RockwellAutomation Publication 1756-RM085C-EN-P - August 2011
41
Chapter 3
Converting the PID (PD)
File Type
A PD file is converted to a PID type tag.
The conversion process creates a single dimension array of PID structures for the 
PD file. The tag name is PDx (where x is the PLC-5 or SLC 500 data table file 
number). The number of elements in the converted array is the same as the 
number of elements in the original data table file. Each element in the array is a 
PID structure.
For example, in the ASCII text file:
The table that follows shows some PD addresses and their Logix equivalents:
Although the PID instruction has been translated, the PID instruction has many 
parameters that do not translate directly to RSLogix 5000. The translation must 
be verified.  
Converting SFC Status (SC)
Type
For the SC type, a UDT is created that mimics the file type structure of a SC so 
the data isn’t lost. Look for the PCE instructions that are created for all SC-
related statements, address references, and instructions. The table that follows 
shows the file comparisons:
This DATA statement:
Converts to:
DATA PD10:10
256 0 0 0 0 0
00 0 0 0 0
00.1 0 0 0 0
00 0 0 0 0
00 15 10 1 0
00 0 0 0 0
00 0 0 0 0
00
...
tag PD10
type PID10[11].1 :={536870912,0, 0,0,0, 0,0,
0,0,0, 0,0,0.1,0
0,0,0, 0,0,0,0,
0,0,0, 0,0,0,[0,
0,0,0, 0,0,0,0,
0,0,0, 0,0,0,0]}
...
Original Address
Converted Address
PD10:1
PD10[1]
PD10:1/15
PD10:1/EN
PD10:1.0/15
PD10[1].EN
PD10:1.2
PD10[1].SP
Word
Legacy Bit #
RSLogix5000UDT
Bit#
Mnemonic
Description
0
0
0
SA
0
1
1
FS
First Scan (SFC use)
0
2
2
LS
Last Scan (SFC use)
0
3
3
OV
Overflow
0
4
4
ER
Error
How to insert text box in pdf document - insert text into PDF content in C#.net, ASP.NET, MVC, Ajax, WinForms, WPF
XDoc.PDF for .NET, providing C# demo code for inserting text to PDF file
add text to pdf in acrobat; adding text to a pdf
How to insert text box in pdf document - VB.NET PDF insert text library: insert text into PDF content in vb.net, ASP.NET, MVC, Ajax, WinForms, WPF
Providing Demo Code for Adding and Inserting Text to PDF File Page in VB.NET Program
add text to pdf file reader; add text block to pdf
42
RockwellAutomation Publication 1756-RM085C-EN-P - August 2011
Chapter3
Converting the ASCII String
(ST) File Type
ASCII string files are handled differently during the conversion depending on 
whether it is a PC5 or SLC file that is being translated. The size of each structure 
type is equivalent. However, there are some data type differences. The tables that 
follow compare the ASCII string structure with the RSLogix 5000 string 
structure.  
The data type differences are described below.
PC5 file translation
For this file format: 
• The strings’ data values remain as strings.  
• The LEN is determined when the RSLogix 5000 tag is initialized.
0
5
5
DN
Done
1
NA
NA
BASE
2
NA
NA
PRE
3
NA
NA
TIM
This DATA statement:
Converts to:
DATASC10:0
0X003F 0 0
...
SC10 : SC_UDT[1] := { {16#0000003F, 0,0,…},...};
Word
Legacy Bit #
RSLogix5000UDT
Bit#
Mnemonic
Description
Legacy ASCII StringStructure
Legacy ASCIIstring structures are made up of 42 16-bit words
Word
Mnemonic
Description
0
LEN
Thiselement of the structure
containsthelength of the string
1-41
N/A
These 41 wordscontain the
stringdata.Two ASCIIbytesare
stored in each word.
RSLogix 5000 String Structure
The RSLogix5000 structure contains 1 16-bit word (INT) and 82 8-bit words (SINT)
Mnemonic
Type
Description
LEN
INT
Thisisthe length of the string
STR
SINT [82]
Each SINT containsa single
ASCIIcharacter.
