RockwellAutomation Publication 1756-RM085C-EN-P - August 2011
21
Chapter 1
See 
C
h
a
pt
e
2 Co
n
v
e
r
t
i
n
g P
r
o
g
r
a
m S
t
r
uct
u
r
e for more information about how 
the translation tool converts the PLC-5 or SLC 500 data table.
Completing the MSG
Configuration
The translation tool only partially converts MSG instructions. Use the RSLogix 
5000 programming software to configure each MSG instruction by completing 
the information on the Communication tab.
Other Considerations
The following are additional issues to keep in mind:
• The time base for instructions is fixed at 1 msec for a Logix controller.   
The conversion process scales PLC-5 and SLC 500  presets and 
accumulators accordingly. For example, a PLC-5  with a time base of 0.01 
sec and a preset of 20 is converted to a time base of 1 msec and a preset of 
200.
• Instruction comments are not converted.
• A Logix controller is a 32-bit based controller. This means that most of the 
Logix instructions use 32-bit words, as opposed to the 16-bit words in 
PLC-5 processors. This might mean that instructions that use masks 
might work differently after the conversion.
IMPORTANT
For more informationabout configuring MSG instructions, seethe
Logix5000 Instruction Set Reference Manual, publication
1756-
RM003.
This manual is available in PDF format on theRSLogix 5000
programmingsoftware CDROM.
How to insert text box in pdf - insert text into PDF content in C#.net, ASP.NET, MVC, Ajax, WinForms, WPF
XDoc.PDF for .NET, providing C# demo code for inserting text to PDF file
add text to pdf document in preview; how to add text to a pdf file in reader
How to insert text box in pdf - VB.NET PDF insert text library: insert text into PDF content in vb.net, ASP.NET, MVC, Ajax, WinForms, WPF
Providing Demo Code for Adding and Inserting Text to PDF File Page in VB.NET Program
how to enter text in a pdf document; add text to pdf
22
RockwellAutomation Publication 1756-RM085C-EN-P - August 2011
Chapter1
• The conversion process creates alias tags for address comments. These 
aliases are then used in place of the converted tags.
Alias tags utilize additional memory in a Logix controller, so you may  
want to delete those alias tags that you do not plan to use. Use the 
RSLogix 5000 programming software to delete aliases after you import the 
project.
VB.NET PDF Text Box Edit Library: add, delete, update PDF text box
Extract Field Data. Data: Auto Fill-in Field Data. Field: Insert, Delete, Update Highlight Text. Add Text. Add Text Box. Drawing Markups. PDF Print. Work with
acrobat add text to pdf; how to add text to pdf file
C# PDF Text Box Edit Library: add, delete, update PDF text box in
C# PDF: Add Text Box. C#.NET PDF SDK - Add Text Box to PDF Page in C#.NET. C# Explanation to How to Add Text Box to PDF Page in C# Project with .NET PDF Library.
add text pdf acrobat; how to add text to a pdf document
RockwellAutomation Publication 1756-RM085C-EN-P - August 2011
23
Chapter
2
Converting Program Structure
Introduction
A Logix 5000 controller uses a different execution model than either the PLC-5 
processor or the SLC 500 processor. The Logix 5000 controller operating system 
is a preemptive multitasking system that is IEC 61131-3 compliant and uses: 
• Tasks 
• Programs 
• Routines
This chapter provides a short description of  the Logix 5000 controller to help 
you better understand the translation results.  
Dividing Logic into Tasks,
Programs, and Routines
The tasks, programs, and routines work together as follows: 
• Tasks: Tasks are used to configure controller execution. A task provides 
scheduling and priority information for a set of one or more programs. You 
can configure tasks as either continuous, periodic, or event tasks.
• Programs: Programs are used to group data and logic. A task contains 
programs, each with its own routines and program-scoped tags. Once a 
task is triggered (activated), all the programs assigned to the task execute in 
the order in which they are listed in the Controller Organizer
Programs are useful for projects developed by multiple programmers. 
During development, the code in one program that makes use of program-
scoped tags, can be duplicated in a second program, which minimizes the 
possibility of tag names colliding.
• Routines: Routines are used to encapsulate executable code written in a 
single programming language.
Routines contain the executable code. Each program has a main routine 
that is the first routine to execute within a program. You can use logic, such 
as the Jump to Subroutine (JSR) instruction, to call other routines. You 
can also specify an optional program fault routine.
