RockwellAutomation Publication 1756-RM085C-EN-P - August 2011
11
Chapter 1
The Documentation Database ASCII Export dialog box appears. 
8. Select the  AB 6200 tab, make your selections, and click OK. 
The Select Export Destination Directory dialog box appears.
9. Under Directories, select the directory where the PC5 or SLC file resides. 
10. Accept the warning about comments and symbols. Click OK.
RSLogix 5 programming software stores PLC-5 programs using RSP file 
extensions. RSLogix 500 programming software stores SLC 500 programs using 
RSS file extensions. 
Export Option 2: Create TXT files and PC5/SLC files for export at the same
time
To create both files for export at the same time, use the following steps.
1. In RSLogix 5 or RSLogix 500, select File>Save As. 
How to insert text in pdf using preview - insert text into PDF content in C#.net, ASP.NET, MVC, Ajax, WinForms, WPF
XDoc.PDF for .NET, providing C# demo code for inserting text to PDF file
how to add text to a pdf file in acrobat; add text to a pdf document
How to insert text in pdf using preview - VB.NET PDF insert text library: insert text into PDF content in vb.net, ASP.NET, MVC, Ajax, WinForms, WPF
Providing Demo Code for Adding and Inserting Text to PDF File Page in VB.NET Program
adding text fields to pdf acrobat; how to enter text in pdf file
12
RockwellAutomation Publication 1756-RM085C-EN-P - August 2011
Chapter1
The Save Program As dialog box appears. The example below shows the 
Save As dialog box from RSLogix 5. 
2. In the Save as type field, select X5 or ACH to activate the “Export 
database” checkbox.
3. Check the “Export database” checkbox.  
4. Under Export file type, select one of the following,  depending on the 
programming software you are using.
• For RSLogix 5, select A.B. 6200
• For RSLogix 500, select A.P. S.
5. In the Save as type field, change the file type fromX5 or ACH to PC5 or 
SLC. Even though the A.B. 6200 format is dimmed, the database will be 
exported in that format. 
6. Click Save. The Export PC5 Format or the Export SLC 500 Format dialog 
box appears.
7. On the export format dialog box, use the following steps.
a. Select Complete Program Save.
b. Select all the export options.
c. Click OK.
How to C#: Preview Document Content Using XDoc.Word
How to C#: Preview Document Content Using XDoc.Word. Overview for How to Use XDoc.Word to preview document content without loading
adding text to pdf; how to add text to a pdf document using acrobat
How to C#: Preview Document Content Using XDoc.PowerPoint
How to C#: Preview Document Content Using XDoc.PowerPoint. Overview for How to Use XDoc.PowerPoint to preview document content without
add text to pdf document online; add text to pdf reader
RockwellAutomation Publication 1756-RM085C-EN-P - August 2011
13
Chapter 1
Using the Translation Tool
Wizard to Convert a PLC-5
or SLC 500 Program
Once you have the ASCII text file of the PLC-5 or SLC 500 program file, you 
can convert the logic to its Logix equivalent. In RSLogix 5000, use the following 
steps.
1. From the File menu, choose Translate PLC-5/SLC 2.0. 
2. The translation wizard appears. Use the wizard to walk through steps 1-5. 
Wizard step 1 notes
• To start, select one of the option buttons.
– For PLC-5 to Logix...button - Select this option to browse for PC5 
files.
– For SLC-500 to Logix...button - Select this option to browse for SLC 
files.
C# PDF Page Insert Library: insert pages into PDF file in C#.net
toolkit allows developers to specify where they want to insert (blank) PDF last page or after any desired page of current PDF document) using C# .NET
how to insert text box in pdf; how to insert text box in pdf document
C# WinForms Viewer: Load, View, Convert, Annotate and Edit PDF
Supported PDF Processing Features by Using RasterEdge WinForms Viewer for C#.NET. Overview. Highlight PDF text. • Add text to PDF document in preview.
add text field pdf; adding text to pdf in reader
14
RockwellAutomation Publication 1756-RM085C-EN-P - August 2011
Chapter1
• To use a different TXT file name than the program file name, clear the 
‘Documentation file(s) associated with the logic file use the same name’ 
checkbox. Browse to the first database file name (TXT). 
• RSLogix 5 or RSLogix 500 can also be launched from the wizard. To do so,  
click the Launch RSLogix 5 or the Launch RSLogix 500 icon at the top of 
the dialog box.  
For this to work, the software must be installed on the same computer as 
the translation tool.
Wizard step 2 notes
• Browse to the RS5000 file you want to create.
• By default, the file name chosen and displayed by the translation tool is the 
same as the RSLogix 5 or RSLogix 500 file. It has an L5K extension and is 
placed in the directory of that file. 
• Select the controller type and version. The version you select must 
correspond to a version of RSLogix 5000 currently installed and supported 
on your computer.
After the translation is completed, you can change the controller type and 
increase the revision, if necessary.
Wizard step 3 notes
Choose from the following translation options.