VB.NET PDF Text Box Edit Library: add, delete, update PDF text box
Extract Field Data. Data: Auto Fill-in Field Data. Field: Insert, Delete, Update Highlight Text. Add Text. Add Text Box. Drawing Markups. PDF Print. Work with
add text boxes to a pdf; add text pdf file
C# PDF Text Box Edit Library: add, delete, update PDF text box in
DNN (DotNetNuke), SharePoint. Provide .NET SDK library for adding text box to PDF document in .NET WinForms application. A web based
adding text to pdf in acrobat; how to add text to pdf
RockwellAutomation Publication 1756-RM085C-EN-P - August 2011
43
Chapter 3
For example, in the ASCII text file:
SLC file translation
For this file format:
• The ASCII strings are broken apart. In other words, a data statement is 
created for each ASCII string, not each ASCII string file.
• The translation tool then creates a single dimension tag.
• These data statements do not display the <# of Elements> after the <File 
Reference>.  In this case,  this integer represents an actual element number.  
The data values contain integers. The first value encountered is the byte 
length in decimal format. The remaining values are shown as 41 16- bit 
words in hexadecimal format.
For example, in the ASCII text file:
The table that  follows is a convenient summary of the ladder instructions 
specifically related to strings.      
This DATA statement:
Converts to:
DATA ST15::1
...
ST15 : STRING[2]:= {{5,{72,101,108,108,111,0,...0}},
{5, {84,104,101,114,101,0,...0}} };
Note:
No emptyspacesare allowed in the initialization of
structures. Therefore the STR elementofthe tag isshown
with zerospadding its contents.
This DATA statement:
Converts to:
DATA ...ST15:000
50X4865 0X6C6C 0X6F00
0X0000 0X0000 ...
DATA ...ST15:001
50X5468 0X6572 0X6500
0X0000 0X0000 0X0000
ST15 : STRING[2]:= {{5,{72,101,108,108,111,0,...0}},
{5, {84,104,101,114,101,0,...0}} };
Note:
No emptyspacesare allowed in the initialization of
structures.Therefore,theSTRelement of the tagisshown
with zerospadding its contents.
Description
PLC-5 Instruction
SLC500 Instruction
Logix Instruction
string to integer conversion
ACI
ACI
STOD
integer to string conversion
AIC
AIC
DTOS
string to real conversion
na
na
STOR
realto string conversion
na
na
RTOS
string compare for equal
ASR
ASR
EQU
string compare for not equal
na
na
NEQ
string compare for greater than
na
na
GRT
string compare for greater than or equal
na
na
GEQ
string compare for less than
na
na
LES
string compare for less than or equal
na
na
LEQ
C# PDF Annotate Library: Draw, edit PDF annotation, markups in C#.
installed. Support to add text, text box, text field and crop marks to PDF document. Able class. C#.NET: Add Text Box to PDF Document. Provide
how to insert text in pdf reader; adding text to a pdf in preview
C# WPF PDF Viewer SDK to annotate PDF document in C#.NET
Ability to insert a text note after selected text. Support to create a text box annotation to PDF file. C#.NET WPF PDF Viewer Library: Annotate PDF Document.
add text field to pdf acrobat; adding text to pdf document
44
RockwellAutomation Publication 1756-RM085C-EN-P - August 2011
Chapter3
Converting the ControlNet
(CT) File Type
The CT type appears only in the PC5 files. The initial values appearing in the 
Legacy Data statement are first partitioned into sets of 22 individual elements. 
The table below shows the file comparisons
.
For each partition of the CT array, a new RSLogix MESSAGE structure is 
created. This structure’s name is formed by concatenating the Legacy filename, 
and the Legacy element index separated by an underscore.