IMPORTANT
Currently, the translation tool converts only ladder instructions. SFC
and structured text files are not converted.
C# PDF Annotate Library: Draw, edit PDF annotation, markups in C#.
C#.NET: Add Text Box to PDF Document. Provide users with examples for adding text box to PDF and edit font size and color in text box field in C#.NET program.
add text box to pdf; how to insert text box in pdf file
C# WPF PDF Viewer SDK to annotate PDF document in C#.NET
Support to replace PDF text with a note annotation. Ability to insert a text note after selected text. Support to create a text box annotation to PDF file.
adding a text field to a pdf; adding text to a pdf form
24
RockwellAutomation Publication 1756-RM085C-EN-P - August 2011
Chapter2
As the translation tool converts the PLC-5 or SLC 500 logic, consider the 
program structures in the table below.    
Creating a Continuous Task A Logix controller supports one continuous task that operates in a self-triggered 
mode. It restarts itself after each completion. The continuous task operates as the 
lowest priority task in the controller (one priority level lower than the lowest 
periodic task). This means that all periodic tasks will interrupt the continuous 
task.
The translation tool automatically creates one continuous task named MainTask 
with a default watchdog setting of 500 msec. It contains a single program named 
MainProgram and uses a main routine named MainRoutine.
The translation tool creates a continuous task, but it uses the EVENT instruction 
to better simulate the PLC-5/SLC 500 behavior.
Creating Event Tasks
The translation tool also creates Event tasks for each program file configured in 
the PLC-5 Main Control Program (MCP).
To call each Event task, the translation tool creates EVENT instructions within 
the continuous task. It uses the PLC-5 status file to determine which is the first 
MCP and orders them accordingly, in the MainRoutine.
The SLC 500 processors do not contain an MCP, so ladder program 2, which is 
the main ladder program, becomes the main routine.
Conversionstep
Page
Creating a Continuous Task
24
Creating Event Tasks
24
Creating Periodic Tasksfor Selectable Timed
Interrupts (STIs)
25
Converting Input Interrupts (DIIs/PIIs)
25
Creating a StatusFile
25
IMPORTANT
For more information on Logix5000Controllers, see the Logix5000
Controllers Design Considerations Reference Manual,publication
1756-RM094F-EN-P
.NET PDF Document Viewing, Annotation, Conversion & Processing
Extract bookmark & outlines. Extract hyperlink inside PDF. PDF Write. Insert text, text box into PDF. Edit, delete text from PDF. Insert images into PDF.
how to add text to a pdf in acrobat; add text pdf
C# WPF Viewer: Load, View, Convert, Annotate and Edit PDF
Add text to PDF document. • Insert text box to PDF file. • Draw markups to PDF document. PDF Protection. • Add signatures to PDF document.
how to add text box to pdf document; adding text to a pdf document
RockwellAutomation Publication 1756-RM085C-EN-P - August 2011
25
Chapter 2
Creating Periodic Tasksfor
SelectableTimedInterrupts
(STIs)
Processor status word 31 contains the number of the ladder program, if any, that 
is designated for use as a selectable timed interrupt (STI). The translation tool 
creates a Periodic task and converts this program file named _filenumber_STI 
into its main routine.
The translation tool retrieves the STI interval from the processor status file. If 
necessary, the translation tool converts the interval to a 1 msec time base. After 
the conversion, you will have to edit the task properties to specify its priority.
Processor status bit S:2/1 allows enabling and disabling of the STI. A Logix 
controller does not support this. The translation tool generates a PCE instruction 
if it encounters any references to S:2/1.
Converting Input Interrupts
(DIIs/PIIs)
A Logix controller does not support input interrupts (DIIs or PIIs). If the PLC-5 
processor has a PII or the SLC 500 processor has a DII, the translation tool 
converts it to a subroutine in the Continuous task. You must edit the Logix5000 
logic to call the converted routine.
Processor status word 46 identifies the program file to be used as a DII or PII. 
The translation tool generates a PCE instruction and places it in the converted 
DII/PII routine.
Creating a Status File
Within the continuous task, the translation tool automatically creates a 
subroutine named StatusFile. This StatusFile contains GSV instructions to 
retrieve the following controller information.