• Create Alias Tag for existing PLC-5/SLC Physical Addresses
This option creates alias tags for all I/O file addresses. For example, a   
PLC-5 address of  O:1.7 will have an alias tag if O_001_Bit07 created. An  
SLC address of I1.3/2 will have an alias tag of I1_003_Bit02 created. This  
may make mapping legacy I/O data to the Logix platform easier because     
the aliases can be modified to point at the new I/O data without a change    
to the program logic. 
• Create Alias Tag for PLC-5/SLC Symbols
This options creates alias tags for all symbols found in the database files. If 
this option is not selected, the symbols will be added as tag comments to 
the converted legacy types.
C# WPF Viewer: Load, View, Convert, Annotate and Edit PDF
Features about PDF Processing Features by Using RasterEdge WPF Viewer for C#.NET. Overview. Add text to PDF document. • Insert text box to PDF file.
add text boxes to pdf document; adding text to a pdf in acrobat
How to C#: Preview Document Content Using XDoc.excel
How to C#: Preview Document Content Using XDoc.Excel. Overview for How to Use XDoc.Excel to preview document content without loading
add editable text box to pdf; add text box to pdf file
RockwellAutomation Publication 1756-RM085C-EN-P - August 2011
15
Chapter 1
See 
Co
n
v
e
r
t
i
n
g S
y
mb
o
ls in Chapter 3 for details on how symbols are 
treated.
Wizard step 4 notes
• Click Translate. Since every PLC-5 and SLC500 application is unique, 
there may be syntax errors.
• If there are any syntax errors during translation, the Syntax Error dialog 
box appears showing the line at which the syntax error occurred. You can 
elect to do any of the actions that follow:
– Edit the error immediately at this dialog box and then click Save & 
Retry to restart the translation. 
– Examine the original application to decide if the area where the syntax 
error is occurring is something that can be deleted permanently or if it is 
something that can be removed and then later be recreated in RSLogix 
5000. 
– Edit the PC5, SLC, and TXT files using Notepad.
– Review the table that follows for the most common syntax errors and 
their descriptions.  
Common Syntax Errors
The translation tool may run into syntax errors within the program and database 
files. If so, you must correct those errors so that the translation tool can continue 
the conversion. To understand more common errors, see the table that follows.
Syntax Error
Description
How toFix the Error
Invalid symbolname
The translation toolexpectsthe symbol
namesto be alphanumeric.
RSLogix5 and RSLogix500 software
enforce theserules,but using the 6200
software or manuallyediting the
database filesmaycause these rulesto
be broken.
Search for symbol names
that are not alphanumeric.
"(quote) within a "(quote) Quotesare used todenote the startand
end of stringvaluesor rung/instruction/
addresscomments.
If a rung/instruction/addresscomment
containsa quote,thetranslation tool
doesn’t know thatit isn’t theend of the
string.
Eitherremovethequote or
make it a double quote
("").The translation tool
will translate the double
quote asa single quote
within RSLogix5000.
C# PDF insert image Library: insert images into PDF in C#.net, ASP
How to insert and add image, picture, digital photo from RasterEdge.com, this C#.NET PDF image adding Using this C# .NET image adding library control for PDF
how to add text to pdf document; add text pdf professional
VB.NET PDF insert image library: insert images into PDF in vb.net
Insert Image to PDF Page Using VB. inputFilePath As String = Program.RootPath + "\\" 1.pdf" Dim doc New PDFDocument(inputFilePath) ' Get a text manager from
add text boxes to pdf; how to add text to a pdf document using reader
16
RockwellAutomation Publication 1756-RM085C-EN-P - August 2011
Chapter1
Wizard step 4 notes continued...
• Once all the syntax errors are corrected and the translation is finished,  
click Launch RSLogic 5000.    
• After selecting the name, location, and revision number of the project file 
on the Save Imported Project As dialog box, click Import.  
• If  RSLogix 5000 version(v)17 software generates the following import 
error, use the steps that follow to resolve the error. 
"MSG configuration incomplete because no local tag is specified"
a. Restart the translation tool and select v16 as the Logix controller 
revision.
b. After the application is imported successfully into RSLogix 5000 
version 16 software, change the controller revision to v17. 
c. Continue with the translation.
• Once the files have finished importing, RSLogix 5000 opens and the 
bottom of the screen displays the results. Double click on the errors in the 
results window to locate the PCE (Possible Conversion Error) messages 
that the translation tool inserted within the rungs. 
Wizard step 5 notes
Once you have gone through the steps using the translation wizard, click Finish 
to close the translation tool. Continue with the rest of the conversion steps   
starting with analyzing and resolving PCE instructions.
%within a %
%charactersare used to denote the
start and end of comments within the
program file and occasionally in
database files.
This type of comment isignored by the
translation tool.If a comment contains
another %, the translation tool doesn’t
know that it isn’t the end of the
comment.
Remove the extra % or
make it a double %. The
translation toolwill treat
the double %% as
consecutive comments.
