Get total memory. 
source_array[5] 
Null value. 
source_array[6] 
Get largest contiguous block of additional free logic memory. 
source_array[7] 
Null value. 
source_array[8] 
Get largest contiguous block of free I/O memory. 
source_array[9] 
Null value. 
source_array[10] 
Get largest contiguous block of free data and logic memory. 
source_array[11] 
Null value. 
Source Length 
12 
Write 12 bytes (12 SINTs). 
Destination 
INT_array of type INT[29] 
Communication 
Path 
1, slot_number_of_controller 
Write Logic to Get Memory 
Information 
20 
Rockwell Automation Publication 1756-PM015F-EN-P – October 2014 
Documents you may be interested
Documents you may be interested