• The controller local date and time in human readable format
• Fault information about the controller provided by the FAULTLOG 
object 
• Status for the Battery, bad or missing
• The physical hardware of the controller identified by the 
CONTROLLERDEVICE object 
• Status for Mode switch in REMOTE
• Status for Forces enabled and present
C# WinForms Viewer: Load, View, Convert, Annotate and Edit PDF
Add text to PDF document in preview. • Add text box to PDF file in preview. • Draw PDF markups. PDF Protection. • Sign PDF document with signature.
add text to pdf file online; how to insert a text box in pdf
VB.NET PDF - Annotate PDF with WPF PDF Viewer for VB.NET
annotation. Ability to insert a text note after selected text. transparency. Support to create a text box annotation to PDF file in .NET project. VB
how to enter text in pdf; how to insert text in pdf file
26
RockwellAutomation Publication 1756-RM085C-EN-P - August 2011
Chapter2
There are special considerations for some data in the status file as shown in the  
table that follows. 
This status data:
Is handledthis way:
MCP status data
The PLC-5 processor can support from 1-16 main control programs.EachMCP uses3 wordsof status
data. Statuswords 80-127 contain this information.
STI statusdata
The Enhanced PLC-5 processor can also support a selectable timed interrupt. The processor status
file containsthe interrupt time intervaland the number of the programfile to execute. Statusword
31 contains the program file number; statusword 30 containsthe interrupt time interval
DII/PIIstatus data
ThePLC-5 and SLC500 processors support an input interrupt.Statusword46 containsthe number of
the programfile to execute.
ALogix controllerdoes not support thisfeature. If the import/export file contains PIIstatusdata, the
PIIprogram file is converted and placed as a routine in the Continuous program.The conversion
processalso placesa PCE instruction in the converted routine to identifythat the routine was used
for a PII.
Indexed addressing
Status word 24 containsthe current address index used for indexed addressing.ALogix controller
doesnot use this index value.During the conversion,the processcreates a tag for S24:
S24 INT (Radix:=Decimal) := <value>
RockwellAutomation Publication 1756-RM085C-EN-P - August 2011
27
Chapter
3
Converting Data
Introduction
A Logix controller is based on a 32-bit architecture, as opposed to the 16-bit 
architecture of PLC-5 and SLC 500 processors. To provide seamless conversion 
and the best possible performance, many data table values are converted to 32-bit 
values (DINT values). This chapter provides detailed information about 
converting various file types. The table that follows shows the file conversions “at 
a glance” and where in the chapter you can find the conversion detail. 
PLC-5 or SLC
filetype
Logixarray
type
Radix
Comments
Page
O
INT
BINARY
28
I
INT
BINARY
28
S
INT
HEX
APCE instruction isgenerated for
each S address.
29
B
DINT
BINARY
The 16-bit value iscopied into the
32-bit location and sign-extended.
31
T
Eachaddressthat referencesaPRE
or ACCvalue generatesa PCE
instruction.
32
C
COUNTER
APCE instruction isgenerated
when overflow(.OV)andunderflow
(.UN)bit fieldsare encountered.
33
R
CONTROL
34
Rto Serial Port
Control
35
N
DINT
DECIMAL
The 16-bit value iscopied into the
32-bit location and sign-extended.
35
F
REAL
36
A
INT
HEX
36
D
DINT
HEX
The 16-bit value iscopied into the
32-bit location and zero-filled.
37
BT
MESSAGE
37
M0
INT
38
M1
INT
38
MG
MESSAGE
39
PD
PID
41
SC
Thisisa SFC statustype.
41
ST
STRING
The RSLogix 5000 structure
contains116-bit word (INT)and82
8-bit words (SINT).
42
CT
MESSAGE
44
RockwellAutomation Publication 1756-RM085C-EN-P - August 2011
28
How PLC-5 and SLC 500 files identify data table values
The PLC-5 and SLC 500 import/export files use DATA statements to identify 
file types, as shown in the example below.
DATA <file_reference>:<last_element_number>
<data_value>
The table that follows describes the fields in the example above:
How Logix files identify file types
The Logix import/export file uses tag declarations to initialize values. For 
example: 
Converting Input (I) and
Output (O) Data
The conversion process for I/O data tables tries to follow the layout of the input 
and output image tables in the PLC-5 and SLC 500 processor. To do this, the 
conversion process creates one, single-dimension array for I data and one, single-
dimension array for O data. The size of the input and output image tables in the 
PLC-5 or SLC 500 processor determines the size of these converted arrays.
The conversion process creates single-dimension, INT arrays for I and O files. 