The MessageType and LocalTag attributes of the MESSAGE structure are set 
later when a CIO instruction that uses this CT element as the fourth operand is 
encountered. Then, the fifth operand is used to set the LocalTag.
append on string to another
ACN
ACN
CONCAT
move charactersfrom one string to another
AEX
AEX
MID
search one string for a matching string
ASC
ASC
FIND
delete charactersfrom a string
na
na
DELETE
insert a string into another string
na
na
INSERT
convert a string to all uppercase letters
na
na
UPPER
convert a string to all lowercase letters
na
na
LOWER
Description
PLC-5 Instruction
SLC500 Instruction
LogixInstruction
Word
Legacy
Bit #
RSLogix
5000 Bit #
Legacy
Mnemonic
RSLogix
5000 Mnemonic
Description
0
15
31
TO
TO
0
14
30
EN
EN
enable
0
13
29
ST
ST
0
12
28
DN
DN
done
0
11
27
ER
ER
error
0
10
26
CO
CO
0
9
25
EW
EW
1
na
na
ERR
ERR
error value
2
na
na
RLEN
REQ_LEN
length
3
na
na
DLEN
DN_LEN
position
4
na
na
FILE
RemoteIndex
5
na
na
ELEM
RemoteElement
.NET PDF Document Viewing, Annotation, Conversion & Processing
Extract hyperlink inside PDF. PDF Write. Insert text, text box into PDF. Edit, delete text from PDF. Insert images into PDF. Edit, remove images from PDF.
add text pdf reader; add text to pdf in preview
C# WPF Viewer: Load, View, Convert, Annotate and Edit PDF
Highlight PDF text in preview. • Add text to PDF document. • Insert text box to PDF file. • Draw markups to PDF document. PDF Protection.
adding text box to pdf; adding text pdf file
RockwellAutomation Publication 1756-RM085C-EN-P - August 2011
45
Chapter 3
Converting Constant Values The conversion process maintains constants. The format of converted constants 
varies slightly to conform with Logix format requirements.
For example:
Converting Indirect
Addresses
Indirect addressing is when a part of an address is replaced with a reference to 
another address. The PLC-5 and SLC 500 processors can use an address 
reference to define these address parts:
• file number
• word or element number
• bit number (only for B type addresses)
The conversion tool supports indirect addresses, except when the indirection is 
an array specification. Indirect array specifications are converted to aliases.
For example:
Constant type
PLC-5/SLC500 example
Conversion
Conversionrule
Integer
&N49
-49
49
-49
remove &N, if present
copy remainder of constant
Binary
&B00110001
2#00110001
replace &B with 2#
copy remainder of constant
ASCII
&A1
&Amx
16#0031
16#6D78
convert to hexconstant
Hex
&H0031
0x0032
0X0033
16#0031
16#0032
16#0033
replace &H,0x,or 0X with 16#
copy remainder of constant
BCD
&D0049
16#0031
convert to hexconstant
Octal
&O61
8#61
replace &Owith 8#
copy remainder of constant
Float
-12.34E-12
3.45
-12.34E-12
3.45
this syntaxiscompletelycompatible
copy the constant asis
Type
PLC-5/SLC500 example
Conversion
Conversion rule
File number
N[N7:0]:5
na
The conversion toolcannot convert an indirect file number.
APCE instruction isgenerated.
Word or element
number
N12:[N7:0]
N12[N7_0]
N7:0 translatesto arraytag N7[0].
AliasN7_0 replacesthe indirect address.
N12:[T4:1.PRE]
N12[T4_1_PRE]
T4:1.PRE translatesto arraytag T4[1].PRE.
AliasT4_1_PRE replacesthe indirect address.
Bit number
B3/[N7:0]
B3[N7_0 / 16].[N7_0 AND 15]
The conversion process must convert tothe correct word
and bit within that word.
AliasN7_0 replace the indirect address.
C# WinForms Viewer: Load, View, Convert, Annotate and Edit PDF
Highlight PDF text. • Add text to PDF document in preview. • Add text box to PDF file in preview. • Draw PDF markups. PDF Protection.
add text to pdf online; how to add text field to pdf
VB.NET PDF - Annotate PDF with WPF PDF Viewer for VB.NET
Ability to insert a text note after selected text. Support to create a text box annotation to PDF file in .NET VB.NET WPF PDF Viewer: Annotate PDF Document.
add text box in pdf; adding text to pdf in preview
46
RockwellAutomation Publication 1756-RM085C-EN-P - August 2011
Chapter3
Converting indirect addressing on the file number
Indirect addressing on the file number can actually be implemented after the 
conversion process if the original data table files are consecutive. For example, a 
PLC-5 processor has 5 program files with heat treating “recipes” in them.