Errant characters
Theprogramordatabasefilecontainsa
randomcharacter or two that doesnot
fit the syntaxof the program or
database files. Thisismore common
with manually-edited filesthan a direct
export from RSLogix5 or RSLogix500.
Remove the errant
characters.
Invalid rung syntax
The rung has invalid syntax,such as
unmatched parentheses.
Checkand fixthe rung
syntax.
Syntax Error
Description
How to Fix the Error
RockwellAutomation Publication 1756-RM085C-EN-P - August 2011
17
Chapter 1
Working with PCE
Instructions
The translation tool inserts a Possible Conversion Error (PCE) instruction  
within the appropriate ladder rung to help you identify possible errors with the 
conversion.  To complete the conversion process, you will want to locate, analyze, 
and fix a discrepancies using the PCE instructions.
For a list of PCE instruction errors, see 
A
p
p
e
nd
ix 
A P
r
o
g
r
a
m
m
i
n
g Co
n
v
e
rsio
E
r
r
o
rs (P
C
E) M
es
sa
g
es
Recognizing the instructions
Text is appended to the rung comments that have the PCE instruction. The 
message text begins with asterisks(*) and the words “Generated by Translation 
Tool”, and ends with asterisks.
An example of a PCE instruction follows:
*** Generated by Translation Tool: Source and destination types may differ *** ";
N: PCE(120, PCE011) COP(I1_008, N23[0], 4);
Locating PCE instructions
You can also locate all of the PCE instructions by verifying the logic. The 
Verify>Controller task compiles the Logix program and checks for errors. This is 
an easy way to see where all the PCE instructions are because the error checking 
will point them out. To locate the PCE instructions, use the following steps.
1. From the Logic menu, choose Verify> Controller. 
The bottom of the screen displays results.
18
RockwellAutomation Publication 1756-RM085C-EN-P - August 2011
Chapter1
2.  Double-click the error shown in the error window to go directly to the 
rung where the error resides.
Resolving PCE Instructions
Once you import the converted Logix project, find each PCE instruction. A PCE 
instruction highlights a possible conversion error. Delete each PCE instruction 
and replace it with the appropriate, corrected logic.
Working with UNK
Instructions
The translation tool converts some PLC-5 and SLC 500 instructions that have 
no equivalent in the Logix architecture. Once you import these instructions into 
the Logix project, they appear as UNK instructions. You must delete each UNK 
instructions and replace it with the appropriate corrected logic.
Configuring the Controller
and Chassis
Once you have resolved any errors,  continue the conversion process by  using  the 
Controller Properties dialog box  in RSLogix 5000 to assign the chassis size and 
slot number of the controller. Use the steps that follow. 
1. Place the cursor over the Controller folder to specify the I/O modules. 
.
2. Select Properties. The Controller Properties dialog box appears.
RockwellAutomation Publication 1756-RM085C-EN-P - August 2011
19
Chapter 1
3. Configure the controller by specifying the slot number of the controller 
and the chassis size.
4. Click OK. 
5. Continue to use the Controller Organizer to specify the I/O modules and 
other devices for the controller. The example that follows shows how to 
specify the I/O module. 
a. Select the I/O Configuration.
b. Right-click and select New Module.
20
RockwellAutomation Publication 1756-RM085C-EN-P - August 2011
Chapter1
Mapping the I/O
The file structure in a Logix controller is tag-based. To facilitate the conversion, 
the translation tool creates tags and arrays of tags to align and map the PLC-5 
files. For example:   
The tags created for physical I/O (For example,  I.2) are empty at the end of the 
conversion process. 
• To continue with the conversion process,  use the RSLogix 5000 
programming software to add all the I/O modules to the tree structure for 
a Logix controller.  
• Then, program instructions to map the Logix I/O tags to the 
converted tags.
– For example, if you add a 16-point input module in slot 2 of the local 
chassis, the programming software creates these I/O tag structures:
Local:1.C (configuration information)
Local:1.Data (fault and input data)
– Use a BTD, MOV, or CPS instructions to map the Local:1.Data word 
into the I2 tag created by the conversion process.
– A MOV instruction moves one element at a time. A BTD instruction 
moves a group of bits, which lets you account for the offset in the 
starting bit that occurs when you map an INT data type to a DINT 
data type. If consecutive I/O groups map to consecutive elements in an 
array, a CPS instruction is more efficient.
For example, if I:000 through I:007 map to Local:1:I.Data[0] through 
Local:1:I.Data[7], use:
CPS
SourceLocal:1:I.Data[0]
Destination:I[0]
Length:8
– If you use a MOV instruction, do not mix data types. If you mix data 
types, the conversion from one data type to another manipulates the 
sign bit, which means you cannot be sure that the high-order bit is set 
properly.
PLC-5 address
Maps to:
N7:500
N7[500]
N17:25
N17[25]
R6:100
R6[100]
I:002
I[2]
O:001
O[1]