The tags names are I and O, respectively. The number of elements in the 
converted array is the same as the number of elements in the original data table 
file.
This field:
Specifies the:
file_reference
file type
For example, N identifiesan integer file type.
last_element_number
size of the file
The conversion processusesthisvalue to determinethe number of
elementsto place in the arrayused for thisfile.
Forexample,DATAN7:9meansthat filenumber7 isan integer file
with 10 elements.
data_value
contents of the file
For example:
DATA N7:2
10 11 12
showsthatfile number7 isanintegerfilewith three elements.The
valuesof these elementsare:
N7:010
N7:111
N7:212
This data tablefile and
elements:
Couldconvert to:
Specifies:
F8 with 1 element
REAL:= 3.25
asingle,realvalue
N7 with 3 elements
DINT[3]={42,-56, 1090}
an integer arraywith three
elements
T4 with 2 elements
[2] := {{16#c0000000,1000,
910},{16#c0000000,3000,2550}
anarrayof two structures;each
structure hasthree members
RockwellAutomation Publication 1756-RM085C-EN-P - August 2011
29
Chapter 3
For example, in the ASCII text file:
The PLC-5 processor, SLC 500 processor, and Logix controllers use different 
addressing schemes for I/O data. For example:   
To preserve the original address, the conversion process creates alias tags based on 
the physical address. For example:
Converting the Status (S)
File Type
Status files are handled differently during the conversion depending on whether it 
is a PC5 or SLC file that is being translated.     
PC5 file translation
• The RSLogix tag name is S.
• RSLogix tag dimension is one more than the dimension specified after the 
colon in the Legacy DATA statement.
• Initial values follow the constant conversion rules.
This DATA statement:
Converts to:
DATA O:177
0X0000 0X0000 ...
...
tag O
type INT[128](Radix:= Binary) := {16#0000,...}
DATA I:037
0X0000 0X0000 ...
...
tag I
type INT[32](Radix:= Binary):= {16#0000,... }
Controller
I/O Addressing
PLC-5 processor
Base 8 (octal)
SLC 500 processor
Base 10 (decimal)
Logixcontroller
Base 10 (decimal)
Controller
Original Address
Converted Address
Alias TagName
PLC-5 processor
I:007
I[7]
I_007
O:010
O[8]
O_010
I:021/05
I[17].05
I_021_Bit05
O:035/15
O[29].13
O_035_Bit015
SLC 500 processor I:007
I[7]
I_007
O:010
O[10]
O_010
I:021/05
I[21].05
I_021_Bit05
O:035/15
O[35].15
O_035_Bit015
30
RockwellAutomation Publication 1756-RM085C-EN-P - August 2011
Chapter3
The number of elements in the converted array is the same as the number of 
elements in the original data table. For example, in the ASCII text file:
The table that follows shows some examples of  S addresses and their Logix 
equivalents. 
There are special considerations for some data in the status file as shown in the  
table that follows:  
SLC file translation
• The RSLogix tag name is S.
• RSLogix tag dimension is based off the number of initial values present.
• Initial values follow the constant conversion rules.
• If  legacy logic references the file type (S) with the number following, the 
number will be removed during the translation.
PC5 DATA statement:
Converts to:
DATAS:127
0X0000 0X0000 ...
...
S:INT[164] (Radix := Hex):= {16#0000,... };
Original Address
Converted Address
S:3
S[3]
S:1/15
S[1].15
S:24
S24
Status data:
How handled:
MCP status data
The PLC-5 processor can support from 1-16 main control programs.EachMCP uses3 wordsof status
data. Statuswords 80-127 contain this information.
STI statusdata
The Enhanced PLC-5 processor can also support a selectable timed interrupt. The processor status
file containsthe interrupt time intervaland the number of the programfile to execute. Statusword
31 contains the program file number; statusword 30 containsthe interrupt time interval
DII/PIIstatus data
ThePLC-5 and SLC500 processors support an input interrupt.Statusword46 containsthe number of
the programfile to execute.
ALogix controllerdoes not support thisfeature. If the import/export file contains PIIstatusdata, the
PIIprogram file is converted and placed as a routine in the Continuous program.The conversion
processalso placesa PCE instruction in the converted routine to identifythat the routine was used
for a PII.
Indexed addressing
Status word 24 containsthe current address index used for indexed addressing.ALogix controller
doesnot use this index value.During the conversion,the processcreates a tag for S24:
S24 INT (Radix:=Decimal) := <value>