In the ASCII text file:
DATA N10:5
0, 5, 350, 15, 200, 60
DATA N11:5
1, 10, 400, 25, 300, 15
DATA N12:5
2, 5, 500, 20, 350, 90
DATA N13:5
3, 50, 300, 120, 150, 90
DATA N14:5
4, 10, 700, 30, 500, 240
These data files convert to:
N10 : DINT[6] (Radix:=Decimal):=[0, 5, 350, 15, 200, 60];
N11 : DINT[6] (Radix:=Decimal):=[1, 10, 400, 25, 300, 15];
N12 : DINT[6] (Radix:=Decimal):=[2, 5, 500, 20, 350, 90];
N13 : DINT[6] (Radix:=Decimal):=[3, 50, 300, 120, 150, 90];
N14 : DINT[6] (Radix:=Decimal):=[4, 10, 700, 30, 500, 240];
Use a text editor to modify these integer files into a two-dimensional array:
RECIPES : DINT[6, 6] (Radix:=Decimal):=[0, 5, 350, 15, 200, 60,
1, 10, 400, 25, 300, 15,
2, 5, 500, 20, 350, 90,
3, 50, 300, 120, 150, 90,
4, 10, 700, 30, 500, 240];
Element
Description
0
Recipe number
1
Heat segment 1:time in minutes
2
Heat segment 1:temperature in F
°
3
Heat segment 2:time in minutes
4
Heat segment 2:temperature in F
°
5
Roomtemperature cooling time in minutes
RockwellAutomation Publication 1756-RM085C-EN-P - August 2011
47
Chapter 3
Assume that there is an indirect address reference to N[N7:0]:0 to read the recipe 
number. In the converted project, use RECIPES[N7_0, 0], where N7_0 is the 
translated form of N7:0. You have to modify the bounds checking because the 
original file numbers ranged from 10 to 14, but the first index in the two-
dimensional array ranges from 0 to 4.
Converting Indexed
Addresses
Indexed addresses in the PLC-5 and SLC 500 processors are when a # character 
precedes the address.
Addresses controlled by the processor status word S:24
The processor status word S:24 contains the current index value to add to an 
address reference. The conversion process adds the value of S:24 to an indexed 
values it converts and places a PCE instruction in the output import/export file.
For example:
Addresses that specify data in files (Logix arrays)
Indexed addresses are also used with the file instructions to operate on files of 
data. These instruction use a CONTROL structure to determine the index value 
- the current position within the file.
A Logix controller stores data in arrays, rather than files. Indexed addresses for 
PLC-5 and SLC 500 file instructions are converted to array tags, without adding 
the value of status word S:24.
For example:
This address:
Converts to:
#N7:2
N7[2 + S24]
This instruction:
Converts to:
AVE #N10:0 N11:0 R6:0 6 0
AVE(N10[0],0,N11[0],R6[0],6,0)
48
RockwellAutomation Publication 1756-RM085C-EN-P - August 2011
Chapter3
Alias Creation Rules
The translation tool creates RSLogix 5000 alias declarations following specific 
rules. 
• Aliases are literals assigned to specific tag references. These literals are then 
used in place of the associated tag reference. 
• The translation tool creates alias declarations based upon the content of 
the legacy documentation import/export file.
• Aliases are also created when the file number, word offset or bit offset of an 
address is indirect.  
• Aliases may be created when you choose to have the translation tool create 
aliases during the translation process. 
• Alias declarations are always associated with a tag declaration. If a tag 
declaration created by the translation tool has an associated radix, then any 
aliases based in that tag must be assigned the same radix. 
Converting Symbols
The conversion process converts a symbol to a description. The translation 
wizard gives you the option to have the system create alias tags for symbols.   
No aliases created (default)
The translation tool converts symbols without aliases being created, as follows:  
The PLC-5 and SLC 500 import/export file uses SYM statements to 
identify symbols:
SYM <address_reference> <literal>
The table that follows describes the fields in the example above.
The PLC-5 and SLC 500 processors support some symbol formats that are not 
supported in a Logix controller. In these cases, the conversion process modifies 
the symbol text.
This field:
Specifies the:
address_reference
address
The conversion process createsa tag to correspond to the actual
address.
literal
symboltext
The conversion process convertsthe symboltext to a description.
RockwellAutomation Publication 1756-RM085C-EN-P - August 2011
49
Chapter 3
The table below shows how the conversion process modifies the symbol text.
If an address reference has both a symbol and an address comment, the conversion 
process concatenates the symbol to the end of the address comment.
Aliases created
If you choose to have the translation tool create aliases, the translation process  
will be the same but an RSLogix 5000 alias is generated with the SYM “name” as 
the (alias) tag name and the <address reference> is the alias reference.  
Generating alias tags uses up memory in the Logix 5000 processor.
The table that follows shows the difference between the symbol conversion  
options.
Logix tag:
SYM statement:
Modifiedtag:
N7 :INT[9](Radix:= Decimal)
SYM N7:2 Kitty
N7 :INT[9](Radix:= Decimal, Comment[2]:=”Kitty”)
B3 :INT[5] (Radix:= Binary)
SYM B3:4/5 Puppy
B3 :INT[5] (Radix:= Binary,Comment[4].5:=”Puppy”)
T4 :[2]
SYM T4:0 Ducky
SYM T4:1 2ndDuck
T4 :[2] (Comment[0]:=”Ducky”,
Comment[1]:=”_2ndDuck”)
na
SYM N[N7:0]:0 Pig
Thisaddressformat isnot supported in the conversion process.
No tag is created.
Associated Tag
Symbol Statement
Symbol as Tag Comment
Symbol as Alias
N7 :INT[9](Radix:= Decimal);
SYM N7:2 Kitty
N7 : INT[9](Radix := Decimal,
Comment[2]=”Kitty”);
KittyOFN7[2]
B3 :INT[5] (Radix:= Binary);
SYM B3:4/5 Puppy
B3 :INT[5](Radix:= Binary,
Comment[5]=”Puppy”);
PuppyOFB3[4].5
T4 :[2];
SYM T4:0 Ducky
SYM T4:1 2dnDuck
T4 : [2](Comment[0]=”Ducky”,
Comment[1] = “_2ndDuck”;
DuckyOFT4[0]
_2ndDuck OF T4[1]
N/A
SYM N[N7:0]:0 Piglet
N/A
No aliaswillbe created.
Unsupported addressformat
50
RockwellAutomation Publication 1756-RM085C-EN-P - August 2011
Chapter3
Converting Address
Comments
The conversion process converts address comments to descriptions.
The PLC-5 and SLC 500 import/export file uses AC statements to identify 
address comments:
AC [formatting_keyword] <address_reference> 
<“comment_text”>Where:
For example:
If an address reference has both a symbol and an address comment, the conversion 
process concatenates the symbol to the end of the address comment.
This field:
Specifies the:
formatting_keyword
format of the comment text.
The PLC-5 and SLC 500 processors support formatting commands
forcommenttext.Theconversionprocessignoresthese formatting
keywords.
address_reference
address
The conversion process createsa tag to correspond to the actual
address.
literal
comment text
The conversion process convertsthe comment text to
adescription.
Logixtag:
AC statement:
Modified tag:
N7 : INT[9](Radix := Decimal)
ACN7:2 Kitty
N7 : INT[9](Radix := Decimal,Comment[2]:=”Kitty”)
B3 :INT[5](Radix:= Binary)
ACB3:4/5 Puppy
B3 :INT[5](Radix:= Binary, Comment[4].5:=”Puppy”)